| Pr. | Explanation | Settings | Factory | NOTE |
|
|
| Setting |
| ||||
|
|
|
|
|
|
| |
| 03.05 | Terminal Count | 0 to 9999 | 0 |
|
| |
|
|
| Value |
|
|
|
|
03.06 | Preliminary Count | 0 to 9999 | 0 |
|
| ||
Value |
|
| |||||
|
|
|
|
|
|
| |
03.07 | EF Active When | 0: Terminal count value attained, no EF | 0 |
|
| ||
Terminal Count | display |
|
| ||||
|
|
| Value Attained | 1: Terminal count value attained, EF active |
|
|
|
|
|
|
| 0: Fan always ON |
|
|
|
|
|
|
| 1: 1 minute after AC motor drive stops, fan |
|
|
|
|
|
|
| will be OFF |
|
|
|
03.08 | Fan Control | 2: Fan ON when AC motor drive runs, fan | 0 |
|
| ||
|
|
|
| OFF when AC motor drive stops |
|
|
|
|
|
|
| 3: Fan ON when preliminary heatsink |
|
|
|
|
|
|
| temperature attained |
|
|
|
|
|
|
| Read only |
|
|
|
|
|
|
| Bit0=1:RLY used by PLC |
|
|
|
|
|
| The Digital Output | Bit1=1:MO1 used by PLC |
|
|
|
|
|
| Bit2=1:MO2/RA2 used by PLC |
|
|
| |
|
|
| Used by PLC |
|
|
| |
03.09 | Bit3=1:MO3/RA3 used by PLC | ## |
|
| |||
(NOT for VFD*E*C |
|
| |||||
|
|
| Bit4=1:MO4/RA4 used by PLC |
|
|
| |
|
|
| models) |
|
|
| |
|
|
| Bit5=1:MO5/RA5 used by PLC |
|
|
| |
|
|
|
|
|
|
| |
|
|
|
| Bit6=1:MO6/RA6 used by PLC |
|
|
|
|
|
|
| Bit7=1:MO7/RA7 used by PLC |
|
|
|
|
|
| The Analog Output | Read only |
|
|
|
03.10 | Used by PLC | Bit0=1:AFM used by PLC | ## |
|
| ||
(NOT for VFD*E*C | Bit1=1: AO1 used by PLC |
|
| ||||
|
|
|
|
|
| ||
|
|
| models) | Bit2=1: AO2 used by PLC |
|
|
|
03.11 | Brake Release | 0.00 to 20.00Hz | 0.00 |
|
| ||
Frequency |
|
| |||||
|
|
|
|
|
|
| |
03.12 | Brake Engage | 0.00 to 20.00Hz | 0.00 |
|
| ||
Frequency |
|
| |||||
|
|
|
|
|
|
| |
|
|
|
| Read only |
|
|
|
|
|
|
| Bit0: RLY Status |
|
|
|
|
|
|
| Bit1: MO1 Status |
|
|
|
|
|
| Display the Status of | Bit2: MO2/RA2 Status |
|
|
|
03.13 | Bit3: MO3/RA3 Status | ## |
|
| |||
|
|
| Output Terminals | Bit4: MO4/RA4 Status |
|
|
|
|
|
|
| Bit5: MO5/RA5 Status |
|
|
|
|
|
|
| Bit6: MO6/RA6 Status |
|
|
|
|
|
|
| Bit7: MO7/RA7 Status |
|
|
|
| 03.14 | Desired Frequency | 0.00 to 600.0Hz | 0.00 |
|
| |
|
|
| 2 Attained |
|
|
|
|
|
|
| Group 4 Input Function Parameters |
|
|
| |
04.00 | Keypad | 0.0 to 100.0 % | 0.0 |
|
| ||
Potentiometer Bias |
|
| |||||
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
04.01 | Keypad | 0: Positive bias | 00 |
|
| ||
Potentiometer Bias | 1: Negative bias |
|
| ||||
|
|
| Polarity |
|
|
|
|
04.02 | Keypad | 0.1 to 200.0 % | 100.0 |
|
| ||
Potentiometer Gain |
|
| |||||
|
|
|
|
|
|
|
English- 17