| Fault | Fault Descriptions |
| Corrective Actions |
|
| |
| Name |
|
|
| |||
|
|
|
|
|
|
| |
|
|
| 1. | Check if the motor is suitable for operation by |
| ||
|
| Auto accel/decel failure |
| AC motor drive. | |||
|
| 2. | Check if the regenerative energy is too large. | ||||
|
|
| |||||
|
|
| 3. | Load may have changed suddenly. | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| Return to the factory. | |||||
|
| OV or LV | |||||
|
|
|
|
|
|
| |
|
| Temperature sensor error |
|
|
|
|
|
|
|
|
|
|
| ||
|
|
| 1. | Check parameter settings (Pr.10.01) and |
| ||
|
|
|
| AVI/ACI wiring. | |||
|
| PID feedback signal error | 2. | Check for possible fault between system | |||
|
|
|
| response time and the PID feedback signal | |||
|
|
|
| detection time (Pr.10.08) |
| ||
|
| Analog signal error | Check the wiring of ACI | ||||
|
| Phase Loss | Check Power Source Input if all 3 input phases are |
| |||
|
| connected without loose contacts. | |||||
|
|
| |||||
|
|
| When (one of) the output terminal(s) is grounded, |
| |||
|
|
| short circuit current is more than 50% of AC motor | ||||
|
|
| drive rated current, the AC motor drive power | ||||
|
|
| module may be damaged. | ||||
|
| Ground fault | NOTE: The short circuit protection is provided | ||||
|
| for AC motor drive protection, not for protection | |||||
|
|
| of the user. | ||||
|
|
| 1. | Check whether the IGBT power module is | |||
|
|
|
| damaged. | |||
|
|
| 2. | Check for possible poor insulation at the output | |||
|
|
|
| line. | |||
|
|
| 1. | Check the RS485 connection between the AC |
| ||
|
|
|
| motor drive and RS485 master for loose wires | |||
|
|
|
| and wiring to correct pins. | |||
|
| Communication Error | 2. | Check if the communication protocol, address, | |||
|
|
| transmission speed, etc. are properly set. | ||||
|
|
|
| ||||
|
|
| 3. | Use the correct checksum calculation. | |||
|
|
| 4. | Please refer to group 9 in the chapter 5 for | |||
|
|
|
| detail information. | |||
|
| Auto Tuning Error | 1. | Check cabling between drive and motor |
| ||
|
| 2. | Retry again | ||||
|
|
| |||||
|
| Communication | 1. | Press RESET key to set all parameters to |
| ||
|
| error on the control board |
| factory setting. | |||
|
| or power board | 2. | Return to the factory. |
| ||
|
| Motor overheat protection | 1. | Check if the motor is overheat | |||
|
| 2. | Check Pr.07.12 to Pr.07.17 settings | ||||
|
|
| |||||
|
| PG signal error | 1. | Check the wiring of PG card |
| ||
|
| 2. | Try another PG card | ||||
|
|
| |||||
|
| CANopen Guarding Time out | Connect to CAN bus again and reset CAN bus |
| |||
|
| (Only for VFDxxxExxC) |
|
|
|
|
|
|
| CANopen Heartbeat Time out | Connect to CAN bus again and reset CAN bus |
| |||
|
| (Only for VFDxxxExxC) |
|
|
|
|
|