Bryant 310JAV, 310AAV warranty Position of Igniter to Burner, Cleaning Heat Exchanger

Page 34

e.Remove blower wheel from housing.

f.Clean wheel and housing.

12.Reassemble motor and blower by reversing steps 11f, finish- ing with 11a. Be sure to reattach ground wire to the blower housing.

13.Verify that blower wheel is centered in blower housing and set screw contacts the flat portion of the motor shaft. Loosen set screw on blower wheel and reposition if necessary.

14.Spin the blower wheel by hand to verify that the wheel does not rub on the housing.

15.Reinstall blower assembly in furnace.

16.Reinstall control box assembly in furnace.

Heating fan speed(s) MUST be adjusted to provide proper air temperature rise as specified on the rating plate. Failure to adjust the heating speed(s) may shorten heat exchanger life. Recommended operation is at the midpoint of the rise range or slightly above. Refer to SET TEMPERATURE RISEunder START-UP, ADJUSTMENT, and SAFETY CHECK.

NOTE: Refer to Table 7 for motor speed lead relocation if leads were not identified before disconnection.

17.Reconnect blower leads to furnace control. Refer to furnace wiring diagram, and connect thermostat leads if previously disconnected. (See Fig. 39.)

18.To check blower for proper rotation: a. Turn on electrical supply.

Blower access door switch opens 115-v power to furnace control. No component operation can occur. Caution must be taken when manually closing this switch for service purposes. Failure to follow this warning could result in electrical shock, personal injury, or death.

b. Manually close blower access door switch.

NOTE: If thermostat terminals are jumpered at the time blower access door switch is closed, blower will run for 90 sec before beginning a heating or cooling cycle.

c.Perform component self-test as shown at the bottom of the SERVICE label, located on the front of blower access door.

d.Verify blower is rotating in the correct direction.

19.If furnace is operating properly, RELEASE BLOWER AC- CESS DOOR SWITCH. Replace blower access door and remove any jumpers or reconnect any disconnected thermostat leads.

20.Downflow or horizontal furnaces with vent pipe through furnace only:

a.Install and connect short piece of vent pipe inside furnace to existing vent.

b.Connect vent connector to vent elbow.

21.Reinstall casing door.

22.Turn on gas supply and cycle furnace through one complete heating and cooling cycle. Verify the unit temperature rise as shown in Adjustments Section. Adjust temperature rise as shown in Adjustments Section. If outdoor temperature is below 70° F, turn off circuit breaker to outdoor unit before running furnace in the cooling cycle. Turn outdoor circuit breaker on after completing cooling cycle.

CLEANING HEAT EXCHANGER

The following steps should be performed by a qualified service technician:

NOTE: If the heat exchangers get a heavy accumulation of soot and carbon, they should be replaced rather than trying to clean them thoroughly. A build-up of soot and carbon indicates that a problem exists which needs to be corrected, such as improper adjustment of manifold pressure, insufficient or poor quality combustion air, incorrect size or damaged manifold orifice(s), improper gas, or a restricted heat exchanger. Action must be taken to correct the problem.

If it becomes necessary to clean the heat exchangers because of dust or corrosion, proceed as follows:

1.Turn OFF gas and electrical power to furnace.

2.Remove outer access door.

3.Disconnect vent connector from furnace vent elbow.

4.For downflow or horizontal furnace having an internal vent pipe, remove internal vent pipe within the casing.

5.Disconnect wires to the following components. Mark wires to aid in reconnection of:

a.Draft safeguard switch.

b.Inducer motor.

c.Pressure switch(es).

d.Limit overtemperature switch.

e.Gas valve.

f.Hot surface igniter.

g.Flame-sensing electrode

h.Flame rollout switches.

i.Remove NOx baffles on low NOx models.

6.Remove screws that fasten the collector box assembly to the cell panel. Be careful not to damage the collector box. Inducer assembly and elbow need not be removed from collector box.

7.Disconnect gas line from gas manifold.

8.Remove the 4 screws that attach the burner assembly to the cell panel. The gas valve and individual burners need not be removed from support assembly.

NOTE: Be very careful when removing burner assembly to avoid breaking igniter. See Fig. 44 and 45 for correct igniter location.

