Allied Air Enterprises 95G1DF, A95DF, 92G1DF Unconfined Space, Confined Space, Air from Inside

Page 7

air is brought into the house for combustion, negative pressure (outside pressure is greater than inside pressure) will build to the point that a down draft can occur in the furnace vent pipe or chimney. As a result, combustion gases enter the living space creating a potentially dangerous situation.

In the absence of local codes concerning air for combustion and ventilation, use the guidelines and procedures in this section to install these furnaces to ensure efficient and safe operation. You must consider combustion air needs and requirements for exhaust vents and gas piping. A portion of this information has been reprinted with permission from the National Fuel Gas Code (ANSI-Z223.1/NFPA 54). This reprinted material is not the complete and official position of ANSI on the referenced subject, which is represented only by the standard in its entirely.

In Canada, refer to the CSA B149 Installation codes.

CAUTION

Do not install the furnace in a corrosive or contaminated atmosphere. Meet all combustion and ventilation air requirements, as well as all local codes.

All gas-fired appliances require air for the combustion process. If sufficient combustion air is not available, the furnace or other appliance will operate inefficiently and unsafely. Enough air must be provided to meet the needs of all fuel-burning appliances and appliances such as exhaust fans which force air out of the house. When fireplaces, exhaust fans, or clothes dryers are used at the same time as the furnace, much more air is required to ensure proper combustion and to prevent a down draft. Insufficient air causes incomplete combustion which can result in carbon monoxide.

In addition to providing combustion air, fresh outdoor air dilutes contaminants in the indoor air. These contaminants may include bleaches, adhesives, detergents, solvents and other contaminants which can corrode furnace components.

The requirements for providing air for combustion and ventilation depend largely on whether the furnace is installed in an unconfined or a confined space.

Unconfined Space

An unconfined space is an area such as a basement or large equipment room with a volume greater than 50 cubic feet (1.42 m³) per 1,000 Btu (.29 kW) per hour of the combined input rating of all appliances installed in that space. This space also includes adjacent rooms which are not separated by a door. Though an area may appear to be unconfined, it might be necessary to bring in outdoor air for combustion if the structure does not provide enough air by

infiltration. If the furnace is located in a building of tight construction with weather stripping and caulking around the windows and doors, follow the procedures in the “Air from Outside” section.

Confined Space

A confined space is an area with a volume less than 50 cubic feet (1.42 m³) per 1,000 Btu (.29 kW) per hour of the combined input rating of all appliances installed in that space. This definition includes furnace closets or small equipment rooms.

When the furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air must be handled by ducts which are sealed to the furnace casing and which terminate outside the space containing the furnace. This is especially important when the furnace is mounted on a platform in a confined space such as a closet or small equipment room. Even a small leak around the base of the unit at the platform or at the return air duct connection can cause a potentially dangerous negative pressure condition. Air for combustion and ventilation can be brought into the confined space either from inside the building or from outside.

Air from Inside

If the confined space that houses the furnace adjoins a space categorized as unconfined, air can be brought in by providing two permanent openings between the two spaces. Each opening must have a minimum free area of 1 square inch (645 mm²) per 1,000 Btu (.29 kW) per hour of total input rating of all gas-fired equipment in the confined space. Each opening must be at least 100 square inches (64516 mm²). One opening shall be within 12 inches (305 mm) of the top of the enclosure and one opening within 12 inches (305 mm) of the bottom. See Figure 4.

EQUIPMENT IN CONFINED SPACE − ALL AIR FROM INSIDE

ROOF TERMINATED

EXHAUST PIPE

 

 

OPENINGS

SIDE WALL

 

(To Adjacent

 

Unconfined

TERMINATED

FURNACE

Space)

EXHAUST PIPE

 

 

(ALTERNATE

 

 

LOCATION)

 

 

NOTE − Each opening shall have a free area of at least one square inch per 1,000 Btu (645 mm2 per .29 kW) per hour of the total input rating of all equipment in the enclosure, but not less than 100 square inches (64516 mm2 ).

