Carrier 58TMA operating instructions Gas Rate Cu Ft/Hr, → -Redundant Automatic Gas Control Valve

Page 21

Table 11—Gas Rate (Cu Ft/Hr)

SECONDS

SIZE OF TEST DIAL

SECONDS

SIZE OF TEST DIAL

FOR 1

1

2

5

FOR 1

1

2

5

REVOLUTION

cu ft

cu ft

cu ft

REVOLUTION

cu ft

cu ft

cu ft

10

360

720

1800

50

72

144

360

11

327

655

1636

51

71

141

355

12

300

600

1500

52

69

138

346

13

277

555

1385

53

68

136

340

14

257

514

1286

54

67

133

333

15

240

480

1200

55

65

131

327

16

225

450

1125

56

64

129

321

17

212

424

1059

57

63

126

316

18

200

400

1000

58

62

124

310

19

189

379

947

59

61

122

305

20

180

360

900

60

60

120

300

21

171

343

857

62

58

116

290

22

164

327

818

64

56

112

281

23

157

313

783

66

54

109

273

24

150

300

750

68

53

106

265

25

144

288

720

70

51

103

257

26

138

277

692

72

50

100

250

27

133

267

667

74

48

97

243

28

129

257

643

76

47

95

237

29

124

248

621

78

46

92

231

INLET￿ PRESSURE￿ TAP

ON/OFF￿

SWITCH

 

O￿

F￿

F

 

ON

LOW-FIRE￿

ADJUSTMENT￿ ALLEN SCREW￿ (UNDER CAP)

HIGH-FIRE￿

ADJUSTMENT￿ ALLEN SCREW￿ (UNDER CAP)

30

120

240

600

80

45

90

225

31

116

232

581

82

44

88

220

32

113

225

563

84

43

86

214

33

109

218

545

86

42

84

209

34

106

212

529

88

41

82

205

35

103

206

514

90

40

80

200

36

100

200

500

92

39

78

196

37

97

195

486

94

38

76

192

38

95

189

474

96

38

75

188

39

92

185

462

98

37

74

184

40

90

180

450

100

36

72

180

41

88

176

439

102

35

71

178

42

86

172

429

104

35

69

173

43

84

167

419

106

34

68

170

44

82

164

409

108

33

67

167

45

80

160

400

110

33

65

164

46

78

157

391

112

32

64

161

47

76

153

383

116

31

62

155

48

75

150

375

120

30

60

150

49

73

147

367

 

 

 

 

a.Place duct thermometers in return and supply ducts as near furnace as possible. Be sure thermometers do not see heat exchangers so that radiant heat will not affect thermometer readings. This is particularly important with straight-run ducts.

b.When thermometer readings stabilize, subtract return-air temperature from supply-air temperature to determine tem- perature rise.

NOTE: If temperature rise is outside this range, first check: (1.) Gas input for low- and high-heat operation.

(2.) Derate for altitude if applicable.

(3.) Return and supply ducts for excessive restrictions

causing static pressures greater than 0.50-in. wc.

c. Adjust air temperature rise by adjusting blower speed. Increase blower speed to reduce temperature rise. Decrease blower speed to increase temperature rise. For high heat, speed selection can be med-high, med (5-speed blowers only), or med-low (factory setting). For low heat, speed tap selection can be low (factory setting), med-low, or med (5-speed blowers only).

MANIFOLD￿

PRESSURE￿

TAP

A97358

Fig. 19—Redundant Automatic Gas Control Valve

BURNER FLAME

BURNER

MANIFOLD

Fig. 20—Burner Flame

A89020

 

Disconnect electrical power before changing speed tap (or removing motor lead cap if used on 5-speed motors). A failure to follow this warning can cause personal injury or death.

