Allied Air Enterprises A95DF, 92G1DF, A93DF, 95G1DF dimensions GAS Meter Clocking Chart

Page 36

Gas Pressure Adjustment

Gas Flow (Approximate)

GAS METER CLOCKING CHART

 

 

Seconds for One Revolution

Unit

 

Natural

 

LP

 

 

1 cu ft

2 cu ft

 

1 cu ft

 

2 cu ft

 

 

Dial

Dial

 

Dial

 

DIAL

 

 

 

 

 

 

 

 

−045

 

80

160

 

200

 

400

−070

 

55

110

 

136

 

272

−090

 

41

82

 

102

 

204

−110

 

33

66

 

82

 

164

−135

 

27

54

 

68

 

136

 

Natural−1000 btu/cu ft

LP−2500 btu/cu ft

 

TABLE 11

NOTE: To obtain accurate reading, shut off all other gas appliances connected to meter.

Furnace should operate at least 5 minutes before checking gas flow. Determine time in seconds for two revolutions of gas through the meter. (Two revolutions assures a more accurate time.) Divide by two and compare to time in Table 11. If manifold pressure matches Table 12 and rate is incorrect, check gas orifices for proper size and restriction. Remove temporary gas meter if installed.

Supply Pressure Measurement

A threaded plug on the inlet side of the gas valve provides access to the supply pressure tap. Remove the threaded plug, install a field-provided barbed fitting and connect a manometer to measure supply pressure. Replace the threaded plug after measurements have been taken.

Manifold Pressure Measurement

1.Remove the threaded plug from the outlet side of the gas valve and install a field provided barbed fitting. Connect to a manometer to measure manifold pressure.

2.Start unit and allow 5 minutes for unit to reach steady state.

3.While waiting for the unit to stabilize, observe the flame. Flame should be stable and should not lift from burner. Natural gas should burn blue.

4.After allowing unit to stabilize for 5 minutes, record manifold pressure and compare to value given in Table 12.

NOTE: Shut unit off and remove manometer as soon as an accurate reading has been obtained. Take care to remove barbed fitting and replace threaded plug.

Supply Line and Manifold Pressure (inches w.c.)

Unit

Fuel

Manifold

Line Pressure

Pressure

 

 

 

 

 

 

 

 

 

 

 

All

Nat. Gas

3.5

4.5 − 10.5

 

 

 

 

All

L.P. Gas

10.0

11.0 − 13.0

 

 

 

 

TABLE 12

NOTE:A natural to L.P. propane gas changeover kit is necessary to convert this unit. Refer to the changeover kit installation instruction for the conversion procedure.

Proper Combustion

Furnace should operate minimum 15 minutes with correct manifold pressure and gas flow rate before checking combustion. Take combustion sample beyond the flue outlet and compare to the tables below. The maximum carbon monoxide reading should not exceed 50 ppm.

Unit

CO2% For Nat

CO2% For L.P.

All

7.2 − 7.9

8.6 − 9.3

 

 

 

The maximum carbon monoxide reading should not exceed 50 ppm.

TABLE 13

High Altitude Information

NOTE: In Canada, certification for installations at elevations over 4500 feet (1372 m) is the jurisdiction of local authorities.

The furnace requires no manifold pressure adjustments for operation at altitudes up to 10,000 feet (3048 m) above sea level. Units installed at altitudes of 4501 - 10,000 feet (1373 to 3048 m) require a pressure switch change which can be ordered separately. Table 14 lists conversion kit and pressure switch requirements at varying altitudes.

The combustion air pressure switch is factory-set and requires no adjustment.

