Pr.

Explanation

Settings

Factory Setting

NOTE

 

 

 

27: DCBUS error (cF3.3)

 

 

 

 

 

28: IGBT Overheat (cF3.4)

 

 

 

 

 

29: Power Board Overheat (cF3.5)

 

 

 

 

 

30: Control Board CPU WRITE failure

 

 

 

06.11

Fourth Most Recent

(cF1.1)

 

 

 

 

Fault Record

31: Control Board CPU WRITE failure

 

 

 

 

 

(cF2.1)

 

 

 

 

 

32: ACI signal error (AErr)

 

 

 

 

 

33: Reserved

 

 

 

06.12

Fifth Most Recent

34: Motor PTC overheat protection (PtC1)

 

 

 

Fault Record

35-39: Reserved

 

 

 

 

 

 

 

 

 

40: Communication time-out error of control

 

 

 

 

 

board and power board (CP10)

 

 

 

 

 

Group 7 Motor Parameters

 

 

 

07.00

Motor Rated Current

30 %FLA to 120% FLA

FLA

 

 

 

(Motor 0)

 

 

 

 

07.01

Motor No-Load

0%FLA to 99% FLA

0.4*FLA

 

 

Current (Motor 0)

 

 

 

 

 

 

 

 

Torque

 

 

 

 

07.02

Compensation

0.0 to 10.0

0.0

 

 

 

(Motor 0)

 

 

 

 

 

Slip Compensation

0.00 to 10.00

0.00

 

 

07.03

(Used without PG)

 

 

 

 

 

(Motor 0)

 

 

 

 

 

Motor Parameters

0: Disable

 

 

 

07.04

1: Auto tuning R1

0

 

 

Auto Tuning

 

 

 

2: Auto tuning R1 + no-load test

 

 

 

 

 

 

 

 

 

Motor Line-to-line

0~65535 mΩ

 

 

 

07.05

Resistance R1

0

 

 

 

(Motor 0)

 

 

 

 

07.06

Motor Rated Slip

0.00 to 20.00 Hz

3.00

 

 

(Motor 0)

 

 

 

 

 

 

 

07.07

Slip Compensation

0 to 250%

200

 

 

Limit

 

 

 

 

 

 

 

 

Torque

 

 

 

 

07.08

Compensation Time

0.01 ~10.00 Sec

0.30

 

 

 

Constant

 

 

 

 

07.09

Slip Compensation

0.05 ~10.00 sec

0.20

 

 

Time Constant

 

 

 

 

 

 

 

 

Accumulative Motor

 

 

 

 

07.10

Operation Time

0 to 1439 Min.

0

 

 

 

(Min.)

 

 

 

 

 

Accumulative Motor

 

 

 

 

07.11

Operation Time

0 to 65535 Day

0

 

 

 

(Day)

 

 

 

 

07.12

Motor PTC

0: Disable

0

 

 

Overheat Protection

1: Enable

 

 

 

 

 

 

 

Input Debouncing

 

 

 

 

07.13

Time of the PTC

0~9999(*2ms)

100

 

 

 

Protection

 

 

 

 

 

Motor PTC

 

 

 

 

07.14

Overheat Protection

0.1~10.0V

2.4

 

 

 

Level

 

 

 

English- 22

Page 22
Image 22