Pr.

Explanation

Settings

Factory

NOTE

 

 

Setting

 

 

 

 

 

 

 

08.17

Auto Energy Saving

0: Disable

0

 

 

1: Enable

 

 

 

 

 

 

 

 

 

 

 

0: AVR function enable

 

 

 

08.18

AVR Function

1: AVR function disable

0

 

 

2: AVR function disable for decel.

 

 

 

 

 

 

 

 

 

 

 

3: AVR function disable for stop

 

 

 

 

 

 

 

 

 

 

08.19

Software Brake

115V / 230V series: 370.0to 430.0V

380.0

 

 

Level

460V series: 740.0 to 860.0V

760.0

 

 

 

 

 

 

 

 

Compensation

0.0~5.0

 

 

 

08.20

Coefficient for Motor

 

0.0

 

 

 

 

Instability

 

 

 

 

08.21

OOB Sampling Time

0.1 to 120.0 sec

1.0

 

 

 

 

 

 

 

 

 

08.22

Number of OOB

00 to 32

20

 

 

Sampling Times

 

 

 

 

 

 

 

 

08.23

OOB Average

Read only

#.#

 

 

Sampling Angle

 

 

 

 

 

 

 

 

08.24

DEB Function

0: Disable

0

 

 

1: Enable

 

 

 

 

 

 

 

 

08.25

DEB Return Time

0 to 250 sec

0

 

 

 

 

 

 

 

 

 

 

 

Group 9 Communication Parameters

 

 

 

09.00

Communication

1 to 254

1

 

 

Address

 

 

 

 

 

 

 

 

 

 

 

0: Baud rate 4800bps

 

 

 

09.01

Transmission Speed

1: Baud rate 9600bps

1

 

 

 

 

 

2: Baud rate 19200bps

 

 

 

 

 

 

3: Baud rate 38400bps

 

 

 

 

 

 

0: Warn and keep operating

 

 

 

09.02

Transmission Fault

1: Warn and ramp to stop

3

 

 

Treatment

2: Warn and coast to stop

 

 

 

 

 

 

 

 

 

 

3: No warning and keep operating

 

 

 

09.03

Time-out Detection

0.1 ~ 120.0 seconds

0.0

 

 

0.0: Disable

 

 

 

 

 

 

 

 

 

 

 

0: 7,N,2 (Modbus, ASCII)

 

 

 

 

 

 

1: 7,E,1 (Modbus, ASCII)

 

 

 

 

 

 

2: 7,O,1 (Modbus, ASCII)

 

 

 

 

 

 

3: 8,N,2 (Modbus, RTU)

 

 

 

 

 

 

4: 8,E,1 (Modbus, RTU)

 

 

 

09.04

Communication

5: 8,O,1 (Modbus, RTU)

0

 

 

Protocol

6: 8,N,1 (Modbus, RTU)

 

 

 

 

 

 

 

 

 

 

7: 8,E,2 (Modbus, RTU)

 

 

 

 

 

 

8: 8,O,2 (Modbus, RTU)

 

 

 

 

 

 

9: 7,N,1 (Modbus, ASCII)

 

 

 

 

 

 

10: 7,E,2 (Modbus, ASCII)

 

 

 

 

 

 

11: 7,O,2 (Modbus, ASCII)

 

 

 

09.05Reserved

09.06Reserved

09.07

Response Delay

0 ~ 200 (unit: 2ms)

1

 

Time

 

 

 

 

 

 