Carrier 58TMA operating instructions Btu/Cu Ft

Page 18

Table 10—Model 58TMA Orifice Size and Manifold Pressure for Correct Input

(Tabulated Data Based on 21,000 Btuh High Heat/13,500 Btuh Low Heat per Burner,

Derated 4% for Each 1000 Ft Above Sea Level)*

 

 

 

AVG GAS

 

 

 

 

 

SPECIFIC GRAVITY OF NATURAL GAS

 

 

 

 

ALTITUDE

 

0.58

 

0.60

 

0.62

 

0.64

 

0.66

 

HEAT VALUE

 

 

 

 

 

 

 

RANGE

AT ALTITUDE

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

 

 

(FT)

 

Pressure

 

Pressure

 

Pressure

 

Pressure

 

Pressure

 

 

 

(BTU/CU FT)

No.

 

No.

 

No.

 

No.

 

No.

 

 

 

 

 

 

 

High/Low

 

 

High/Low

 

 

High/Low

 

 

High/Low

 

 

High/Low

 

 

 

850

42

 

3.3/1.4

42

 

3.4/1.4

42

 

3.5/1.5

42

 

3.7/1.5

42

 

3.8/1.6

 

 

 

875

43

 

3.8/1.6

42

 

3.2/1.3

42

 

3.3/1.4

42

 

3.5/1.4

42

 

3.6/1.5

Canada

 

 

900

43

 

3.6/1.5

43

 

3.7/1.5

42

 

3.2/1.3

42

 

3.3/1.3

42

 

3.4/1.4

 

0

925

43

 

3.4/1.4

43

 

3.5/1.5

43

 

3.6/1.5

43

 

3.8/1.6

42

 

3.2/1.3

 

 

950

44

 

3.7/1.5

44

 

3.8/1.6

43

 

3.5/1.4

43

 

3.6/1.5

43

 

3.7/1.5

and

 

to

975

44

 

3.5/1.5

44

 

3.6/1.5

44

 

3.8/1.6

43

 

3.4/1.4

43

 

3.5/1.4

 

 

1000

44

 

3.3/1.4

44

 

3.5/1.4

44

 

3.6/1.5

44

 

3.7/1.5

44

 

3.8/1.6

U.S.A.

 

 

 

 

 

 

 

 

2000

1025

44

 

3.2/1.3

44

 

3.3/1.4

44

 

3.4/1.4

44

 

3.5/1.5

44

 

3.6/1.5

 

 

1050

45

 

3.7/1.5

45

 

3.8/1.6

44

 

3.2/1.3

44

 

3.4/1.4

44

 

3.5/1.4

 

 

 

 

 

 

 

 

 

 

 

1075

46

 

3.7/1.5

46

 

3.8/1.6

45

 

3.7/1.5

44

 

3.2/1.3

44

 

3.3/1.4

 

 

 

1100

46

 

3.5/1.5

46

 

3.6/1.5

46

 

3.8/1.6

45

 

3.7/1.5

45

 

3.8/1.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AVG GAS

 

 

 

 

 

SPECIFIC GRAVITY OF NATURAL GAS

 

 

 

 

ALTITUDE

 

0.58

 

0.60

 

0.62

 

0.64

 

0.66

 

HEAT VALUE

 

 

 

 

 

 

 

RANGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AT ALTITUDE

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

 

 

(FT)

 

Pressure

 

Pressure

 

Pressure

 

Pressure

 

Pressure

 

 

 

(BTU/CU FT)

No.

 

No.

 

No.

 

No.

 

No.

 

 

 

 

 

 

 

High/Low

 

 

High/Low

 

 

High/Low

 

 

High/Low

 

 

High/Low

 

 

U.S.A.

