21.Check for gas leaks.
22.Replace main furnace door.
Step 4 — Cleaning Heat Exchangers
The following items should be performed by a qualified service technician.
PRIMARY HEAT EXCHANGERS
If the heat exchangers get an accumulation of light dirt or dust on the inside, they may be cleaned by the following procedure:
NOTE: If heat exchangers get a heavy accumulation of soot and carbon, both the primary and secondary heat exchangers should be replaced rather than trying to clean them thoroughly due to their intricate design. A
1.Turn off gas and electrical supplies to furnace.
2.Remove main furnace door.
!CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in furnace component damage.
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and hazardous operation.
3.Disconnect wires or connectors to flame rollout switch, gas valve, igniter, and flame sensor.
4.Disconnect
5.Remove the pressure switch tube from intake housing.
6.Remove screws attaching intake housing to burner box, and rotate intake housing away from burner box for removal.
7.Using backup wrench, disconnect gas supply pipe from fur- nace gas control valve.
8.Disconnect pressure tubing from gas valve.
PRIMARY HX
INLET OPENINGS
A96305
Fig. 8 - Cleaning Inlet Openings of Primary
Heat Exchangers
9.Remove 2 screws attaching top filler panel and rotate up- wards to gain access to screws attaching burner box to cell panel.
10.Remove screws attaching burner box to cell panel. (See Fig. 6).
NOTE: Burner box, cover, manifold, gas valve, and burner assembly should be removed as one assembly.
11.Clean heat exchanger openings with a vacuum and a soft brush. (See Fig. 8.)
NOTE: After cleaning, inspect the heat exchanger to ensure they are free of all foreign objects that may restrict flow of combustion products.
12.Reverse items 4 through 10 for reassembly.
!CAUTION
UNIT MAY NOT OPERATE
Failure to attach this ground wire to an adequate casing ground may cause the furnace control to lock out.
The ground wire from the gas valve MUST be attached to the burner box attachment screw.
NOTE: Be sure burner box gasket is installed between burner box and cell panel. (See Fig. 6.) If gasket is damaged, replace it.
NOTE: Inspect
13.Refer to furnace wiring diagram and reconnect wires to flame rollout switch, gas valve, igniter, and flame sensor.
14.Reconnect pressure switch tubes to gas valve and intake housing. Refer to tube routing label on main furnace door or Fig. 10 for proper tube location. Be sure tubes are not kinked.
15.Turn on gas and electrical supplies to furnace.
16.Check furnace operation through 2 complete heat operating cycles. Look through sight glass in burner enclosure to check burners. Burner flames should be clear blue, almost transparent. (See Fig. 11.)
!WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this safety warning could result in personal injury, death, or property damage.
Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections.
17.Check for gas leaks.
18.Replace main furnace door.
SECONDARY HEAT EXCHANGERS
NOTE: The condensing side (inside) of the secondary heat exchangers CANNOT be serviced or inspected. A small number of bottom outlet openings can be inspected by removing the
58MEC
7