| Pr. | Explanation | Settings |
| Factory | NOTE |
|
|
|
| Setting |
| ||||
|
|
|
|
|
|
|
| |
|
|
| Motor | 0~65535 mΩ |
|
|
| |
07.36 | Resistance R1 | 0 |
|
| ||||
|
|
| (Motor 3) |
|
|
|
|
|
07.37 | Motor Rated Slip | 0.00 to 20.00 Hz | 3.00 |
|
| |||
(Motor 3) |
|
| ||||||
|
|
|
|
|
|
|
| |
07.38 | Motor Pole Number | 2 to 10 | 4 |
|
| |||
(Motor 3) |
|
| ||||||
|
|
|
|
|
|
|
| |
|
|
|
| Group 8 Special Parameters |
|
|
| |
08.00 | DC Brake Current | 0 to 100% | 0 |
|
| |||
Level |
|
| ||||||
|
|
|
|
|
|
|
| |
08.01 | DC Brake Time | 0.0 to 60.0 sec | 0.0 |
|
| |||
during |
|
| ||||||
|
|
|
|
|
|
|
| |
08.02 | DC Brake Time | 0.0 to 60.0 sec | 0.0 |
|
| |||
during Stopping |
|
| ||||||
|
|
|
|
|
|
|
| |
08.03 | 0.00 to 600.0Hz | 0.00 |
|
| ||||
Brake |
|
| ||||||
|
|
|
|
|
|
|
| |
|
|
|
| 0: Operation stops after momentary power |
|
|
| |
|
|
|
| loss |
|
|
| |
|
|
| Momentary Power | 1: Operation continues after momentary |
|
|
| |
|
|
| power loss, speed search starts with the | 0 |
|
| ||
08.04 | Loss Operation |
|
| |||||
Master Frequency reference value |
|
| ||||||
|
|
| Selection |
|
|
| ||
|
|
| 2: Operation continues after momentary |
|
|
| ||
|
|
|
| power loss, speed search starts with the |
|
|
| |
|
|
|
| minimum frequency |
|
|
| |
|
|
|
|
|
|
|
|
|
08.05 | Maximum Allowable | 0.1 to 5.0 sec | 2.0 |
|
| |||
Power Loss Time |
|
| ||||||
|
|
|
|
|
|
|
| |
|
|
|
| 0: Disable speed search |
|
|
| |
08.06 | 1: Speed search starts with last frequency | 1 |
|
| ||||
Search | command |
|
| |||||
|
|
|
|
|
| |||
|
|
|
| 2: Starts with minimum output frequency |
|
|
| |
08.07 | B.B. Time for Speed | 0.1 to 5.0 sec | 0.5 |
|
| |||
|
|
| Search |
|
|
|
|
|
08.08 | Current Limit for | 30 to 200% | 150 |
|
| |||
Speed Search |
|
| ||||||
|
|
|
|
|
|
|
| |
08.09 | Skip Frequency 1 | 0.00 to 600.0 Hz | 0.00 |
|
| |||
Upper Limit |
|
| ||||||
|
|
|
|
|
|
|
| |
08.10 | Skip Frequency 1 | 0.00 to 600.0 Hz | 0.00 |
|
| |||
Lower Limit |
|
| ||||||
|
|
|
|
|
|
|
| |
08.11 | Skip Frequency 2 | 0.00 to 600.0 Hz | 0.00 |
|
| |||
Upper Limit |
|
| ||||||
|
|
|
|
|
|
|
| |
08.12 | Skip Frequency 2 | 0.00 to 600.0 Hz | 0.00 |
|
| |||
Lower Limit |
|
| ||||||
|
|
|
|
|
|
|
| |
08.13 | Skip Frequency 3 | 0.00 to 600.0 Hz | 0.00 |
|
| |||
Upper Limit |
|
| ||||||
|
|
|
|
|
|
|
| |
08.14 | Skip Frequency 3 | 0.00 to 600.0 Hz | 0.00 |
|
| |||
Lower Limit |
|
| ||||||
|
|
|
|
|
|
|
| |
| 08.15 | Auto Restart After | 0 to 10 (0=disable) | 0 |
|
| ||
|
|
| Fault |
|
|
|
|
|
08.16 | Auto Reset Time at | 0.1 to 6000 sec | 60.0 |
|
| |||
Restart after Fault |
|
| ||||||
|
|
|
|
|
|
|
|
English- 24