775

43

 

3.7/1.5

42

 

3.2/1.3

42

 

3.3/1.4

42

 

3.4/1.4

42

 

3.5/1.4

 

 

Altitudes

800

43

 

3.5/1.4

43

 

3.6/1.5

43

 

3.7/1.5

42

 

3.2/1.3

42

 

3.3/1.3

Canada

 

2001

825

44

 

3.8/1.6

43

 

3.4/1.4

43

 

3.5/1.5

43

 

3.6/1.5

43

 

3.7/1.5

 

to

850

44

 

3.6/1.5

44

 

3.7/1.5

44

 

3.8/1.6

43

 

3.4/1.4

43

 

3.5/1.5

 

3000

875

44

 

3.4/1.4

44

 

3.5/1.4

44

 

3.6/1.5

44

 

3.7/1.5

44

 

3.8/1.6

and

 

or

900

44

 

3.2/1.3

44

 

3.3/1.4

44

 

3.4/1.4

44

 

3.5/1.4

44

 

3.6/1.5

 

Canada

925

46

 

3.8/1.6

45

 

3.8/1.6

44

 

3.2/1.3

44

 

3.3/1.4

44

 

3.4/1.4

U.S.A.

 

 

 

 

 

 

 

Altitudes

950

46

 

3.6/1.5

46

 

3.7/1.5

45

 

3.7/1.5

45

 

3.8/1.6

44

 

3.2/1.3

 

2000

975

46

 

3.4/1.4

46

 

3.5/1.5

46

 

3.7/1.5

46

 

3.8/1.6

45

 

3.7/1.5

 

 

 

 

 

 

 

 

 

to

1000

47

 

3.7/1.5

47

 

3.8/1.6

46

 

3.5/1.4

46

 

3.6/1.5

46

 

3.7/1.5

 

 

4500

1025

47

 

3.5/1.5

47

 

3.6/1.5

47

 

3.8/1.6

46

 

3.4/1.4

46

 

3.5/1.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AVG GAS

 

 

 

 

 

SPECIFIC GRAVITY OF NATURAL GAS

 

 

 

 

ALTITUDE

 

0.58

 

0.60

 

0.62

 

0.64

 

0.66

 

HEAT VALUE

 

 

 

 

 

 

 

RANGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AT ALTITUDE

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

 

 

(FT)

 

Pressure

 

Pressure

 

Pressure

 

Pressure

 

Pressure

 

 

 

(BTU/CU FT)

No.

 

No.

 

No.

 

No.

 

No.

 

 

 

 

 

 

 

High/Low

 

 

High/Low

 

 

High/Low

 

 

High/Low

 

 

High/Low

 

 

 

750

43

 

3.5/1.4

43

 

3.6/1.5

43

 

3.7/1.5

42

 

3.2/1.3

42

 

3.3/1.4

 

 

 

775

44

 

3.8/1.6

43

 

3.4/1.4

43

 

3.5/1.4

43

 

3.6/1.5

43

 

3.7/1.5

 

 

 

800

44

 

3.5/1.5

44

 

3.7/1.5

44

 

3.8/1.6

43

 

3.4/1.4

43

 

3.5/1.4

Only

 

3001

825

44

 

3.3/1.4

44

 

3.4/1.4

44

 

3.5/1.5

44

 

3.7/1.5

44

 

3.8/1.6

 

 

850

45

 

3.8/1.6

44

 

3.2/1.3

44

 

3.3/1.4

44

 

3.4/1.4

44

 

3.6/1.5

U.S.A.

 

to

875

46

 

3.7/1.5

45

 

3.7/1.5

44

 

3.2/1.3

44

 

3.3/1.3

44

 

3.4/1.4

 

 

900

46

 

3.5/1.5

46

 

3.7/1.5

46

 

3.8/1.6

45

 

3.7/1.5

44

 

3.2/1.3

 

4000

925

47

 

3.8/1.6

46

 

3.5/1.4

46

 

3.6/1.5

46

 

3.7/1.5

46

 

3.8/1.6

 

 

 

 

 

 

 

 

 

 

950

47

 

3.6/1.5

47

 

3.7/1.5

46

 

3.4/1.4

46

 

3.5/1.5

46

 

3.6/1.5

 

 

 

975

47

 

3.4/1.4

47

 

3.5/1.5

47

 

3.7/1.5

47

 

3.8/1.6

46

 

3.4/1.4

 

 

 

1000

48

 

3.7/1.5

48

 

3.8/1.6

47

 

3.5/1.4

47

 

3.6/1.5

47

 

3.7/1.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*For 125-20 size only, input is 20,500 Btuh for high fire. Deduct 0.1-in. from manifold pressure shown in table. Change orifice size if manifold pressure falls below 3.2-in. wc.

