Delta Electronics VFD-XXXE Group 5 Multi-Step Speeds Parameters, Group 6 Protection Parameters

Models: VFD-XXXE

1 36
Download 36 pages 29.99 Kb
Page 20
Image 20

 

Pr.

Explanation

Settings

Factory

NOTE

 

 

Setting

 

 

 

 

 

 

 

 

 

 

Bit8: MI9 Status

 

 

 

 

 

 

Bit9: MI10 Status

 

 

 

 

 

 

Bit10: MI11 Status

 

 

 

 

 

 

Bit11: MI12 Status

 

 

 

 

 

Internal/External

0~4095

0

 

 

04.27

Multi-function Input

 

 

 

 

 

 

Terminals Selection

 

 

 

 

04.28

Internal Terminal

0~4095

0

 

 

Status

 

 

 

 

 

 

 

 

 

 

Group 5 Multi-Step Speeds Parameters

05.00

1st Step Speed

0.00 to 600.0 Hz

0.00

 

 

 

Frequency

 

 

 

05.01

2nd Step Speed

0.00 to 600.0 Hz

0.00

 

 

 

Frequency

 

 

 

05.02

3rd Step Speed

0.00 to 600.0 Hz

0.00

 

 

 

Frequency

 

 

 

05.03

4th Step Speed

0.00 to 600.0 Hz

0.00

 

 

 

Frequency

 

 

 

05.04

5th Step Speed

0.00 to 600.0 Hz

0.00

 

 

 

Frequency

 

 

 

05.05

6th Step Speed

0.00 to 600.0 Hz

0.00

 

 

 

Frequency

 

 

 

05.06

7th Step Speed

0.00 to 600.0 Hz

0.00

 

 

 

Frequency

 

 

 

05.07

8th Step Speed

0.00 to 600.0 Hz

0.00

 

 

 

Frequency

 

 

 

05.08

9th Step Speed

0.00 to 600.0 Hz

0.00

 

 

 

Frequency

 

 

 

05.09

10th Step Speed

0.00 to 600.0 Hz

0.00

 

 

 

Frequency

 

 

 

05.10

11th Step Speed

0.00 to 600.0 Hz

0.00

 

 

 

Frequency

 

 

 

05.11

12th Step Speed

0.00 to 600.0 Hz

0.00

 

 

 

Frequency

 

 

 

05.12

13th Step Speed

0.00 to 600.0 Hz

0.00

 

 

 

Frequency

 

 

 

05.13

14th Step Speed

0.00 to 600.0 Hz

0.00

 

 

 

Frequency

 

 

 

05.14

15th Step Speed

0.00 to 600.0 Hz

0.00

 

 

 

Frequency

 

 

 

 

 

 

Group 6 Protection Parameters

 

 

06.00

Over-Voltage Stall

115/230V series: 330.0V to 410.0V

390.0V

 

460V series: 660.0V to 820.0V

780.0V

 

Prevention

 

 

 

0.0: Disable over-voltage stall prevention

 

 

 

 

 

 

 

 

 

Over-Current Stall

0:Disable

 

 

06.01

Prevention during

170

 

20 to 250%

 

 

 

Accel

 

 

 

 

 

 

 

 

 

Over-Current Stall

0:Disable

 

 

06.02

Prevention during

170

 

20 to 250%

 

 

 

Operation

 

 

 

 

 

 

 