A92185
Fig. 9 - Turn Off Electrical Supply
A05099
Fig. 10 - Remove Furnace Door
A04150
Fig. 11 - Control Switch to OFF
A04151
Fig. 12 - Control Switch to ON
A05100
Fig. 13 - Furnace Door Replaced
A92359
Fig. 14 - Turn On Electrical Supply
i
A06189
Fig. 15 - Open Valve
7.Replace main furnace door. (See Fig. 13.)
8.Turn ON the electrical supply to the furnace and wait 1 minute. (See Fig. 14.)
9.Open the external manual gas valve. (See Fig. 15.)
10.Set the room thermostat to a temperature slightly above the
room temperature. This will automatically signal the furnace to start.
11.When the furnace receives the start signal, the inducer is started. When the pressure switch senses that there is suf-
ficient combustion air, the hot surface igniter is energized. After the hot surface igniter is heated for 17 seconds, the gas valve permits gas to flow to the main burners. After ignition and a time delay of about 30 sec, the furnace blower will start.
Variable-capacity furnaces start at medium speed until the
control makes the necessary adjustments to operate the
blower at either the low-, medium-, or high-heat speed.
NOTE: If the burners fail to ignite after 4 attempts, the furnace control system will lock out. If lockout occurs, main burners fail to light, or blower does not come on, shut down the furnace and call your dealer for service.