9/32”

11/32”

A02150

Fig. 44—Position of Igniter to Burner

33

Image 34
Contents 310AAV/JAV Induced-Combustion 4-Way Multipoise Furnace Table of Contents → -Dimensional Drawing Safety ConsiderationsInstallation → -Clearances to CombustiblesIntroduction DimensionsCodes and Standards → Electrostatic Discharge ESD Precautions Procedure LocationAIR for Combustion and Ventilation Location Relative to Cooling EquipmentConfined Space Minimum Free Area of Combustion Air OpeningUnconfined Space BtuhUpflow Installation Downflow InstallationInstallation Ventilation from OutdoorsFilter Arrangement Horizontal InstallationAir Ducts Floor and Plenum Opening Dimensions Ductwork Acoustical Treatment Opening Dimensions→ -Duct Flanges Furnace Plenum Opening Floor Opening Casing→ -Horizontal Unit Suspension Supply AIR Connections17 3/4″ Return AIR ConnectionsGas Piping 22″Upflow Return Air Configurations and Restrictions → a-Right Side Gas Entry Example → -Maximum Capacity of PipeNominal Length of Pipe FT Iron Internal Diameter Size → -Electrical Data WiringFor Power Cord Installation BOX RelocationBOX Cover Installation For BX Cable InstallationAccessories Venting Nscngpic Carbon Monoxide Poisoning HazardNgpic General Venting Requirements Masonry Chimney RequirementsVent Internal Area of Chimney Additional Venting Requirements START-UP, ADJUSTMENT, and Safety CheckAppliance Application Requirements Sidewall VentingChimney Inspection Chart Adjustments Start-Up ProceduresExample 88,000 Btuh Input Furnace Installed AT 4300 FT See Venting Notes on Horizontal Left Application-Vent Elbow Left Horizontal Left Application-Vent Elbow Right Then UpHorizontal Right Application-Vent Elbow PCB Speed Selection Altitude Derate Multipler for U.S.AAltitude Percent Derate Multiplier Factor Check Safety Controls GAS Rate CU FT/HRElectrical Controls and Wiring ChecklistService and Maintenance Procedures IntroductionService Label Care and MaintenanceBlower Motor and Wheel Cleaning AND/OR Replacing AIR FilterFilter Size Information Furnace Filter Quantity and Size Casing WidthCleaning Heat Exchanger Position of Igniter to BurnerCleaning Heat Exchanger Cell Sequence of OperationWiring Diagrams TroubleshootingAltitude 675 725750 5001 775 800 6000 825 850 875 900 700 6001 725 750 7000 775 800 825 8509001 10,000775 800 900 925 950 975850 3000 875 900 Canada 925 875 900 925 950750 5001 775 800 6000 825 850 875 900 600 9001 625 650 10,000 675 700 725 Troubleshooting Guide Blocked vent switch used in Chimney Adapter Kit Copyright 2002 Carrier Corporation
Related manuals
Manual 52 pages 27.61 Kb

310JAV, 310AAV specifications

The Bryant 310AAV and 310JAV are high-efficiency air conditioning and heating systems designed for residential and light commercial applications. These models embody Bryant's commitment to delivering reliable comfort solutions while prioritizing energy efficiency and performance.

One of the standout features of the Bryant 310AAV and 310JAV is their impressive Seasonal Energy Efficiency Ratio (SEER) ratings. The higher the SEER, the more efficient the unit is in using electricity to cool your space. The Bryant 310AAV boasts a SEER rating of up to 16, while the 310JAV offers a slightly lower rating. This efficiency translates into cost savings on monthly energy bills while ensuring indoor comfort throughout the year.

Both models utilize advanced technologies, including two-stage heating and cooling capabilities. This means that the systems can adjust their operation based on the heating or cooling needs of a space, providing optimal temperature control while reducing energy waste. The two-stage operation also contributes to quieter operation levels, making these units suitable for residential settings where noise is a concern.

The 310AAV and 310JAV are equipped with variable-speed compressors, which further enhance their efficiency and comfort levels. The variable-speed technology allows the system to operate at different speeds, ensuring consistent temperature management and reducing the frequency of on-and-off cycling. This leads to steadier indoor temperatures and improved humidity control.

In addition to their performance features, Bryant places a strong emphasis on durability and dependability. The units are constructed with high-quality materials that are designed to withstand various environmental conditions. Features such as a weather-resistant cabinet and an efficient coil design help protect the units from wear and tear, ensuring long-lasting performance.

The implementation of environmentally friendly refrigerant options is another characteristic that demonstrates Bryant's commitment to sustainability. Both the 310AAV and 310JAV utilize R-410A refrigerant, which has a lower environmental impact compared to older refrigerants, aligning with modern standards for eco-friendly HVAC systems.

Overall, the Bryant 310AAV and 310JAV represent a blend of efficiency, advanced technology, and durability. With their attractive SEER ratings, two-stage operation, variable-speed capabilities, and commitment to sustainability, these models stand out as excellent choices for homeowners and businesses looking to enhance their heating and cooling solutions while keeping energy consumption in check. Whether for residential comfort or light commercial use, these Bryant units promise reliability and performance for years to come.