PFG Series 7 Gas-fired Water Boiler — Boiler Manual

Draft hood installation

Secure the draft hood to the outlet at the top of the boiler with sheet metal screws. The bottom of the draft hood or “skirt” must have the clearance dimension above the jacket top panel as indicated on the draft hood.

Do not alter draft hood. CSA design certification becomes void. If draft hood is altered, severe personal injury or death will occur, resulting from flue gas spillage or carbon monoxide emissions.

Spill switch installation (PFG-5 ONLY)

Fasten spill switch to draft hood as shown on page 21. Connect wires as shown on wiring diagram label located inside boiler door.

Damper installation

If damper will be installed, see Control Supplement for information.

Breeching erection

(Also refer to chimney or vent requirements, Page 4)

Connect from draft hood or damper outlet to chimney or vent with same size as breeching. Where possible, vertical venting to the outside from the draft hood or damper outlet will offer best performance. Where hori- zontal breeching is used, slope upward at least ¼ inch per lineal foot toward the chimney or vent and support with hangers to prevent sagging.

A minimum vertical height of 3 feet of breeching before any elbow or horizontal breeching is recommended to reduce chances of flue gas spillage at the draft hood. Long horizontal breechings, excessive numbers of elbows or tees, or other obstructions that restrict the flow of combustion gas should be avoided.

Breeching must not be connected to any portion of a mechanical draft system that can operate under posi- tive pressure.

Wiring

For your safety, turn off the electrical power supply at the service entrance panel before making any electrical connections to avoid possible electrical shock hazard.

All wiring must be installed in accordance with re- quirements of the National Electrical Code and any additional national, state or local code requirements having jurisdiction. All wiring must be N.E.C. Class 1. The boiler must be electrically grounded in accordance with the National Electrical Code, ANSI/NFPA No. 70- latest edition.

In Canada, all wiring must be done in accordance with the CSA C22.1 Canadian Electrical Code Part 1.

Iforiginalrolloutthermalfuseelementwireassuppliedwith PFG-5 boiler must be replaced, type 200°C wire or equivalent must be used. If other original wire as sup- plied with any PFG boiler must be replaced, type 105°C wire or equivalent must be used.

The boiler is shipped with control components com- pletely wired except for spill switch and damper (if provided).

A separate electrical circuit should be used for the boiler with a fused disconnect switch (15 amp. recom- mended).

Refer to wiring diagram label affixed to the inside of the jacket door. Bring electrical supply through proper opening in the jacket left end panel and into the electri- cal junction box. Wire electrical supply, circulator and thermostat as shown on the wiring diagram.

For boilers equipped with control systems other than constant burner pilot, refer to separate instructions for application data.

Install room thermostat

Install room thermostat on an inside wall. Never install where it will be influenced by drafts, hot or cold water pipes, lighting fixtures, television, rays of the sun or near a fireplace.

Heat anticipator in thermostat must be set to match the power requirements of the primary control to which it is connected. Refer to wiring diagram on jacket door for recommended heat anticipator setting with standard equipment. Wire the thermostat as shown.

12

Part Number 550-110-641/0605

Image 12
Contents PFGGas-fired water boiler Contents Section I Installation Installation clearancesCombustion air and ventilation openings Select the boiler locationWhen removing boiler from common venting system Chimney or vent requirementsResidential garage installation Boiler foundationPlacing the boiler Hydrostatic pressure testBoiler piping connections to the heating Multiple zoning Filling the systemBypass piping Using with refrigeration system External heat exchangersFreeze protection Size and install gas piping Follow good piping practicesGas supply piping Draft hood installation Spill switch installation PFG-5 onlyDamper installation WiringWiring multiple zones Canadian installations Chain & s-hookCheck-out procedure Installation instructions have been followedInstaller Company Address Phone Installer’s signature Check off steps as completedSection II Service Handling ceramic fiber and fiberglass materialsBeginning of each heating season Daily during heating seasonPeriodically during heating season Monthly during heating seasonTo inspect base insulation To place in operationCheck pilot burner flame Check main burner flamesTo clean boiler heating surfaces To clean main burnersAnnual shut-down procedure Inspect venting systemCommon problems and possible solutions Section III Replacement Parts Description Part NumberPFG Series 7 Gas-fired Water Boiler Boiler Manual Section IV Ratings and dimensions DOEPFG Series 7 Gas-fired Water Boiler Boiler Manual PFG Series 7 Gas-fired Water Boiler Boiler Manual