FIGURE 4

506725-01

Issue 1109

Page 7 of 48

Image 7
Contents A95DF, A93DF, 95G1DF & 92G1DF Table of ContentsFront View Side View TOP ViewParts Arrangement Building Codes Safety InformationGas Furnace Shipping and Packing List Package 1 of 1 containsLocations and Clearances Installed in Combination with a Cooling CoilUse of Furnace as Construction Heater Combustion, Dilution & Ventilation Air Product Contains Fiberglass WoolEquipment in Confined Space − ALL AIR from Inside Unconfined SpaceConfined Space Air from InsideEquipment in Confined Space − ALL AIR from Outside Air from OutsideShipping Bolt Removal Installation Setting EquipmentUnits with 1/2 HP Blower Motor Installation on Combustible Flooring Figure Installation on Non-Combustible Flooring FigureNON−COMBUSTIBLE Floor Opening Size Combustible Flooring Base Opening Size Installation on Cooling Coil Cabinet FigureReturn Air Opening Downflow Units Piping and Fittings Specifications Outdoor Termination Kits Usage Canadian Applications OnlyStandard Concentric Venting Practices Piping Suspension Guidelines Joint Cementing ProcedureReplacing Furnace That WAS Part of a Common Vent System Models Exhaust Piping FigureMinimum Vent Pipe Lengths MIN. Vent LengthA95DF / 95G1DF and A93DF / 92G1DF Typical Intake Pipe Connections Direct Vent Applications Typical Exhaust Pipe ConnectionsGeneral Guidelines for Vent Terminations For Canadian Installations OnlyIntake Piping Typical AIR Intake Pipe ConnectionsInside Corner Detail No minimum to outside corner Direct Vent Roof Termination KIT Exhaust Pipe Termination Size ReductionModel 51mm 76mm Direct Vent Concentric Rooftop Termination Direct Vent Application Using Existing ChimneyDirect Vent Concentric Wall Termination NON−DIRECT Vent Field Supplied Wall Termination NON−DIRECT Vent Application Using Existing ChimneyNON−DIRECT Vent Field Supplied Wall Termination Extended NON−DIRECT Vent Roof Termination KITUnit with Evaporator Coil Condensate PipingTrap / Drain Assembly Using 1/2 PVC or 3/4 PVC Leak Check Gas PipingFire or Explosion Hazard GAS Pipe Capacity − FT 3 /HR kL/HR Carbon Monoxide Poisoning Hazard Removal of the Furnace from Common VentElectrostatic Discharge ESD Precautions and ProceduresAccessory Terminals ElectricalGenerator Use Voltage Requirements Indoor Blower SpeedsTypical Wiring Diagram Placing the furnace into operation Integrated ControlAutomatic Hot Surface Ignition System Unit Start-UpFailure To Operate Priming Condensate TrapGas Valve Operation Figure Turning Off Gas to UnitGAS Meter Clocking Chart Burner Orifice Conversion Kits at Varying Altitudes Carbon Monoxide Poisoning Hazard Primary Limit Flame Rollout Switches TwoPressure Switch Temperature RiseBlower Data A93DF1D / 92G1DF Blower Data A95DF1D / 95G1DF Electrical SHOCK, Fire Or Explosion Hazard Cleaning the Burner Assembly Diagnostic Codes Planned ServiceBlower Parts Repair Parts ListCabinet Parts Heating Parts Control Panel PartsReturn Duct GAS SupplyIntake / Exhaust Pipe Duct System Supply AIR DuctUnit Operation Manufacturer Requirements Clear of ALL Obstructions

A95DF, 95G1DF, A93DF, 92G1DF specifications

Allied Air Enterprises offers a range of high-efficiency commercial and residential heating and cooling systems, with models like the 92G1DF, A93DF, 95G1DF, and A95DF gaining popularity for their cutting-edge technology and advanced features. Each of these models stands out in performance, reliability, and energy efficiency, making them excellent choices for diverse applications.

The 92G1DF model features a multi-stage gas valve that enhances temperature regulation, allowing for more precise heating. With an impressive Annual Fuel Utilization Efficiency (AFUE) rating, this furnace efficiently utilizes fuel, resulting in lower energy costs and reduced emissions. Its compact design makes it suitable for installations in tight spaces, while the durable heat exchanger extends the unit’s lifespan.

In contrast, the A93DF is engineered for enhanced comfort and flexibility. This model incorporates a variable-speed blower motor, which adjusts air circulation according to the heating demands in the space. This feature not only maximizes comfort by providing consistent temperatures but also promotes energy savings by reducing unnecessary power consumption. Additionally, the A93DF includes advanced diagnostic capabilities that simplify troubleshooting and maintenance, making it a favorite among HVAC professionals.

The 95G1DF is another noteworthy model that combines versatile performance with exceptional efficiency. This furnace boasts an AFUE rating of up to 95%, making it one of the most efficient models in its class. Its innovative design includes a secondary heat exchanger that captures additional heat from exhaust gases, optimizing energy utilization. Furthermore, the 95G1DF is equipped with an advanced control system that allows homeowners to set specific comfort levels.

Lastly, the A95DF model takes efficiency to a new level. With features such as a modulating gas valve and a variable-speed blower, this unit seamlessly adapts to changing heating needs. The A95DF not only heats a space but also enhances air quality through advanced filtration options. Its whisper-quiet operation adds to user satisfaction, making it ideal for residential settings.

In summary, Allied Air Enterprises' models 92G1DF, A93DF, 95G1DF, and A95DF demonstrate a commitment to innovation and energy efficiency, with features designed to provide superior comfort and reliability. With their advanced technologies and high-performance characteristics, these models are positioned as top contenders in the heating and cooling marketplace, ensuring that customers can enjoy a comfortable environment year-round.