18

Image 18
Contents Electrostatic Discharge ESD Precautions SUPPLY-AIR Plenum InstallationDimensional Drawing Dimensions Unit Size Vent Conn SHIP. WTMinimum Inches Clearance to Combustible Construction Hazardous Locations GeneralLocation Relative to Cooling Equipment Unconfined Space→ Downflow Installation Confined Space Air for Combustion Ventilation from OutdoorsInput Installation on Combustible FloorFree Area Of Combustion Air Opening Furnace Plenum Opening Floor Opening CasingInstall Furnace Construct Working PlatformTypical Attic Installation → -Horizontal Crawlspace Installation on Hanger Rods→ -Horizontal Installation on Blocks Furnace Casing Width FiltersNominal Internal Length of Pipe FT Iron Pipe Diameter Size Wiring AccessoriesSetup Switch Description Electrical DataAmps Gage FT‡ CKT BKR AMPS† Delay SEC → -Setup Switches on Control Center Factory SettingsDesired Heating Setup Switch Mode Blower OFF Sequence of Operation→ -Unit Wiring Diagram Connection DiagramPage Page START-UP Procedures AdjustmentsExample Altitude Derate Multiplier for U.S.AUnited States CanadaBTU/CU FT 725 1.6 625 1.4 Gas Rate Cu Ft/Hr → -Redundant Automatic Gas Control ValveCheck Safety Controls Speed SelectionColor Speed AS Shipped Checklist Service Training

58TMA specifications

The Carrier 58TMA is a high-efficiency gas furnace designed to provide reliable heating solutions for residential spaces. As part of Carrier's extensive range of heating products, the 58TMA series exemplifies innovation in home comfort technology, offering advanced features that cater to both performance and energy savings.

One of the standout features of the Carrier 58TMA is its variable-speed blower motor. This technology allows for precise airflow control, ensuring consistent temperatures throughout the home while minimizing energy consumption. The variable-speed operation also contributes to quieter operation, enhancing indoor comfort without the disruptive noise commonly associated with traditional furnaces.

The furnace operates with a multi-stage gas valve, enhancing its efficiency. With the ability to modulate heating output based on demand, the 58TMA ensures that the home is heated only as needed. This not only improves energy efficiency but also maintains a more stable and comfortable indoor environment. The combination of the multi-stage gas valve and variable-speed blower results in significant energy cost savings for homeowners.

Another impressive aspect of the Carrier 58TMA is its high Annual Fuel Utilization Efficiency (AFUE) rating. With an AFUE of up to 96%, this gas furnace is engineered to convert a majority of the fuel it consumes into heat, reducing waste and lowering utility bills. Such efficiency ratings make the 58TMA an attractive option for eco-conscious consumers looking to minimize their carbon footprint.

In addition to efficiency and performance, the Carrier 58TMA is designed with durability in mind. The unit features a robust cabinet made from high-quality materials, along with an advanced heat exchanger that ensures long-lasting performance. Moreover, it comes equipped with an advanced electrical ignition system, providing reliable start-up under various conditions without the need for a pilot light.

For added convenience, the 58TMA can be integrated with Carrier's Smart Thermostat technology. This allows homeowners to monitor and adjust their heating settings remotely, facilitating an optimized comfort experience while further enhancing energy savings.

Overall, the Carrier 58TMA's combination of efficiency, advanced technology, and durability makes it a standout option in the market for homeowners seeking dependability and energy savings in their heating solutions. With its innovative features and user-friendly operation, the 58TMA represents a significant advancement in modern furnace design, providing peace of mind and comfort year after year.