Delta Electronics VFD-XXXE quick start Up/Down

Models: VFD-XXXE

1 36
Download 36 pages 29.99 Kb
Page 15
Image 15

 

Pr.

Explanation

Settings

Factory

NOTE

 

 

Setting

 

 

 

 

 

 

 

 

 

 

0: Disable. Operation status is not changed

 

 

 

 

 

 

even if operation command source Pr.02.01

 

 

 

 

 

 

is changed.

 

 

 

 

 

 

1: Enable. Operation status is not changed

 

 

 

 

 

 

even if operation command source Pr.02.01

 

 

 

02.05

Line Start Lockout

is changed.

1

 

 

2: Disable. Operation status will change if

 

 

 

 

 

 

 

 

 

 

 

operation command source Pr.02.01 is

 

 

 

 

 

 

changed.

 

 

 

 

 

 

3: Enable. Operation status will change if

 

 

 

 

 

 

operation command source Pr.02.01 is

 

 

 

 

 

 

changed.

 

 

 

 

 

 

0: Decelerate to 0 Hz

 

 

 

02.06

Loss of ACI Signal

1: Coast to stop and display “AErr”

1

 

 

(4-20mA)

2: Continue operation by last frequency

 

 

 

 

 

 

 

 

 

 

command

 

 

 

 

 

 

0: by UP/DOWN Key

 

 

 

02.07

Up/Down Mode

1: Based on accel/decel time

0

 

 

2: Constant speed (Pr.02.08)

 

 

 

 

 

 

 

 

 

 

 

3: Pulse input unit (Pr.02.08)

 

 

 

 

 

 

 

 

 

 

 

 

Accel/Decel Rate of

 

 

 

 

 

 

Change of

 

 

 

 

02.08

UP/DOWN

0.01~10.00 Hz

0.01

 

 

 

 

Operation with

 

 

 

 

 

 

Constant Speed

 

 

 

 

 

 

 

0: Digital keypad UP/DOWN keys or Multi-

 

 

 

 

 

 

function Inputs UP/DOWN. Last used

 

 

 

 

 

 

frequency saved.

 

 

 

 

 

Source of Second

1: 0 to +10V from AVI

0

 

 

 

 

2: 4 to 20mA from ACI or 0 to +10V from

 

 

02.09

Frequency

 

 

AVI2

 

 

 

 

 

Command

 

 

 

 

 

3: RS-485 (RJ-45)/USB communication

 

 

 

 

 

 

 

 

 

 

 

 

4: Digital keypad potentiometer

 

 

 

 

 

 

5: CANopen communication

 

 

 

 

 

 

For VFD*E*C models, the factory setting is

5

 

 

 

 

Combination of the

0: First Master Frequency Command

 

 

 

 

 

1: First Master Frequency Command+

 

 

 

 

 

First and Second

 

 

 

02.10

Second Master Frequency Command

0

 

 

Master Frequency

 

 

 

 

2: First Master Frequency Command -

 

 

 

 

 

Command

 

 

 

 

 

Second Master Frequency Command

 

 

 

 

 

 

 

 

 

02.11

Keypad Frequency

0.00 to 600.0Hz

60.00

 

 

 

 

 

Command

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Communication

0.00 to 600.0Hz

 

 

 

02.12

Frequency

 

60.00

 

 

 

 

Command

 

 

 

 

 

 

The Selections for

0: Save Keypad & Communication

 

 

 

 

 

Saving Keypad or

Frequency

 

 

 

02.13

Communication

1: Save Keypad Frequency only

0

 

 

 

 

Frequency

2: Save Communication Frequency only

 

 

 

 

 

Command

 

 

 

 

English- 15

Page 15
Image 15
Delta Electronics VFD-XXXE quick start Up/Down