Empire Products RB) GAS Supply, Installing a New Main Gas Cock, Checking Manifold Pressure

Page 7

GAS SUPPLY

Check all local codes for requirements, especially for the size and type of gas supply line required.

Recommended Gas Pipe Diameter

 

Pipe Length

Schedule 40 Pipe

Tubing, Type L

(feet)

Inside Diameter

Outside Diameter

 

Nat.

L.P.

Nat.

L.P.

0-10

1/2"

3/8"

1/2"

3/8"

 

12.7mm

9.5mm

12.7mm

9.5mm

10-40

1/2"

1/2"

5/8"

1/2"

 

12.7mm

12.7mm

15.9mm

12.7mm

40-100

1/2"

1/2"

3/4"

1/2"

 

12.7mm

12.7mm

19mm

12.7mm

100-150

3/4"

1/2"

7/8"

3/4"

 

19mm

12.7mm

22.2mm

19mm

Note: Never use plastic pipe. Check to confirm whether your local codes allow copper tubing or galvanized.

Note: Since some municipalities have additional local codes, it is always best to consult your local authority and installation code.

Installing a New Main Gas Cock

Each appliance should have its own manual gas cock.

A manual main gas cock should be located in the vicinity of the unit. Where none exists, or where its size or location is not adequate, contact your local authorized installer for installation or relocation.

Compounds used on threaded joints of gas piping shall be resistant to the action of liquefied petroleum gases. The gas lines must be checked for leaks by the installer. This should be done with a soap solution watching for bubbles on all exposed connections, and if unexposed, a pressure test should be made.

Never use an exposed flame to check for leaks.Appliance must be disconnected from piping at inlet of control valve and pipe capped or plugged for pressure test. Never pressure test with appliance connected; control valve will sustain damage!

A gas valve and ground joint union should be installed in the gas line upstream of the gas control to aid in servicing. It is required by the National Fuel Gas Code that a drip line be installed near the gas inlet. This should consist of a vertical length of pipe tee connected into the gas line that is capped on the bottom in which condensation and foreign particles may collect.

Figure 1

The use of the following gas connectors is recommended:

ANS Z21.24 Appliance Connectors of Corrugated Metal Tubing and Fittings

ANS Z21.45 Assembled Flexible Appliance Connectors of Other Than All-Metal Construction

The above connectors may be used if acceptable by the authority having jurisdiction. The state of Massachusetts requires that a flexible appliance connector cannot exceed three feet in length.

Pressure Testing of the Gas Supply System

1.To check the inlet pressure to the gas valve, a 1/8" (3.175mm) N.P.T. plugged tapping, accessible for test gauge connection, must be placed immediately upstream of the gas supply connection to the appliance.

2.The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa).

3.The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa).

Attention! If one of the procedures results in pressures in excess of 1/2 psig (14" w.c.) (3.5 kPa) on the appliance gas valve, it will result in a hazardous condition.

Checking Manifold Pressure

Both Propane and Natural gas valves have a built-in pressure regulator in the gas valve. Natural gas models will have a manifold pressure of approximately 3.5" w.c. (.871kPa) at the valve outlet with the inlet pressure to the valve from a minimum of 4.5" w.c. (1.120kPa) for the purpose of input adjustment to a maximum of 10.5" w.c. (2.614kPa) Propane gas models will have a manifold pressure approximately 10.0" w.c. (2.49kPa) at the valve outlet with the inlet pressure to the valve from a minimum of 11.0" w.c. (2.739kPa) for the purpose of input adjustment to a maximum of 13.0" w.c. (3.237kPa).

A1/8" (3.175mm) N.P.T. plugged tapping, accessible for test gauge connection, is located on the outlet side of the gas control.

12425-7-0406

Page 7

Image 7
Contents Installation Instructions Table of Contents This is a Heating Appliance Important Safety InformationLP-GAS Warning Odor Safety Information for Users of LP-GASIntroduction SpecificationsOval all parts purchase locally Recommended Vent ConfigurationInsulated Vent Enclosure Checking Manifold Pressure Installing a New Main Gas CockPressure Testing of the Gas Supply System GAS SupplyROUGH-IN Instructions ClearancesVentilation and Combustion AIR Location ALL ModelsFinishing Instructions Installing Furnace FigurePlastering Figure Outer Casing Figure Installing Control DoorSystem Check Figure Thermostat Location SG ModelsLighting Instructions Service technician or gas supplierWhat to do if YOU Smell GAS Proper Main Burner Flame Vent Safety Shutoff SystemProper Pilot Flame If Pilot Does Not Light By Any Means TroubleshootingMain Gas Valve Does Not Open When Thermostat Is Turned On Pilot Does Not LightHOW to Order Repair Parts Parts ListParts View Models Remote Bulb Control Installation InstructionsGWT-25 RB, GWT-35 RB, GWT-50 RB GWTB-2 for Models Optional Blower Installation InstructionsGWT-25 SG, RB, GWT-35 SG, RB, GWT-50 SG, RB GWTB-2 Wiring Diagram Service Notes

GWT-35-2, RB), GWT-25-2 specifications

Empire Products is renowned for its commitment to quality and innovation, particularly in the realm of heating solutions. Among their extensive range, the GWT-35-2 and GWT-25-2 gas-fired wall heaters stand out as exceptional choices for both residential and commercial applications.

The Empire GWT-35-2 is designed to deliver a powerful heating solution, boasting an impressive heat output. With an efficiency rating that ensures optimal warmth while minimizing energy consumption, this model is perfect for larger spaces that require consistent and reliable heating. Its sleek design allows it to seamlessly blend into various room aesthetics, while the multiple installation options make it versatile enough to meet varying layouts and preferences.

On the other hand, the GWT-25-2 is tailored for slightly smaller areas, yet it does not compromise on performance. This model provides ample heating efficiency and is well-suited for those looking to maintain a cozy atmosphere in modest-sized rooms. The unit’s compact form factor allows for easy installation without occupying too much wall space, making it an ideal option for residential settings.

Both models utilize advanced technologies that contribute to their superior performance. The state-of-the-art electronic ignition system in the GWT series ensures reliable startups, while the built-in thermostat provides precise temperature control. Users can easily adjust settings to their comfort levels, enhancing overall user satisfaction. Additionally, the heaters are equipped with innovative safety features such as automatic shut-off mechanisms, making them a safe choice for any environment.

Another key characteristic of the GWT-35-2 and GWT-25-2 is their fuel efficiency. By utilizing natural gas or propane, these units are designed to reduce energy costs without sacrificing heating quality. The durable construction of both models guarantees longevity and resilience, meaning customers can expect years of dependable service.

In summary, Empire Products' GWT-35-2 and GWT-25-2 wall heaters exemplify cutting-edge heating technology. Their combination of efficiency, performance, and safety features makes them a reliable choice for anyone in need of effective heating solutions, whether in a home or a commercial space. With Empire's commitment to quality, customers can feel confident in their investment in these powerful heating units.