Page 36 of 48

Issue 1109

506725-01

Image 36
Contents Table of Contents A95DF, A93DF, 95G1DF & 92G1DFTOP View Front View Side ViewParts Arrangement Safety Information Gas FurnaceShipping and Packing List Package 1 of 1 contains Building CodesInstalled in Combination with a Cooling Coil Locations and ClearancesUse of Furnace as Construction Heater Product Contains Fiberglass Wool Combustion, Dilution & Ventilation AirUnconfined Space Confined SpaceAir from Inside Equipment in Confined Space − ALL AIR from InsideAir from Outside Equipment in Confined Space − ALL AIR from OutsideInstallation Setting Equipment Shipping Bolt RemovalUnits with 1/2 HP Blower Motor Installation on Non-Combustible Flooring Figure Installation on Combustible Flooring FigureNON−COMBUSTIBLE Floor Opening Size Installation on Cooling Coil Cabinet Figure Combustible Flooring Base Opening SizeReturn Air Opening Downflow Units Piping and Fittings Specifications Canadian Applications Only Outdoor Termination Kits UsageStandard Concentric Joint Cementing Procedure Venting Practices Piping Suspension GuidelinesReplacing Furnace That WAS Part of a Common Vent System Exhaust Piping Figure Minimum Vent Pipe LengthsMIN. Vent Length ModelsA95DF / 95G1DF and A93DF / 92G1DF Typical Exhaust Pipe Connections Typical Intake Pipe Connections Direct Vent ApplicationsFor Canadian Installations Only Intake PipingTypical AIR Intake Pipe Connections General Guidelines for Vent TerminationsInside Corner Detail No minimum to outside corner Exhaust Pipe Termination Size Reduction Direct Vent Roof Termination KITModel 51mm 76mm Direct Vent Application Using Existing Chimney Direct Vent Concentric Rooftop TerminationDirect Vent Concentric Wall Termination NON−DIRECT Vent Application Using Existing Chimney NON−DIRECT Vent Field Supplied Wall Termination ExtendedNON−DIRECT Vent Roof Termination KIT NON−DIRECT Vent Field Supplied Wall TerminationCondensate Piping Unit with Evaporator CoilTrap / Drain Assembly Using 1/2 PVC or 3/4 PVC Gas Piping Leak CheckFire or Explosion Hazard GAS Pipe Capacity − FT 3 /HR kL/HR Removal of the Furnace from Common Vent Carbon Monoxide Poisoning HazardPrecautions and Procedures Accessory TerminalsElectrical Electrostatic Discharge ESDIndoor Blower Speeds Generator Use Voltage RequirementsTypical Wiring Diagram Integrated Control Automatic Hot Surface Ignition SystemUnit Start-Up Placing the furnace into operationPriming Condensate Trap Gas Valve Operation FigureTurning Off Gas to Unit Failure To OperateGAS Meter Clocking Chart Burner Orifice Conversion Kits at Varying Altitudes Carbon Monoxide Poisoning Hazard Flame Rollout Switches Two Pressure SwitchTemperature Rise Primary LimitBlower Data A93DF1D / 92G1DF Blower Data A95DF1D / 95G1DF Electrical SHOCK, Fire Or Explosion Hazard Cleaning the Burner Assembly Planned Service Diagnostic CodesRepair Parts List Cabinet Parts Heating PartsControl Panel Parts Blower PartsGAS Supply Intake / Exhaust PipeDuct System Supply AIR Duct Return DuctUnit Operation Clear of ALL Obstructions Manufacturer Requirements

A95DF, 95G1DF, A93DF, 92G1DF specifications

Allied Air Enterprises offers a range of high-efficiency commercial and residential heating and cooling systems, with models like the 92G1DF, A93DF, 95G1DF, and A95DF gaining popularity for their cutting-edge technology and advanced features. Each of these models stands out in performance, reliability, and energy efficiency, making them excellent choices for diverse applications.

The 92G1DF model features a multi-stage gas valve that enhances temperature regulation, allowing for more precise heating. With an impressive Annual Fuel Utilization Efficiency (AFUE) rating, this furnace efficiently utilizes fuel, resulting in lower energy costs and reduced emissions. Its compact design makes it suitable for installations in tight spaces, while the durable heat exchanger extends the unit’s lifespan.

In contrast, the A93DF is engineered for enhanced comfort and flexibility. This model incorporates a variable-speed blower motor, which adjusts air circulation according to the heating demands in the space. This feature not only maximizes comfort by providing consistent temperatures but also promotes energy savings by reducing unnecessary power consumption. Additionally, the A93DF includes advanced diagnostic capabilities that simplify troubleshooting and maintenance, making it a favorite among HVAC professionals.

The 95G1DF is another noteworthy model that combines versatile performance with exceptional efficiency. This furnace boasts an AFUE rating of up to 95%, making it one of the most efficient models in its class. Its innovative design includes a secondary heat exchanger that captures additional heat from exhaust gases, optimizing energy utilization. Furthermore, the 95G1DF is equipped with an advanced control system that allows homeowners to set specific comfort levels.

Lastly, the A95DF model takes efficiency to a new level. With features such as a modulating gas valve and a variable-speed blower, this unit seamlessly adapts to changing heating needs. The A95DF not only heats a space but also enhances air quality through advanced filtration options. Its whisper-quiet operation adds to user satisfaction, making it ideal for residential settings.

In summary, Allied Air Enterprises' models 92G1DF, A93DF, 95G1DF, and A95DF demonstrate a commitment to innovation and energy efficiency, with features designed to provide superior comfort and reliability. With their advanced technologies and high-performance characteristics, these models are positioned as top contenders in the heating and cooling marketplace, ensuring that customers can enjoy a comfortable environment year-round.