Carrier 58TMA Electrical Data, Setup Switch Description, Amps Gage FT‡ CKT BKR AMPS†

Page 11

Table 6—Electrical Data

UNIT

VOLTS—

OPERATING

MAX

MIN

MAX WIRE

MAX FUSE OR

HERTZ—

VOLTAGE RANGE

UNIT

WIRE

LENGTH

HACR-TYPE

SIZE

PHASE

Max*

Min*

AMPS

GAGE

FT‡

CKT BKR AMPS†

 

065-08

115—60—1

127

104

8.0

14

46

15

065-12

115—60—1

127

104

10.5

14

35

15

085-12

115—60—1

127

104

12.0

14

30

15

085-16

115—60—1

127

104

14.2

14

26

15

105-16

115-60-1

127

104

13.2

14

29

15

105-20

115—60—1

127

104

17.2

12

33

20

125-20

115—60—1

127

104

17.9

12

32

20

*Permissible limits of the voltage range at which the unit will operate satisfactorily.

Time-delay fuse is recommended.

‡ Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop.

FIELD 24-V WIRING￿

FIELD 115-, 208/230-, 460-V WIRING￿ FACTORY 24-V WIRING￿ FACTORY 115-V WIRING

1-STAGE THERMOSTAT TERMINALS

FIVE￿ WIRE￿

W Y R G C

FIELD-SUPPLIED￿ FUSED DISCONNECT

 

 

TWO-WIRE￿

 

 

 

208/230- OR￿

 

 

HEATING-￿

 

 

 

 

 

ONLY

 

 

 

460-V￿

 

 

 

 

 

 

THREE￿

BLK

BLK

 

W2

 

 

PHASE

 

 

 

 

 

 

 

 

 

WHT

WHT

 

COM

 

 

 

 

 

 

 

 

 

 

 

W/W1

 

 

208/230-V￿

 

GND

 

 

 

 

SINGLE￿

115-V FUSED￿

JUNCTION￿

Y/Y2

 

 

PHASE

 

 

 

 

DISCONNECT￿

BOX

R

 

 

GND

 

SWITCH￿

CONTROL￿

 

 

 

CONDENSING￿

(WHEN REQUIRED)

BOX

G￿

 

 

 

 

UNIT

 

 

 

 

 

 

 

 

 

24-V￿

 

 

 

 

 

TERMINAL￿

 

 

 

 

 

BLOCK

NOTES:

1.

Connect Y-terminal as shown for proper operation.￿

 

 

FURNACE

 

￿

2. Some thermostats require a "C" terminal connection as shown.￿

 

 

 

 

 

3. If any of the original wire, as supplied, must be replaced,￿

 

 

 

 

 

 

use same type or equivalent wire.

A97443

Fig. 15—Heating and Cooling Application Wiring Diagram With 1-Stage Thermostat and Condensing Unit

This furnace can be installed with either single-stage heating or 2-stage heating thermostat.

For single-stage thermostats, connect thermostat W to W/W1 at furnace control terminal block. (See Fig. 15.) For single-stage thermostats the control determines, based on length of previous heating on and off cycles, when to operate in low- and high-gas heat for optimum comfort. Setup Switch-2 (SW-2) must be in the factory-shipped OFF position. See Fig. 17 and Tables 6 and 7 for setup switch information.

If 2-stage heating thermostat is to be used, move SW-2 to ON position at end of furnace installation. This overrides built-in control process for selecting high and low stage and allows 2-stage thermostat to select gas heating modes. The W2 from thermostat must be connected to W2 on control terminal block. (See Fig. 16.)

Before operating furnace, check each manual reset switch for continuity. If necessary, press and release button to reset switch.

Table 7—Setup Switch Description

SETUP

NORMAL

DESCRIPTION OF USE

SWITCH NO.

POSITION

 

 

 

Turn switch on to obtain only

 

OFF

high-gas-heat operation on

SW-1

any call for heat regardless of

(Staged Gas

Only High-Gas Heat

whether R-W/W1, or R-W/W1,

Heat)

 

-W2 is closed. SW-1 overrides

 

 

 

 

SW-2.

