|
|
|
|
| 1 SQ IN. |
|
| |
|
| DUCTS |
|
| PER 4000 |
|
| |
|
|
|
| BTUH* |
|
| ||
|
| TO |
|
|
|
| ||
|
|
|
|
|
|
| ||
| OUTDOORS |
|
|
|
|
| ||
12″ MAX |
| D |
| 12″ |
|
| ||
1 SQ IN. |
|
| VENT |
| MAX |
|
| |
A |
|
|
|
|
| |||
PER 2000 | AIR | THROUGH |
| F |
|
| ||
BTUH* |
| ROOF |
| 1 SQ IN. |
|
| ||
|
| DUCTS |
|
|
|
| ||
|
|
|
|
| PER |
|
| |
|
|
|
|
| 4000 |
|
| |
|
|
| CONFINED SPACE |
| BTUH* |
|
| |
DUCTS |
|
|
| OUTDOORS |
|
| ||
TO |
|
|
|
|
|
|
| |
OUTDOORS |
|
|
|
|
|
| A02098 | |
|
|
|
|
|
|
| ||
|
|
|
|
| 1 SQ IN. |
| Fig. | |
|
|
|
|
| PER |
| ||
|
|
|
|
| 4000 |
|
| |
1 SQ IN. |
|
|
|
| BTUH* |
|
| |
B |
|
| E | G |
|
| ||
PER 2000 |
|
|
|
| ||||
BTUH* |
|
|
|
| 12″ |
|
| |
″ |
|
| C |
| MAX | SIDE RETURN AIR INLET | ||
12 MAX |
|
|
| |||||
|
|
|
| 12″ MAX | These furnaces are shipped with bottom closure panel installed in | |||
|
|
|
|
|
| |||
|
|
|
|
|
| bottom | ||
| AIR DUCTS | DUCT |
| 1 SQ IN. | only side return air is used. | |||
|
|
|
| → NOTE: Side | ||||
|
|
| TO |
| PER 4000 | |||
|
|
| OUTDOORS | BTUH* | most HORIZONTAL configurations. Do not use side | |||
*Minimum dimensions of 3 in. |
|
|
| |||||
|
|
| openings in DOWNFLOW configuration. | |||||
NOTE: Use any of the following |
|
|
| LEVELING LEGS (IF DESIRED) | ||||
combinations of openings: |
|
| ||||||
A & B C & D D & E F & G |
| A02165 | In upflow position with side return inlet(s), leveling legs may be | |||||
|
|
|
|
| ||||
|
|
|
|
| used. (See Fig. 10.) Install | |||
Fig. | ||||||||
| Ventilation from Outdoors | NOTE: Bottom closure must be used when leveling legs are used. | ||||||
|
|
|
|
|
| |||
|
|
|
|
|
| It may be necessary to remove and reinstall bottom closure panel | ||
|
|
|
|
|
| to install leveling legs. To remove bottom closure panel, see Fig. | ||
c. If combustion | air is taken from the | outdoors through a | 9. |
| ||||
To install leveling legs: | ||||||||
single opening or duct (horizontal or vertical) commencing | ||||||||
1. Position furnace on its back. Locate and drill a hole in each | ||||||||
within 12 in. of the top of the confined space, the opening | ||||||||
| bottom corner of furnace. (See Fig. 10.) | |||||||
and duct must have at least 1 sq in. of free area per 3000 |
| |||||||
Btuh of the total input for all equipment within the confined | 2. | For each leg, install nut on bolt and then install bolt and nut in | ||||||
space and not less than the sum of the areas of all vent |
| hole. (Install flat washer if desired.) | ||||||
connectors in the confined space. Equipment clearances to | 3. Install another nut on other side of furnace base. (Install flat | |||||||
the structure shall be at least 1 in. from the sides and back | ||||||||
| washer if desired.) | |||||||
and 6 in. from the front of the appliances. See Table 2 and |
| |||||||
4. Adjust outside nut to provide desired height, and tighten inside | ||||||||
Fig. 8. |
|
|
|
|
| |||
|
|
|
|
|
| nut to secure arrangement. | ||
When ducts are used, they must be of the same cross sectional area |
| |||||||
5. Reinstall bottom closure panel if removed. | ||||||||
as the free area of the openings to which they connect. The | ||||||||
Step | ||||||||
minimum dimension of ducts must not be less than 3 in. | ||||||||
|
| INSTALLATION |
|
| NOTE: For downflow applications, this furnace is approved for | |||
|
|
|
| use on combustible flooring when any one of the 3 accessories are | ||||
Step |
|
|
| used: | ||||
|
|
|
|
| ||||
BOTTOM RETURN AIR INLET |
|
| • | Special Base, KGASB | ||||
|
|
|
| |||||
These furnaces are shipped with bottom closure panel installed in | • Cased Coil Assembly Part No. CD5 or CK5 | |||||||
|
| |||||||
bottom | • Coil Box Part No. KCAKC | |||||||
bottom return | air is | used. To | remove | bottom closure panel, | 1. Determine application being installed from Table 3. | |||
|
|
|
|
|
|
perform the following: | 2. | Construct hole in floor per Table 3 and Fig. 11. | ||
1. | Tilt or raise furnace and remove 2 screws holding bottom filler | |||
3. | Construct plenum to dimensions specified in Table 3 and Fig. | |||
| panel. (See Fig. 9.) | |||
|
| 11. | ||
2. | Rotate bottom filler panel downward to release holding tabs. |
| ||
4. | If downflow subbase, KGASB is used, install as shown in Fig. | |||
3. | Remove bottom closure panel. | |||
| 12. If Coil Assembly Part No. CD5 or CK5 or Coil Box Part | |||
|
|
| ||
4. | Reinstall bottom filler panel and screws. |
| No. KCAKC is used, install as shown in Fig. 13. |
8