Allied Air Enterprises 95G1DF Exhaust Piping Figure, Minimum Vent Pipe Lengths, MIN. Vent Length

Page 15

1.In areas where piping penetrates joist or interior walls, hole must be large enough to allow clearance on all sides of pipe through center of hole using a hanger.

2.When furnace is installed in a residence where unit is shut down for an extended period of time, such as a vacation home, make provisions for draining condensate collection trap and lines.

Exhaust Piping (Figure 20)

Route piping to outside of structure. Continue with installation following instructions given in piping termination section.

CAUTION

Do not discharge exhaust into an existing stack or stack that also serves another gas appliance. If vertical discharge through an existing unused stack is required, insert PVC pipe inside the stack until the end is even with the top or outlet end of the metal stack.

CAUTION

The exhaust vent pipe operates under positive pressure and must be completely sealed to prevent leakage of combustion products into the living space.

Vent Piping Guidelines

This gas furnace can be installed as either a Non-Direct Vent or a Direct Vent gas central furnace.

NOTE: In non-Direct Vent installations, combustion air is taken from indoors and flue gases are discharged outdoors. In Direct Vent installations, combustion air is taken from outdoors and flue gases are discharged outdoors.

Intake and exhaust pipe sizing - Size pipe according to Tables 6 and 7. Table 6 lists the minimum vent pipe lengths permitted. Table 7 lists the maximum pipe lengths permitted.

Regardless of the diameter of pipe used, the standard roof and wall terminations described in section Exhaust Piping Terminations should be used. Exhaust vent termination pipe is sized to optimize the velocity of the exhaust gas as it exits the termination.

In some applications which permit the use of several different sizes of vent pipe, a combination vent pipe may be used. Contact Allied Air Technical Service for assistance in sizing vent pipe in these applications.

MINIMUM VENT PIPE LENGTHS

A95DF, 95G1DF, A93DF, & 92G1DF

MIN. VENT LENGTH*

MODELS

 

 

15 ft. or

045, 070, 090, 110

5 ft plus 2 elbows or

 

10 ft plus 1 elbow

*Any approved termination may be added to the minimum length listed.

TABLE 6

Use the following steps to correctly size vent pipe diameter.

1

045, 070,

090, 110

Furnace capacity?

Standard or

2 Which termination?Concentric? See Table 5

3

Which needs

Intake or

most elbows?

exhaust

 

 

 

4How many?

5

Desired pipe size?

2", 2 1/2"

 

 

or 3"

6What is the altitude?

Use Table 7 to find

7max intake or exhaust pipe length.

FIGURE 19

IMPORTANT

Do not use screens or perforated metal in exhaust or intake terminations. Doing so will cause freeze-ups and may block the terminations.

