Delta Electronics VFD-XXXE quick start Setting

Models: VFD-XXXE

1 36
Download 36 pages 29.99 Kb
Page 23
Image 23

 

Pr.

Explanation

Settings

Factory

NOTE

 

 

Setting

 

 

 

 

 

 

 

 

 

Motor PTC

 

 

 

 

07.15

Overheat Warning

0.1~10.0V

1.2

 

 

 

 

Level

 

 

 

 

 

 

Motor PTC

 

 

 

 

07.16

Overheat Reset

0.1~5.0V

0.6

 

 

 

 

Delta Level

 

 

 

 

07.17

Treatment of the

0: Warn and RAMP to stop

0

 

 

Motor PTC

1: Warn and COAST to stop

 

 

 

 

Overheat

2: Warn and keep running

 

 

 

07.18

Motor Rated Current

30 %FLA to 120% FLA

FLA

 

 

 

 

(Motor 1)

 

 

 

 

07.19

Motor No-Load

0%FLA to 99% FLA

0.4*FLA

 

 

Current (Motor 1)

 

 

 

 

 

 

 

 

07.20

Torque

0.0 to 10.0

0.0

 

 

Compensation

 

 

 

 

(Motor 1)

 

 

 

 

 

 

Slip Compensation

 

 

 

 

07.21

(Used without PG)

0.00 to 10.00

0.00

 

 

 

 

(Motor 1)

 

 

 

 

 

 

Motor Line-to-line

0~65535 mΩ

 

 

 

07.22

Resistance R1

0

 

 

 

 

(Motor 1)

 

 

 

 

07.23

Motor Rated Slip

0.00 to 20.00 Hz

3.00

 

 

(Motor 1)

 

 

 

 

 

 

 

 

07.24

Motor Pole Number

2 to 10

4

 

 

(Motor 1)

 

 

 

 

 

 

 

 

07.25

Motor Rated Current

30 %FLA to 120% FLA

FLA

 

 

 

 

(Motor 2)

 

 

 

 

07.26

Motor No-Load

0%FLA to 99% FLA

0.4*FLA

 

 

Current (Motor 2)

 

 

 

 

 

 

 

 

07.27

Torque

0.0 to 10.0

0.0

 

 

Compensation

 

 

 

 

(Motor 2)

 

 

 

 

 

 

Slip Compensation

 

 

 

 

07.28

(Used without PG)

0.00 to 10.00

0.00

 

 

 

 

(Motor 2)

 

 

 

 

 

 

Motor Line-to-line

0~65535 mΩ

 

 

 

07.29

Resistance R1

0

 

 

 

 

(Motor 2)

 

 

 

 

07.30

Motor Rated Slip

0.00 to 20.00 Hz

3.00

 

 

(Motor 2)

 

 

 

 

 

 

 

 

07.31

Motor Pole Number

2 to 10

4

 

 

(Motor 3)

 

 

 

 

 

 

 

 

07.32

Motor Rated Current

30 %FLA to 120% FLA

FLA

 

 

 

 

(Motor 3)

 

 

 

 

07.33

Motor No-Load

0%FLA to 99% FLA

0.4*FLA

 

 

Current (Motor 3)

 

 

 

 

 

 

 

 

07.34

Torque

0.0 to 10.0

0.0

 

 

Compensation

 

 

 

 

(Motor 3)

 

 

 

 

 

 

Slip Compensation

 

 

 

 

07.35

(Used without PG)

0.00 to 10.00

0.00

 

 

 

 

(Motor 3)

 

 

 

 

English- 23

Page 23
Image 23
Delta Electronics VFD-XXXE quick start Setting