The Specification for the Control Terminals

RA RB RC

The position of the control terminals

Terminals 1

 

 

 

 

 

AFM MCM MO1

 

 

 

Terminals 2

 

 

 

 

 

 

 

RS-485 port

MI1

MI2 MI3

MI4

MI5 MI6 DCM DCM 24V ACM

AVI

ACI 10V

 

Frame

Control Terminals

Torque

 

A, B, C

Terminals 1

5 kgf-cm (4.4 in-lbf)

 

Terminals 2

2 kgf-cm (2 in-lbf)

 

 

 

 

 

 

Wire

12-24 AWG (3.3-0.2mm2)

16-24 AWG (1.3-0.2mm2)

NOTE

Frame A: VFD002E11A/21A/23A, VFD004E11A/21A/23A/43A, VFD007E21A/23A/43A, VFD015E23A/43A, VFD002E11C/21C/23C, VFD004E11C/21C/23C/43C, VFD007E21C/23C/43C, VFD015E23C/43C, VFD002E11T/21T/23T, VFD004E11T/21T/23T/43T, VFD007E21T/23T/43T, VFD015E23T/43T, VFD002E11P/21P/23P, VFD004E11P/21P/23P/43P, VFD007E21P/23P/43P, VFD015E23P/43P

Frame B: VFD007E11A, VFD015E21A, VFD022E21A/23A/43A, VFD037E23A/43A

Frame C: VFD055E23A/43A, VFD075E23A/43A, VFD110E43A

Control Terminals Explanations

 

 

Terminal

Terminal Function

 

Factory Settings (NPN mode)

 

 

 

 

Symbol

 

ON: Connect to DCM

 

 

 

 

 

 

 

 

 

 

MI1

Forward-Stop command

ON:

Run in MI1 direction

 

 

 

OFF:

Stop acc. to Stop Method

 

 

 

 

 

 

 

MI2

Reverse-Stop command

ON:

Run in MI2 direction

 

 

OFF:

Stop acc. to Stop Method

 

 

 

 

 

 

 

MI3

Multi-function Input 3

Refer to Pr.04.05 to Pr.04.08 for programming the

 

 

MI4

Multi-function Input 4

 

 

Multi-function Inputs.

 

 

 

 

ON: the activation current is 5.5mA .

 

 

MI5

Multi-function Input 5

 

 

OFF: leakage current tolerance is 10μA.

 

 

MI6

Multi-function Input 6

 

 

 

 

 

 

 

 

+24V

DC Voltage Source

+24VDC, 20mA used for PNP mode.

 

 

 

RA

Multi-function Relay output

Resistive Load:

 

 

(N.O.) a

5A(N.O.)/3A(N.C.) 240VAC

 

 

 

 

 

 

 

5A(N.O.)/3A(N.C.) 24VDC

 

 

 

Multi-function Relay output

 

 

RB

Inductive Load:

 

 

(N.C.) b

 

 

 

1.5A(N.O.)/0.5A(N.C.) 240VAC

 

 

 

 

 

 

RC

Multi-function Relay common

1.5A(N.O.)/0.5A(N.C.) 24VDC

 

 

Refer to Pr.03.00 for programming

 

 

 

 

 

 

 

 

 

 

 

DCM

Digital Signal Common

Common for digital inputs and used for NPN

 

 

 

mode.

 

 

 

 

 

 

 

 

 

 

 

 

 

English- 9

 

 

 

Page 9
Image 9
Delta Electronics VFD-XXXE quick start Specification for the Control Terminals, Control Terminals Explanations