Pr.

Explanation

Settings

Factory

NOTE

 

 

 

Setting

 

 

 

 

 

 

 

 

 

 

 

 

Bit11:MI12

 

 

 

 

 

 

 

0:N.O., 1:N.C.

 

 

 

 

 

 

 

P.S.:MI1 to MI3 will be invalid when it is 3-

 

 

 

 

 

 

 

wire control.

 

 

 

 

 

 

Digital Terminal

 

 

 

 

04.10

Input Debouncing

1 to 20 (*2ms)

1

 

 

 

 

 

Time

 

 

 

 

 

04.11

Min AVI Voltage

0.0 to 10.0V

0.0

 

 

 

04.12

Min AVI Frequency

0.0 to 100.0%

0.0

 

 

 

04.13

Max AVI Voltage

0.0 to 10.0V

10.0

 

 

 

04.14

Max AVI Frequency

0.0 to 100.0%

100.0

 

 

 

04.15

Min ACI Current

0.0 to 20.0mA

4.0

 

 

 

04.16

Min ACI Frequency

0.0 to 100.0%

0.0

 

 

 

04.17

Max ACI Current

0.0 to 20.0mA

20.0

 

 

04.18

Max ACI Frequency

0.0 to 100.0%

100.0

 

 

 

 

 

 

 

 

 

 

04.19

ACI/AVI2 Selection

0: ACI

0

 

 

1: AVI2

 

 

 

 

 

 

 

 

 

04.20

Min AVI2 Voltage

0.0 to 10.0V

0.0

 

 

 

 

 

 

 

 

 

04.21

Min AVI2 Frequency

0.0 to 100.0%

0.0

 

 

 

 

 

 

 

 

 

04.22

Max AVI2 Voltage

0.0 to 10.0V

10.0

 

 

 

 

 

 

 

 

 

 

04.23

Max AVI2

0.0 to 100.0%

100.0

 

 

Frequency

 

 

 

 

 

 

 

 

 

 

 

 

 

Read only.

 

 

 

 

 

 

 

Bit0=1:MI1 used by PLC

 

 

 

 

 

 

 

Bit1=1:MI2 used by PLC

 

 

 

 

 

 

The Digital Input

Bit2=1:MI3 used by PLC

 

 

 

 

 

 

Bit3=1:MI4 used by PLC

 

 

 

04.24

Used by PLC

Bit4=1:MI5 used by PLC

##

 

 

(NOT for VFD*E*C

Bit5=1:MI6 used by PLC

 

 

 

 

 

 

 

 

 

 

 

models)

Bit6=1: MI7 used by PLC

 

 

 

 

 

 

 

Bit7=1: MI8 used by PLC

 

 

 

 

 

 

 

Bit8=1: MI9 used by PLC

 

 

 

 

 

 

 

Bit9=1: MI10 used by PLC

 

 

 

 

 

 

 

Bit10=1: MI11 used by PLC

 

 

 

 

 

 

 

Bit11=1: MI12 used by PLC

 

 

 

 

 

 

The Analog Input

Read only.

 

 

 

 

 

 

Bit0=1:AVI used by PLC

 

 

 

 

 

 

Used by PLC

 

 

 

04.25

Bit1=1:ACI/AVI2 used by PLC

##

 

 

(NOT for VFD*E*C

 

 

 

 

 

Bit2=1: AI1 used by PLC

 

 

 

 

 

 

models)

 

 

 

 

 

 

Bit3=1: AI2 used by PLC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Read only.

 

 

 

 

 

 

 

Bit0: MI1 Status

 

 

 

 

 

 

 

Bit1: MI2 Status

 

 

 

 

 

 

Display the Status of

Bit2: MI3 Status

 

 

 

04.26

Multi-function Input

Bit3: MI4 Status

##

 

 

 

 

 

Terminal

Bit4: MI5 Status

 

 

 

 

 

 

 

Bit5: MI6 Status

 

 

 

 

 

 

 

Bit6: MI7 Status

 

 

 

 

 

 

 

Bit7: MI8 Status

 

 

 

English- 19