Delta Electronics VFD-XXXE quick start Explanation Settings Factory Setting, For VFD*E*C models

Models: VFD-XXXE

1 36
Download 36 pages 29.99 Kb
Page 16
Image 16

Pr.

Explanation

Settings

Factory Setting

NOTE

 

Initial Frequency

0: by Current Freq Command

 

 

02.14

Selection (for

1: by Zero Freq Command

0

 

keypad &

2: by Frequency Display at Stop

 

 

 

 

 

RS485/USB)

 

 

 

 

Initial Frequency

 

 

 

02.15

Setpoint (for keypad

0.00 ~ 600.0Hz

60.00

 

 

& RS485/USB)

 

 

 

 

 

Read Only

 

 

 

Display the Master

Bit0=1: by First Freq Source (Pr.02.00)

 

 

 

Bit1=1: by Second Freq Source (Pr.02.09)

 

 

02.16

Freq Command

##

 

Bit2=1: by Multi-input function

 

 

Source

 

 

 

Bit3=1: by PLC Freq command (NOT for

 

 

 

 

 

 

 

 

VFD*E*C models)

 

 

 

 

Read Only

 

 

 

 

Bit0=1: by Digital Keypad

 

 

 

Display the

Bit1=1: by RS485 communication

 

 

 

Bit2=1: by External Terminal 2/3 wire mode

##

 

02.17

Operation

 

Bit3=1: by Multi-input function

 

 

Command Source

 

 

 

Bit4=1: by PLC Operation Command (NOT

 

 

 

 

 

 

 

 

for VFD*E*C models)

 

 

 

 

Bit5=1: by CANopen communication

 

 

 

Group 3 Output Function Parameters

 

 

 

 

0: No function

8

 

 

Multi-function

1: AC drive operational

 

 

03.00

Output Relay (RA1,

2: Master frequency attained

 

 

 

RB1, RC1)

3: Zero speed

 

 

 

 

4: Over torque detection

 

 

 

 

5: Base-Block (B.B.) indication

1

 

 

 

6: Low-voltage indication

 

 

 

 

7: Operation mode indication

 

 

 

 

8: Fault indication

 

 

 

 

9: Desired frequency 1 attained

 

 

 

 

10: Terminal count value attained

 

 

 

 

11: Preliminary count value attained

 

 

 

 

12: Over Voltage Stall supervision

 

 

 

Multi-function

13: Over Current Stall supervision

 

 

 

14: Heat sink overheat warning

 

 

03.01

Output Terminal

 

 

15: Over Voltage supervision

 

 

 

MO1

 

 

 

16: PID supervision

 

 

 

 

 

 

 

 

17: Forward command

 

 

 

 

18: Reverse command

 

 

 

 

19: Zero speed output signal

 

 

 

 

20: Warning(FbE,Cexx, AoL2, AUE, SAvE)

 

 

 

 

21: Brake control (Desired frequency

 

 

 

 

attained)

 

 

 

 

22: Drive ready

 

 

 

 

23: Desired frequency 2 attained

 

 

03.02

Desired Frequency

0.00 to 600.0Hz

0.00

 

 

1 Attained

 

 

 

03.03

Analog Output

0: Analog frequency meter

0

 

Signal Selection

1: Analog current meter

 

 

(AFM)

 

 

 

03.04

Analog Output Gain

1 to 200%

100

 

English- 16

Page 16
Image 16