 

 

Turn switch off for installations

 

 

with single-stage thermostats;

 

 

control selects low-gas-heat

 

 

or high-gas-heat operation

SW-2

OFF

based on previous cycles.

Turn switch on for installations

Low-Gas Heat

(Single-Stage

with 2-stage thermostats to

(Adaptive Mode)

Thermostat)

permit only low-gas-heat op-

 

 

 

 

eration in response to closing

 

 

R-W/W1. High-gas heat is

 

 

supplied only when R to

 

 

W/W1 and W2 is closed.

SW-3 and

 

Switches control gas heating

ON, OFF

blower off delay. (See Table

SW4

 

8.)

 

 

11

Image 11
Contents SUPPLY-AIR Plenum Installation Electrostatic Discharge ESD PrecautionsUnit Size Vent Conn SHIP. WT Dimensional Drawing DimensionsMinimum Inches Clearance to Combustible Construction Unconfined Space GeneralLocation Relative to Cooling Equipment Hazardous LocationsConfined Space Air for Combustion Ventilation from Outdoors → Downflow InstallationFurnace Plenum Opening Floor Opening Casing Installation on Combustible FloorFree Area Of Combustion Air Opening InputConstruct Working Platform Install Furnace→ -Horizontal Crawlspace Installation on Hanger Rods Typical Attic InstallationNominal Internal Length of Pipe FT Iron Pipe Diameter Size → -Horizontal Installation on BlocksFurnace Casing Width Filters Accessories WiringAmps Gage FT‡ CKT BKR AMPS† Setup Switch DescriptionElectrical Data Sequence of Operation → -Setup Switches on Control Center Factory SettingsDesired Heating Setup Switch Mode Blower OFF Delay SECConnection Diagram → -Unit Wiring DiagramPage Page Adjustments START-UP ProceduresCanada Altitude Derate Multiplier for U.S.AUnited States ExampleBTU/CU FT 725 1.6 625 1.4 → -Redundant Automatic Gas Control Valve Gas Rate Cu Ft/HrColor Speed AS Shipped Check Safety ControlsSpeed Selection Checklist Service Training

58TMA specifications

The Carrier 58TMA is a high-efficiency gas furnace designed to provide reliable heating solutions for residential spaces. As part of Carrier's extensive range of heating products, the 58TMA series exemplifies innovation in home comfort technology, offering advanced features that cater to both performance and energy savings.

One of the standout features of the Carrier 58TMA is its variable-speed blower motor. This technology allows for precise airflow control, ensuring consistent temperatures throughout the home while minimizing energy consumption. The variable-speed operation also contributes to quieter operation, enhancing indoor comfort without the disruptive noise commonly associated with traditional furnaces.

The furnace operates with a multi-stage gas valve, enhancing its efficiency. With the ability to modulate heating output based on demand, the 58TMA ensures that the home is heated only as needed. This not only improves energy efficiency but also maintains a more stable and comfortable indoor environment. The combination of the multi-stage gas valve and variable-speed blower results in significant energy cost savings for homeowners.

Another impressive aspect of the Carrier 58TMA is its high Annual Fuel Utilization Efficiency (AFUE) rating. With an AFUE of up to 96%, this gas furnace is engineered to convert a majority of the fuel it consumes into heat, reducing waste and lowering utility bills. Such efficiency ratings make the 58TMA an attractive option for eco-conscious consumers looking to minimize their carbon footprint.

In addition to efficiency and performance, the Carrier 58TMA is designed with durability in mind. The unit features a robust cabinet made from high-quality materials, along with an advanced heat exchanger that ensures long-lasting performance. Moreover, it comes equipped with an advanced electrical ignition system, providing reliable start-up under various conditions without the need for a pilot light.

For added convenience, the 58TMA can be integrated with Carrier's Smart Thermostat technology. This allows homeowners to monitor and adjust their heating settings remotely, facilitating an optimized comfort experience while further enhancing energy savings.

Overall, the Carrier 58TMA's combination of efficiency, advanced technology, and durability makes it a standout option in the market for homeowners seeking dependability and energy savings in their heating solutions. With its innovative features and user-friendly operation, the 58TMA represents a significant advancement in modern furnace design, providing peace of mind and comfort year after year.