Pr.

Explanation

Settings

Factory

NOTE

 

 

 

Setting

 

 

 

 

 

 

 

 

12.18

Max. ACI3 Input

0.0 to 20.0mA

20.0

 

 

Current

 

 

 

 

 

 

 

 

 

12.19

Max. ACI3 Scale

0.0 to 100.0%

100.0

 

 

Percentage

 

 

 

 

 

 

 

 

 

12.20

AO1 Terminal

0: AVO1

0

 

 

1: ACO1 (analog current 0.0 to 20.0mA)

 

 

Analog Signal Mode

 

 

 

 

 

2: ACO1 (analog current 4.0 to 20.0mA)

 

 

 

 

 

 

 

 

 

 

12.21

AO1 Analog Output

0: Analog Frequency

0

 

 

Signal

1: Analog Current (0 to 250% rated current)

 

 

 

 

 

 

 

 

12.22

AO1 Analog Output

1 to 200%

100

 

 

Gain

 

 

 

 

 

 

 

 

 

12.23

AO2 Terminal

0: AVO2

0

 

 

1: ACO2 (analog current 0.0 to 20.0mA)

 

 

Analog Signal Mode

 

 

 

 

 

2: ACO2 (analog current 4.0 to 20.0mA)

 

 

 

 

 

 

 

 

 

 

12.24

AO2 Analog Output

0: Analog Frequency

0

 

 

Signal

1: Analog Current (0 to 250% rated current)

 

 

 

 

 

 

 

 

12.25

AO2 Analog Output

1 to 200%

100

 

 

Gain

 

 

 

 

 

 

 

 

 

 

 

 

Group 13: PG function Parameters for Extension Card

 

 

 

 

 

 

 

0: Disabled

 

 

 

13.00

PG Input

1: Single phase

0

 

 

2: Forward/Counterclockwise rotation

 

 

 

 

 

 

 

 

 

 

 

 

 

3: Reverse/Clockwise rotation

 

 

 

 

13.01

PG Pulse Range

1 to 20000

600

 

 

13.02

Motor Pole Number

2 to 10

4

 

 

(Motor 0)

 

 

 

 

 

 

 

 

 

13.03

Proportional Gain

0.0 to 10.0

1.0

 

 

(P)

 

 

 

 

 

 

 

 

 

 

13.04

Integral Gain (I)

0.00 to 100.00 sec

1.00

 

 

 

 

 

Speed Control

 

 

 

 

13.05

Output Frequency

0.00 to 100.00Hz

10.00

 

 

 

 

 

Limit

 

 

 

 

13.06

Speed Feedback

0 to 9999 (*2ms)

500

 

 

Display Filter

 

 

 

 

 

 

 

 

 

 

 

 

Detection Time for

0.0: disabled

 

 

 

13.07

Feedback Signal

1

 

 

0.1 to 10.0 sec

 

 

 

 

 

Fault

 

 

 

 

 

 

 

 

 

 

 

 

 

Treatment of the

0: Warn and RAMP to stop

 

 

 

13.08

Feedback Signal

1: Warn and COAST to stop

1

 

 

 

 

 

Fault

2: Warn and keep operation

 

 

 

13.09

Speed Feedback

0 to 9999 (*2ms)

16

 

 

Filter

 

 

 

 

 

 

 

 

 

13.10

Source of the High-

0: PG card

Read

 

 

speed Counter

1: PLC (NOT for VFD*E*C models)

Only

 

 

 

 

 

 

 

Fault Codes

English- 30

Page 30
Image 30