506725-01

Issue 1109

Page 15 of 48

Image 15
Contents A95DF, A93DF, 95G1DF & 92G1DF Table of ContentsFront View Side View TOP ViewParts Arrangement Building Codes Safety InformationGas Furnace Shipping and Packing List Package 1 of 1 containsInstalled in Combination with a Cooling Coil Locations and ClearancesUse of Furnace as Construction Heater Combustion, Dilution & Ventilation Air Product Contains Fiberglass WoolEquipment in Confined Space − ALL AIR from Inside Unconfined SpaceConfined Space Air from InsideEquipment in Confined Space − ALL AIR from Outside Air from OutsideInstallation Setting Equipment Shipping Bolt RemovalUnits with 1/2 HP Blower Motor Installation on Non-Combustible Flooring Figure Installation on Combustible Flooring FigureNON−COMBUSTIBLE Floor Opening Size Installation on Cooling Coil Cabinet Figure Combustible Flooring Base Opening SizeReturn Air Opening Downflow Units Piping and Fittings Specifications Canadian Applications Only Outdoor Termination Kits UsageStandard Concentric Joint Cementing Procedure Venting Practices Piping Suspension GuidelinesReplacing Furnace That WAS Part of a Common Vent System Models Exhaust Piping FigureMinimum Vent Pipe Lengths MIN. Vent LengthA95DF / 95G1DF and A93DF / 92G1DF Typical Intake Pipe Connections Direct Vent Applications Typical Exhaust Pipe ConnectionsGeneral Guidelines for Vent Terminations For Canadian Installations OnlyIntake Piping Typical AIR Intake Pipe ConnectionsInside Corner Detail No minimum to outside corner Exhaust Pipe Termination Size Reduction Direct Vent Roof Termination KITModel 51mm 76mm Direct Vent Application Using Existing Chimney Direct Vent Concentric Rooftop TerminationDirect Vent Concentric Wall Termination NON−DIRECT Vent Field Supplied Wall Termination NON−DIRECT Vent Application Using Existing ChimneyNON−DIRECT Vent Field Supplied Wall Termination Extended NON−DIRECT Vent Roof Termination KITUnit with Evaporator Coil Condensate PipingTrap / Drain Assembly Using 1/2 PVC or 3/4 PVC Gas Piping Leak CheckFire or Explosion Hazard GAS Pipe Capacity − FT 3 /HR kL/HR Carbon Monoxide Poisoning Hazard Removal of the Furnace from Common VentElectrostatic Discharge ESD Precautions and ProceduresAccessory Terminals ElectricalGenerator Use Voltage Requirements Indoor Blower SpeedsTypical Wiring Diagram Placing the furnace into operation Integrated ControlAutomatic Hot Surface Ignition System Unit Start-UpFailure To Operate Priming Condensate TrapGas Valve Operation Figure Turning Off Gas to UnitGAS Meter Clocking Chart Burner Orifice Conversion Kits at Varying Altitudes Carbon Monoxide Poisoning Hazard Primary Limit Flame Rollout Switches TwoPressure Switch Temperature RiseBlower Data A93DF1D / 92G1DF Blower Data A95DF1D / 95G1DF Electrical SHOCK, Fire Or Explosion Hazard Cleaning the Burner Assembly Diagnostic Codes Planned ServiceBlower Parts Repair Parts ListCabinet Parts Heating Parts Control Panel PartsReturn Duct GAS SupplyIntake / Exhaust Pipe Duct System Supply AIR DuctUnit Operation Manufacturer Requirements Clear of ALL Obstructions

A95DF, 95G1DF, A93DF, 92G1DF specifications

Allied Air Enterprises offers a range of high-efficiency commercial and residential heating and cooling systems, with models like the 92G1DF, A93DF, 95G1DF, and A95DF gaining popularity for their cutting-edge technology and advanced features. Each of these models stands out in performance, reliability, and energy efficiency, making them excellent choices for diverse applications.

The 92G1DF model features a multi-stage gas valve that enhances temperature regulation, allowing for more precise heating. With an impressive Annual Fuel Utilization Efficiency (AFUE) rating, this furnace efficiently utilizes fuel, resulting in lower energy costs and reduced emissions. Its compact design makes it suitable for installations in tight spaces, while the durable heat exchanger extends the unit’s lifespan.

In contrast, the A93DF is engineered for enhanced comfort and flexibility. This model incorporates a variable-speed blower motor, which adjusts air circulation according to the heating demands in the space. This feature not only maximizes comfort by providing consistent temperatures but also promotes energy savings by reducing unnecessary power consumption. Additionally, the A93DF includes advanced diagnostic capabilities that simplify troubleshooting and maintenance, making it a favorite among HVAC professionals.

The 95G1DF is another noteworthy model that combines versatile performance with exceptional efficiency. This furnace boasts an AFUE rating of up to 95%, making it one of the most efficient models in its class. Its innovative design includes a secondary heat exchanger that captures additional heat from exhaust gases, optimizing energy utilization. Furthermore, the 95G1DF is equipped with an advanced control system that allows homeowners to set specific comfort levels.

Lastly, the A95DF model takes efficiency to a new level. With features such as a modulating gas valve and a variable-speed blower, this unit seamlessly adapts to changing heating needs. The A95DF not only heats a space but also enhances air quality through advanced filtration options. Its whisper-quiet operation adds to user satisfaction, making it ideal for residential settings.

In summary, Allied Air Enterprises' models 92G1DF, A93DF, 95G1DF, and A95DF demonstrate a commitment to innovation and energy efficiency, with features designed to provide superior comfort and reliability. With their advanced technologies and high-performance characteristics, these models are positioned as top contenders in the heating and cooling marketplace, ensuring that customers can enjoy a comfortable environment year-round.