Trane RT-PRC007-EN manual Exhaust Air Options, Application Recommendations Power Exhaust Fan

Page 10

Application Considerations

Exhaust Air Options

When is it necessary to provide building exhaust?

Whenever an outdoor air economizer is used, a building generally requires an exhaust system.The purpose of the exhaust system is to exhaust the proper amount of air to prevent over or under- pressurization of the building.

A building may have all or part of its exhaust system in the rooftop unit. Often, a building provides exhaust external to the air conditioning equipment.This external exhaust must be considered when selecting the rooftop exhaust system.

Voyager Commercial rooftop units offer two types of exhaust systems:

1

Power exhaust fan.

2

Barometric relief dampers.

Application Recommendations

Power Exhaust Fan

The exhaust fan option is a dual, nonmodulating exhaust fan with approximately half the air-moving capabilities of the supply fan system.The experience ofTheTrane Company is that a non-modulating exhaust fan selected for 40 to 50 percent of nominal supply cfm can be applied successfully.

The power exhaust fan generally should not be selected for more than 40 to 50 percent of design supply airflow. Since it is an on/off nonmodulating fan, it does not vary exhaust cfm with the amount of outside air entering the building. Therefore, if selected for more than 40 to 50 percent of supply airflow, the building may become underpressurized when economizer operation is allowing lesser

amounts of outdoor air into the building. If, however, building pressure is not of a critical nature, the non-modulating exhaust fan may be sized for more than 50 percent of design supply airflow. ConsultTable PD-16 for specific exhaust fan capabilities with Voyager Commercial units.

Barometric Relief Dampers

Barometric relief dampers consist of gravity dampers which open with increased building pressure. As the building pressure increases, the pressure in the unit return section also increases, opening the dampers and relieving air. Barometric relief may be used to provide relief for single story buildings with no return ductwork and exhaust requirements less than 25 percent.

Altitude Corrections

The rooftop performance tables and curves of this catalog are based on standard air (.075 lbs/ft). If the rooftop airflow requirements are at other than standard conditions (sea level), an air density correction is needed to project accurate unit performance.

Figure PD-1 shows the air density ratio at various temperatures and elevations. Trane rooftops are designed to operate between 40 and 90 degrees Fahrenheit leaving air temperature.

The procedure to use when selecting a supply or exhaust fan on a rooftop for elevations and temperatures other than standard is as follows:

1

First, determine the air density ratio using Figure PD-1.

2

Divide the static pressure at the nonstandard condition by the air density ratio to obtain the corrected static pressure.

3

Use the actual cfm and the corrected static pressure to determine the fan rpm and bhp from the rooftop performance tables or curves.

4

The fan rpm is correct as selected.

5

Bhp must be multiplied by the air density ratio to obtain the actual operating bhp.

In order to better illustrate this procedure, the following example is used:

Consider a 30-ton rooftop unit that is to deliver 11,000 actual cfm at 1.50 inches total static pressure (tsp), 55 F leaving air temperature, at an elevation of 5,000 ft.

1

From Figure PD-1, the air density ratio is 0.86.

2

Tsp=1.50 inches/0.86=1.74 inches tsp.

3

From the performance tables: a 30-ton rooftop will deliver 11,000 cfm at 1.74 inches tsp at 668 rpm and 6.93 bhp.

4

The rpm is correct as selected — 668 rpm.

5

Bhp = 6.93 x 0.86 = 5.96 .

Compressor MBh, SHR, and kw should be calculated at standard and then converted to actual using the correction factors inTable PD-2. Apply these factors to the capacities selected at standard cfm so as to correct for the reduced mass flow rate across the condenser.

