Trane RT-PRC007-EN manual Unit Options

Page 42

Mechanical Specifications

make all heating, cooling and/or ventilating decisions in response to electronic signals from sensors measuring indoor and outdoor temperatures.The control algorithm maintains accurate temperature control, minimizes drift from set point and provides better building comfort. A centralized microprocessor shall provide anti-short cycle timing and time delay between compressors to provide a higher level of machine protection.

Control Options

Inlet Guide Vanes shall be installed on each fan inlet to regulate capacity and limit horsepower at lower system requirements.When in any position other than full open they shall pre-spin intake air in the same direction as fan rotation.The inlet guide vanes shall close when supply fan is off, except in night setback.

The inlet guide vane actuator motor shall be driven by a modulating dc signal from the unit microprocessor. A pressure transducer shall measure duct static pressure and modulate the inlet guide vanes to maintain the required supply air static pressure within a predetermined range.

Variable Frequency Drives (VFDs)

VFDs shall be factory installed and tested to provide supply fan motor speed modulation.The VFD shall receive a 2- 10 VDC signal from the unit microprocessor based upon supply static pressure and shall cause the drive to accelerate or decelerate as required to maintain the supply static pressure setpoint. When subjected to high ambient return conditions the VFD shall reduce its output frequency to maintain operation. Bypass control to provide full nominal air flow in the event of drive failure shall be optional.

Ventilation Override

Ventilation Override shall allow a binary input from the fire/life safety panel to cause the unit to override standard operation and assume one of two factory preset ventilation sequences, exhaust or pressurization.The two

sequences shall be selectable based open a binary select input.

Outside Air

Manual Outside Air

A manually controllable outside air damper shall be adjustable for up to 25 percent outside air. Manual damper is set at desired position at unit start up.

Economizer

Economizer shall be factory installed.The assembly includes: fully modulating 0- 100 percent motor and dampers, minimum position setting, preset linkage, wiring harness, and fixed dry bulb control. Solid state enthalpy and differential enthalpy control shall be a factory or field installed option.

Exhaust Air

Barometric Relief

The barometric relief damper shall be optional with the economizer. Option shall provide a pressure operated damper for the purpose of space pressure equalization and be gravity closing to prohibit entrance of outside air during the equipment “off” cycle.

Power Exhaust Fan

Power exhaust shall be available on all units and shall be factory installed. It shall assist the barometric relief damper in maintaining building pressurization.

Unit Options

ServiceValves

Service valves shall be provided factory installed and include suction, liquid, and discharge 3-way shutoff valves.

Through-The-Base Electrical Provision

An electrical service entrance shall be provided which allows access to route all high and low voltage electrical wiring inside the curb, through the bottom of the outdoor section of the unit and into the control box area.

Non-Fused Disconnect Switch

A factory installed non-fused disconnect switch with external handle shall be provided and shall satisfy NEC requirements for a service disconnect. The non-fused disconnect shall be mounted inside the unit control box.

GFI Convenience Outlet (Factory Powered)

A 15A, 115V Ground Fault Interrupter convenience outlet shall be factory installed. It shall be wired and powered from a factory mounted transformer. Unit mounted non-fused disconnect with external handle shall be furnished with factory powered outlet.

GFI Convenience Outlet (Field Powered)

A 15A, 115V Ground Fault Interrupter convenience outlet shall be factory installed and shall be powered by customer provided 115V circuit.

Hinged Service Access

Filter access panel and supply fan access panel shall be hinged for ease of unit service.

Condenser Coil Guards

Factory installed condenser vinyl coated wire mesh coil guards shall be available to provide full area protection against debris and vandalism.

LonTalk Communication Interface

Available either field or factory-installed for constant volume units. When installed on a constant volume unit, this LonTalk board will allow the unit to communicate as aTrane Comm5 device or directly with generic LonTalk Network Building Automation System Controls.

Stainless Steel Drain Pans

Sloped stainless steel evaporator coil drain pans are durable, long-lasting and highly corrosion resistant.

Black Epoxy Coated Condenser Coil

The coil provides corrosion protection to condenser coils for seacoast application. The protection is a factory applied thermoset vinyl coating, bonded to normal aluminum fin stock.The uniform thickness of the bonded vinyl layer exhibits excellent corrosion protection in salt spray tests performed in accordance with ASTM B117.

