Delta Electronics VFD-XXXE quick start Address only for VFD*E*C models, Only for VFD*E*C

Models: VFD-XXXE

1 36
Download 36 pages 29.99 Kb
Page 26
Image 26

 

Pr.

Explanation

Settings

Factory

NOTE

 

 

Setting

 

 

 

 

 

 

 

 

 

 

0: Baud rate 4800 bps

 

 

 

09.08

Transmission Speed

1: Baud rate 9600 bps

2

 

 

for USB Card

2: Baud rate 19200 bps

 

 

 

 

3: Baud rate 38400 bps

 

 

 

 

 

 

 

 

 

 

 

 

4: Baud rate 57600 bps

 

 

 

 

 

 

0: 7,N,2 for ASCII

 

 

 

 

 

 

1: 7,E,1 for ASCII

 

 

 

 

 

 

2: 7,O,1 for ASCII

 

 

 

 

 

 

3: 8,N,2 for RTU

 

 

 

 

 

Communication

4: 8,E,1 for RTU

 

 

 

 

 

5: 8,O,1 for RTU

 

 

 

09.09

Protocol for USB

1

 

 

6: 8,N,1 (Modbus, RTU)

 

 

 

 

Card

 

 

 

 

 

7: 8,E,2 (Modbus, RTU)

 

 

 

 

 

 

 

 

 

 

 

 

8: 8,O,2 (Modbus, RTU)

 

 

 

 

 

 

9: 7,N,1 (Modbus, ASCII)

 

 

 

 

 

 

10: 7,E,2 (Modbus, ASCII)

 

 

 

 

 

 

11: 7,O,2 (Modbus, ASCII)

 

 

 

 

 

Transmission Fault

0: Warn and keep operating

 

 

 

09.10

1: Warn and ramp to stop

0

 

 

Treatment for USB

 

 

2: Warn and coast to stop

 

 

 

 

Card

 

 

 

 

 

3: No warning and keep operating

 

 

 

 

 

 

 

 

 

09.11

Time-out Detection

0.1 ~ 120.0 seconds

0.0

 

 

for USB Card

0.0: Disable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COM port for PLC

 

 

 

 

09.12

Communication

0: RS485

0

 

 

(NOT for VFD*E*C

1: USB card

 

 

 

 

 

 

 

 

 

models)

 

 

 

 

 

 

CANopen

 

 

 

 

09.13

Communication

0: disable

1

 

 

Address (ONLY for

1: 1 to 127

 

 

 

 

 

 

 

 

 

VFD*E*C models)

 

 

 

 

 

 

 

0: 1M

 

 

 

 

 

CANbus Baud Rate

1: 500K

 

 

 

 

 

2: 250K

 

 

 

09.14

(ONLY for VFD*E*C

5

 

 

3: 125K

 

 

 

 

models)

4: 100K

 

 

 

 

 

 

5: 50K

 

 

 

 

 

Gain of CANbus

 

 

 

 

09.15

Frequency

0.00~2.00

1.00

 

 

(ONLY for VFD*E*C

 

 

 

 

models)

 

 

 

 

 

 

 

bit 0 : CANopen Guarding Time out

 

 

 

 

 

 

bit 1 : CANopen Heartbeat Time out

 

 

 

 

 

CANbus Warning

bit 2 : CANopen SYNC Time out

 

 

 

 

 

bit 3 : CANopen SDO Time out

Read-

 

 

09.16

(ONLY for VFD*E*C

 

 

bit 4 : CANopen SDO buffer overflow

only

 

 

 

 

models)

bit 5 : CAN Bus Off

 

 

 

 

 

 

bit 6 : Error protocol of CANopen

 

 

 

 

 

 

bit 7 : CANopen boot up fault

 

 

 

 

 

Group 10 PID Control Parameters

 

 

 

English- 26

Page 26
Image 26
Delta Electronics VFD-XXXE Address only for VFD*E*C models, Only for VFD*E*C Models, Group 10 PID Control Parameters