Pr.

 

Explanation

Settings

Factory

NOTE

 

 

 

 

Setting

 

 

 

 

 

 

 

 

 

 

00.01

 

Rated Current

Read-only

#.#

 

 

 

 

 

 

Display of the AC

 

 

 

 

 

 

 

 

motor drive

 

 

 

 

 

 

 

 

 

0: Parameter can be read/written

 

 

 

 

 

 

 

 

1: All parameters are read only

 

 

 

 

 

 

 

 

6: Clear PLC program (NOT for VFD*E*C

 

 

 

 

 

 

 

 

models)

 

 

 

00.02

 

Parameter Reset

9: All parameters are reset to factory settings

0

 

 

 

 

 

 

 

(50Hz, 230V/400V or 220V/380V depends

 

 

 

 

 

 

 

 

on Pr.00.12)

 

 

 

 

 

 

 

 

10: All parameters are reset to factory

 

 

 

 

 

 

 

 

settings (60Hz, 220V/440V)

 

 

 

 

 

 

 

 

0: Display the frequency command value

 

 

 

 

 

 

 

 

(Fxxx)

 

 

 

 

 

 

 

 

1: Display the actual output frequency (Hxxx)

 

 

 

 

 

 

 

Start-up Display

2: Display the content of user-defined unit

 

 

 

00.03

 

(Uxxx)

0

 

 

 

Selection

 

 

 

 

 

 

3: Multifunction display, see Pr.00.04

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4: FWD/REV command

 

 

 

 

 

 

 

 

5: PLCx (PLC selections: PLC0/PLC1/PLC2)

 

 

 

 

 

 

 

 

(NOT for VFD*E*C models)

 

 

 

 

 

 

 

 

0: Display the content of user-defined unit

 

 

 

 

 

 

 

 

(Uxxx)

 

 

 

 

 

 

 

 

1: Display the counter value (c)

 

 

 

 

 

 

 

 

2: Display PLC D1043 value (C) (NOT for

 

 

 

 

 

 

 

 

VFD*E*C models)

 

 

 

 

 

 

 

 

3: Display DC-BUS voltage (u)

 

 

 

 

 

 

 

 

4: Display output voltage (E)

 

 

 

 

 

 

 

 

5: Display PID analog feedback signal value

 

 

 

 

 

 

 

 

(b) (%)

 

 

 

00.04

 

Content of Multi-

6: Output power factor angle (n)

0

 

 

 

function Display

7: Display output power (P)

 

 

 

 

 

 

 

8: Display the estimated value of torque as it

 

 

 

 

 

 

 

 

relates to current (t)

 

 

 

 

 

 

 

 

9: Display AVI (I) (V)

 

 

 

 

 

 

 

 

10: Display ACI / AVI2 (i) (mA/V)

 

 

 

 

 

 

 

 

11: Display the temperature of IGBT (h) (°C)

 

 

 

 

 

 

 

 

12: Display AVI3/ACI2 level (I.)

 

 

 

 

 

 

 

 

13: Display AVI4/ACI3 level (i.)

 

 

 

 

 

 

 

 

14: Display PG speed in RPM (G)

 

 

 

 

 

 

 

 

15: Display motor number (M)

 

 

 

00.05

 

User-Defined

0. 1 to 160.0

1.0

 

 

 

Coefficient K

 

 

 

 

 

 

 

 

 

 

 

00.06

 

Power Board

Read-only

#.##

 

 

 

 

 

 

Software Version

 

 

 

 

 

00.07

 

Control Board

Read-only

#.##

 

 

 

 

 

 

Software Version

 

 

 

 

 

00.08

 

Password Input

0 to 9999

0

 

 

 

00.09

 

Password Set

0 to 9999

0

 

 

00.10

 

Control Method

0: V/f Control

0

 

 

 

1: Vector Control

 

 

 

 

 

 

 

 

 

 

00.11Reserved

English- 11

Page 11
Image 11
Delta Electronics VFD-XXXE quick start Explanation Settings Factory, Models, Not for VFD*E*C models