10

RT-PRC007-EN

Image 10
Contents Packaged Rooftop Air Conditioners Introduction American Standard IncContents Standard Features Features and BenefitsOptional Features Simple Design with 70% Fewer Parts Proven DesignThroughTesting and ResearchTrane 3-DScroll Compressor LowTorque VariationMicro Controls Features BenefitsQuality and Reliability MicroSingle Point Power RigorousTestingEase of Installation FC Fans with Inlet GuideVanesEasy to Service ValueVariTrac Barometric Relief Dampers Application Recommendations Power Exhaust FanExhaust Air Options Altitude CorrectionsClearance Requirements Acoustical ConsiderationsDuct Design Selection Procedure Supply Air FanNatural Gas Heating System Air Delivery ProcedureElectric Heating System Unit Electrical RequirementsModel Number Description General Data Table GD-1 General Data 27 1/2 30 TonsTable GD-2- General Data 35-40Ton Table GD-3- General Data 50Ton Table PD-1- Enthalpy of Saturated AIR Performance Adjustment FactorsTable PD-3 Gas Heating Capacity Altitude Correction Factors Table PD-4 27 1/2 Ton Gross Cooling Capacities MBh Performance DataTable PD-5- 30Ton Gross Cooling Capacities Mbh Table PD-6 35Ton Gross Cooling Capacities Mbh Table PD-7 40Ton Gross Cooling Capacities MbhTable PD-8 50Ton Gross Cooling Capacities MBh Table PD-10 Available Electric Heat KW Ranges Table PD-9 Electric Heat AirTemperature RiseTable PD-11 Natural Gas Heating Capacities Table PD-12 Supply Fan Performance 27½ 35Ton Static Pressure in. wg1Table PD-13 Supply Fan Performance 40 and 50Ton Heating System Filters2 Nominal Table PD-14 Component Static Pressure Drops in.W.G.1Gas Heat Electric Heat3 ID Coil 20 HP Table PD-15 Supply Air Fan Drive SelectionsNominal Drive Table PD-16- Power Exhaust Fan Performance Controls VAV Units OnlyCV Units Only Auto Changeover Unoccupied ZoneTemperature Control Cooling and HeatingSupply AirTempering ConventionalThermostat InterfaceCoil Freeze Protection Frostat Occupied/Unoccupied SwitchingFan Failure Switch Night Setback SensorsElectrical Data Electrical Service SizingSet 2. Rooftop units with Electric Heat Table ED-2 27½-50Ton Electrical Service Sizing Data1 Dimensional Data Figure DD-1 27 1/2 35Tons TC,TE,YC Low HeatDimensional Data Figure DD-3 40-50Tons TC,TE,YC Low & High Heat Dimensional Field Installed SensorsConstant CV and VAV Integrated Comfort System SensorsTableW-3 ComponentWeights WeightsTableW-2 Point Loading AverageWeight1 TableW-4 Minimum Operating Clearances for Unit InstallationMechanical Specifications Unit Options Accessories LP Conversion Kit 20-60Ton Literature Order Number File Number PL-RT-TC/TE/YC-27½ 50-TONS-PRC0007-EN-10-2001

RT-PRC007-EN specifications

The Trane RT-PRC007-EN is a part of Trane’s highly regarded line of air-cooled chillers, designed to provide exceptional performance and efficiency for a variety of commercial applications. This model is known for its robust engineering and cutting-edge technologies, making it a favored choice among facility managers and HVAC professionals.

One of the key features of the RT-PRC007-EN is its energy efficiency. Its advanced compressor design, alongside innovative heat exchanger technology, allows it to achieve significant energy savings, meeting or exceeding standards set by the Department of Energy. This efficiency not only results in lower operational costs but also contributes to a smaller carbon footprint, making it an environmentally friendly choice.

The chiller is equipped with variable speed compressors which adjust their output in relation to the cooling demand. This feature ensures optimal performance at all times, reducing energy consumption during partial load operations. Additionally, the RT-PRC007-EN incorporates Trane's unique Adaptive Control technology. This intelligent control system continuously monitors system parameters and environmental conditions, optimizing performance in real-time to ensure reliable operation.

Another standout characteristic of the RT-PRC007-EN is its quiet operation. The inclusion of sound-dampening technology and strategically placed acoustic insulation allows this chiller to operate with minimal noise, making it suitable for installations in noise-sensitive environments like hospitals or schools.

Durability is another hallmark of the RT-PRC007-EN. Built with high-quality materials, it is designed to withstand harsh operating conditions. Its corrosion-resistant components ensure longevity and reduce the need for extensive maintenance, making it a reliable choice for operators.

Lastly, the RT-PRC007-EN comes with a variety of customization options, including different refrigerant types, control systems, and capacity configurations. This flexibility allows it to adapt to the specific needs of different applications and building designs.

In summary, the Trane RT-PRC007-EN represents a fusion of efficiency, reliability, and advanced technology, making it an excellent option for those seeking a cutting-edge air-cooled chiller for their commercial HVAC needs.