Pr.

Explanation

Settings

Factory

NOTE

 

 

 

Setting

 

 

 

 

 

 

 

 

 

 

 

 

0: Disabled

 

 

 

 

 

 

 

1: Enabled during constant speed operation.

 

 

 

 

 

 

 

After the over-torque is detected, keep

 

 

 

 

 

 

 

running until OL1 or OL occurs.

 

 

 

 

 

 

Over-Torque

2: Enabled during constant speed operation.

 

 

 

 

 

 

After the over-torque is detected, stop

 

 

 

06.03

Detection Mode

0

 

 

running.

 

 

 

 

 

(OL2)

 

 

 

 

 

 

3: Enabled during accel. After the over-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

torque is detected, keep running until OL1 or

 

 

 

 

 

 

 

OL occurs.

 

 

 

 

 

 

 

4: Enabled during accel. After the over-

 

 

 

 

 

 

 

torque is detected, stop running.

 

 

 

06.04

Over-Torque

10 to 200%

150

 

 

Detection Level

 

 

 

 

 

 

 

 

 

06.05

Over-Torque

0.1 to 60.0 sec

0.1

 

 

Detection Time

 

 

 

 

 

 

 

 

 

 

 

 

Electronic Thermal

0: Standard motor (self cooled by fan)

 

 

 

06.06

Overload Relay

1: Special motor (forced external cooling)

2

 

 

 

 

 

Selection

2: Disabled

 

 

 

06.07

Electronic Thermal

30 to 600 sec

60

 

 

Characteristic

 

 

 

 

 

 

 

 

 

 

 

 

 

0: No fault

 

 

 

 

 

 

 

1: Over current (oc)

 

 

 

 

 

 

Present Fault

2: Over voltage (ov)

 

 

 

06.08

3: IGBT Overheat (oH1)

0

 

 

Record

 

 

 

 

 

4: Power Board Overheat (oH2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5: Overload (oL)

 

 

 

 

 

 

 

6: Overload1 (oL1)

 

 

 

 

06.09

Second Most

7: Motor over load (oL2)

 

 

 

 

 

 

Recent Fault Record

8: External fault (EF)

 

 

 

 

 

 

 

9: Current exceeds 2 times rated current

 

 

 

 

 

 

 

during accel.(ocA)

 

 

 

 

 

 

 

10: Current exceeds 2 times rated current

 

 

 

 

 

 

 

during decel.(ocd)

 

 

 

 

 

 

 

11: Current exceeds 2 times rated current

 

 

 

 

 

 

 

during steady state operation (ocn)

 

 

 

 

 

 

 

12: Ground fault (GFF)

 

 

 

 

 

 

 

13: Reserved

 

 

 

 

 

 

 

14: Phase-Loss (PHL)

 

 

 

 

 

 

 

15: Reserved

 

 

 

 

 

 

 

16: Auto Acel/Decel failure (CFA)

 

 

 

 

 

 

 

17: SW/Password protection (codE)

 

 

 

06.10

Third Most Recent

18: Power Board CPU WRITE failure (cF1.0)

 

 

 

19: Power Board CPU READ failure (cF2.0)

 

 

 

Fault Record

 

 

 

 

 

 

20: CC, OC Hardware protection failure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(HPF1)

 

 

 

 

 

 

 

21: OV Hardware protection failure (HPF2)

 

 

 

 

 

 

 

22: GFF Hardware protection failure (HPF3)

 

 

 

 

 

 

 

23: OC Hardware protection failure (HPF4)

 

 

 

 

 

 

 

24: U-phase error (cF3.0)

 

 

 

 

 

 

 

25: V-phase error (cF3.1)

 

 

 

 

 

 

 

26: W-phase error (cF3.2)

 

 

 

 

 

 

 

 

 

 

 

English- 21