NOTE: For furnaces with 5-speed motors, ensure that unused speed tap is either capped or, placed on SPARE terminal on control board before power is restored.

d. To change motor speed selection for high heat, remove blower motor lead from control HIGH-GAS-HEAT termi- nal. (See Fig. 14 and Fig. 18.) Select desired blower motor speed lead from 1 of the other terminals and relocate it to HIGH-GAS-HEAT terminal. See Table 11 for lead color identification. Reconnect original lead to SPARE terminal (or use insulating cap, if used, applies only to furnaces with 5-speed blower motors). Follow this same procedure for proper selection of cool and low-gas-heat speed selection.

6.Set thermostat heat anticipator.

a.When using a nonelectronic thermostat, the thermostat heat anticipation must be set to match amp draw of electrical

21

Image 21
Contents SUPPLY-AIR Plenum Installation Electrostatic Discharge ESD PrecautionsUnit Size Vent Conn SHIP. WT Dimensional Drawing DimensionsMinimum Inches Clearance to Combustible Construction Location Relative to Cooling Equipment GeneralHazardous Locations Unconfined SpaceConfined Space Air for Combustion Ventilation from Outdoors → Downflow InstallationFree Area Of Combustion Air Opening Installation on Combustible FloorInput Furnace Plenum Opening Floor Opening CasingConstruct Working Platform Install Furnace→ -Horizontal Crawlspace Installation on Hanger Rods Typical Attic Installation→ -Horizontal Installation on Blocks Furnace Casing Width FiltersNominal Internal Length of Pipe FT Iron Pipe Diameter Size Accessories WiringSetup Switch Description Electrical DataAmps Gage FT‡ CKT BKR AMPS† Desired Heating Setup Switch Mode Blower OFF → -Setup Switches on Control Center Factory SettingsDelay SEC Sequence of OperationConnection Diagram → -Unit Wiring DiagramPage Page Adjustments START-UP ProceduresUnited States Altitude Derate Multiplier for U.S.AExample CanadaBTU/CU FT 725 1.6 625 1.4 → -Redundant Automatic Gas Control Valve Gas Rate Cu Ft/HrCheck Safety Controls Speed SelectionColor Speed AS Shipped Checklist Service Training

58TMA specifications

The Carrier 58TMA is a high-efficiency gas furnace designed to provide reliable heating solutions for residential spaces. As part of Carrier's extensive range of heating products, the 58TMA series exemplifies innovation in home comfort technology, offering advanced features that cater to both performance and energy savings.

One of the standout features of the Carrier 58TMA is its variable-speed blower motor. This technology allows for precise airflow control, ensuring consistent temperatures throughout the home while minimizing energy consumption. The variable-speed operation also contributes to quieter operation, enhancing indoor comfort without the disruptive noise commonly associated with traditional furnaces.

The furnace operates with a multi-stage gas valve, enhancing its efficiency. With the ability to modulate heating output based on demand, the 58TMA ensures that the home is heated only as needed. This not only improves energy efficiency but also maintains a more stable and comfortable indoor environment. The combination of the multi-stage gas valve and variable-speed blower results in significant energy cost savings for homeowners.

Another impressive aspect of the Carrier 58TMA is its high Annual Fuel Utilization Efficiency (AFUE) rating. With an AFUE of up to 96%, this gas furnace is engineered to convert a majority of the fuel it consumes into heat, reducing waste and lowering utility bills. Such efficiency ratings make the 58TMA an attractive option for eco-conscious consumers looking to minimize their carbon footprint.

In addition to efficiency and performance, the Carrier 58TMA is designed with durability in mind. The unit features a robust cabinet made from high-quality materials, along with an advanced heat exchanger that ensures long-lasting performance. Moreover, it comes equipped with an advanced electrical ignition system, providing reliable start-up under various conditions without the need for a pilot light.

For added convenience, the 58TMA can be integrated with Carrier's Smart Thermostat technology. This allows homeowners to monitor and adjust their heating settings remotely, facilitating an optimized comfort experience while further enhancing energy savings.

Overall, the Carrier 58TMA's combination of efficiency, advanced technology, and durability makes it a standout option in the market for homeowners seeking dependability and energy savings in their heating solutions. With its innovative features and user-friendly operation, the 58TMA represents a significant advancement in modern furnace design, providing peace of mind and comfort year after year.