Pr.

Explanation

Settings

 

Factory

NOTE

 

 

 

Setting

 

 

 

 

 

 

 

 

 

 

 

0: Disable PID operation

 

 

 

 

 

 

1: Keypad (based on Pr.02.00)

 

 

 

10.00

PID Set Point

2: 0 to +10V from AVI

0

 

 

Selection

3: 4 to 20mA from ACI or 0 to +10V from

 

 

 

 

 

 

 

 

 

 

AVI2

 

 

 

 

 

 

4: PID set point (Pr.10.11)

 

 

 

 

 

 

0: Positive PID feedback from external

 

 

 

 

 

 

terminal AVI (0 ~ +10VDC)

 

 

 

10.01

Input Terminal for

1: Negative PID feedback from external

0

 

 

terminal AVI (0 ~ +10VDC)

 

 

PID Feedback

 

 

 

 

2: Positive PID feedback from external

 

 

 

 

 

 

 

 

 

 

 

 

terminal ACI (4 ~ 20mA)/ AVI2 (0 ~

 

 

 

 

 

 

+10VDC).

 

 

 

 

 

Input Terminal for

3: Negative PID feedback from external

 

 

 

10.01

terminal ACI (4 ~ 20mA)/ AVI2 (0 ~

0

 

 

PID Feedback

 

 

 

 

+10VDC).

 

 

 

 

 

 

 

 

 

10.02

Proportional Gain

0.0 to 10.0

1.0

 

 

(P)

 

 

 

 

 

 

 

 

 

10.03

Integral Time (I)

0.00 to 100.0 sec (0.00=disable)

1.00

 

 

 

 

 

 

 

 

 

 

 

 

 

10.04

Derivative Control

0.00 to 1.00 sec

0.00

 

 

(D)

 

 

 

 

 

 

 

 

 

 

 

10.05

Upper Bound for

0 to 100%

100

 

 

Integral Control

 

 

 

 

 

 

 

 

 

10.06

Primary Delay Filter

0.0 to 2.5 sec

0.0

 

 

Time

 

 

 

 

 

 

 

 

 

10.07

PID Output Freq

0 to 110%

100

 

 

Limit

 

 

 

 

 

 

 

 

 

 

 

PID Feedback

 

 

 

 

 

10.08

Signal Detection

0.0 to 3600 sec (0.0 disable)

60.0

 

 

 

 

Time

 

 

 

 

 

 

 

Treatment of the

0: Warn and RAMP to stop

 

 

 

10.09

Erroneous PID

1: Warn and COAST to stop

0

 

 

 

 

Feedback Signals

2: Warn and keep operation

 

 

 

10.10

Gain Over the PID

0.0 to 10.0

1.0

 

 

Detection Value

 

 

 

 

 

 

 

 

 

10.11

Source of PID Set

0.00 to 600.0Hz

0.00

 

 

point

 

 

 

 

 

 

 

 

 

 

 

10.12

PID Offset Level

1.0 to 50.0%

10.0

 

 

 

 

 

 

 

 

 

 

10.13

Detection Time of

0.1 to 300.0 sec

5.0

 

 

PID Offset

 

 

 

 

 

 

 

 

 

10.14

Sleep/Wake Up

0.0 to 6550 sec

0.0

 

 

Detection Time

 

 

 

 

 

 

 

 

 

10.15

Sleep Frequency

0.00 to 600.0 Hz

0.00

 

 

 

 

 

 

 

 

10.16

Wakeup Frequency

0.00 to 600.0 Hz

0.00

 

 

 

 

 

 

 

 

 

 

10.17

Minimum PID

0: By PID control

0

 

 

Output Frequency

 

 

1: By minimum output frequency (Pr.01.05)

 

 

 

 

Selection

 

 

 

 

 

 

 

 

 

 

 

 

Group

11 Parameters for Extension Card

 

 

 

English- 27

Page 27
Image 27
Delta Electronics VFD-XXXE quick start AVI2, Parameters for Extension Card