Pr.

Explanation

Settings

Factory

NOTE

 

 

 

Setting

 

 

 

 

 

 

 

 

 

 

 

Mid-Point

0.10 to 600.0 Hz

 

 

 

01.40

Frequency (Fmid)

1.50

 

 

 

 

 

(Motor 3)

 

 

 

 

01.41

Mid-Point Voltage

115V/230V series: 0.1V to 255.0V

10.0

 

 

(Vmid) (Motor 3)

460V series: 0.1V to 510.0V

20.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01.42

Minimum Output

0.10 to 600.0 Hz

1.50

 

 

Frequency (Fmin)

 

 

 

 

 

(Motor 3)

 

 

 

 

01.43

Minimum Output

115V/230V series: 0.1V to 255.0V

10.0

 

 

Voltage (Vmin)

460V series: 0.1V to 510.0V

20.0

 

 

 

 

 

(Motor 3)

 

 

 

 

 

Group 2 Operation Method Parameters

 

 

 

 

 

 

 

0: Digital keypad UP/DOWN keys or Multi-

 

 

 

 

 

 

 

function Inputs UP/DOWN. Last used

 

 

 

 

 

 

 

frequency saved.

 

 

 

 

 

 

Source of First

1: 0 to +10V from AVI

 

 

 

 

 

 

2: 4 to 20mA from ACI or 0 to +10V from

1

 

 

02.00

Master Frequency

 

 

AVI2

 

 

 

 

 

 

Command

 

 

 

 

 

 

3: RS-485 (RJ-45)/USB communication

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4: Digital keypad potentiometer

 

 

 

 

 

 

 

5: CANopen communication

 

 

 

 

 

 

 

For VFD*E*C models, the factory setting is

5

 

 

 

 

 

 

0: Digital keypad

 

 

 

 

 

 

 

1: External terminals. Keypad STOP/RESET

 

 

 

 

 

 

 

enabled.

 

 

 

 

 

 

 

2: External terminals. Keypad STOP/RESET

 

 

 

 

 

 

Source of First

disabled.

1

 

 

 

 

 

3: RS-485 (RJ-45)/USB communication.

 

 

02.01

Operation

 

 

Keypad STOP/RESET enabled.

 

 

 

 

 

 

Command

 

 

 

 

 

 

4: RS-485 (RJ-45)/USB communication.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Keypad STOP/RESET disabled.

 

 

 

 

 

 

 

5: CANopen communication. Keypad

 

 

 

 

 

 

 

STOP/RESET disabled.

 

 

 

 

 

 

 

For VFD*E*C models, the factory setting is

5

 

 

 

 

 

 

0: STOP: ramp to stop; E.F.: coast to stop

 

 

 

02.02

Stop Method

1: STOP: coast to stop; E.F.: coast to stop

0

 

 

2: STOP: ramp to stop; E.F.: ramp to stop

 

 

 

 

 

 

3: STOP: coast to stop; E.F.: ramp to stop

 

 

 

 

 

 

PWM Carrier

 

 

 

 

02.03

Frequency

1 to 15kHz

8

 

 

 

 

 

Selections

 

 

 

 

 

 

 

Motor Direction

0: Enable forward/reverse operation

 

 

 

02.04

1: Disable reverse operation

0

 

 

Control

 

 

 

 

 

2: Disabled forward operation

 

 

 

 

 

 

 

 

 

 

English- 14

Page 14
Image 14
Delta Electronics VFD-XXXE quick start Group 2 Operation Method Parameters, AVI2