42

RT-PRC007-EN

Image 42
Contents Packaged Rooftop Air Conditioners Introduction American Standard IncContents Features and Benefits Standard FeaturesOptional Features Simple Design with 70% Fewer Parts Proven DesignThroughTesting and ResearchTrane 3-DScroll Compressor LowTorque VariationMicro Controls Features BenefitsQuality and Reliability MicroSingle Point Power RigorousTestingEase of Installation FC Fans with Inlet GuideVanesEasy to Service ValueVariTrac Barometric Relief Dampers Application Recommendations Power Exhaust FanExhaust Air Options Altitude CorrectionsAcoustical Considerations Clearance RequirementsDuct Design Selection Procedure Supply Air FanNatural Gas Heating System Air Delivery ProcedureElectric Heating System Unit Electrical RequirementsModel Number Description General Data Table GD-1 General Data 27 1/2 30 TonsTable GD-2- General Data 35-40Ton Table GD-3- General Data 50Ton Performance Adjustment Factors Table PD-1- Enthalpy of Saturated AIRTable PD-3 Gas Heating Capacity Altitude Correction Factors Performance Data Table PD-4 27 1/2 Ton Gross Cooling Capacities MBhTable PD-5- 30Ton Gross Cooling Capacities Mbh Table PD-6 35Ton Gross Cooling Capacities Mbh Table PD-7 40Ton Gross Cooling Capacities MbhTable PD-8 50Ton Gross Cooling Capacities MBh Table PD-9 Electric Heat AirTemperature Rise Table PD-10 Available Electric Heat KW RangesTable PD-11 Natural Gas Heating Capacities Table PD-12 Supply Fan Performance 27½ 35Ton Static Pressure in. wg1Table PD-13 Supply Fan Performance 40 and 50Ton Table PD-14 Component Static Pressure Drops in.W.G.1 Heating System Filters2 NominalGas Heat Electric Heat3 ID Coil Table PD-15 Supply Air Fan Drive Selections 20 HPNominal Drive Table PD-16- Power Exhaust Fan Performance Controls VAV Units OnlyCV Units Only Auto Changeover Unoccupied ZoneTemperature Control Cooling and HeatingSupply AirTempering ConventionalThermostat InterfaceCoil Freeze Protection Frostat Occupied/Unoccupied SwitchingFan Failure Switch Night Setback SensorsElectrical Service Sizing Electrical DataSet 2. Rooftop units with Electric Heat Table ED-2 27½-50Ton Electrical Service Sizing Data1 Dimensional Data Figure DD-1 27 1/2 35Tons TC,TE,YC Low HeatDimensional Data Figure DD-3 40-50Tons TC,TE,YC Low & High Heat Dimensional Field Installed SensorsConstant CV and VAV Integrated Comfort System SensorsTableW-3 ComponentWeights WeightsTableW-2 Point Loading AverageWeight1 TableW-4 Minimum Operating Clearances for Unit InstallationMechanical Specifications Unit Options Accessories LP Conversion Kit 20-60Ton Literature Order Number File Number PL-RT-TC/TE/YC-27½ 50-TONS-PRC0007-EN-10-2001

RT-PRC007-EN specifications

The Trane RT-PRC007-EN is a part of Trane’s highly regarded line of air-cooled chillers, designed to provide exceptional performance and efficiency for a variety of commercial applications. This model is known for its robust engineering and cutting-edge technologies, making it a favored choice among facility managers and HVAC professionals.

One of the key features of the RT-PRC007-EN is its energy efficiency. Its advanced compressor design, alongside innovative heat exchanger technology, allows it to achieve significant energy savings, meeting or exceeding standards set by the Department of Energy. This efficiency not only results in lower operational costs but also contributes to a smaller carbon footprint, making it an environmentally friendly choice.

The chiller is equipped with variable speed compressors which adjust their output in relation to the cooling demand. This feature ensures optimal performance at all times, reducing energy consumption during partial load operations. Additionally, the RT-PRC007-EN incorporates Trane's unique Adaptive Control technology. This intelligent control system continuously monitors system parameters and environmental conditions, optimizing performance in real-time to ensure reliable operation.

Another standout characteristic of the RT-PRC007-EN is its quiet operation. The inclusion of sound-dampening technology and strategically placed acoustic insulation allows this chiller to operate with minimal noise, making it suitable for installations in noise-sensitive environments like hospitals or schools.

Durability is another hallmark of the RT-PRC007-EN. Built with high-quality materials, it is designed to withstand harsh operating conditions. Its corrosion-resistant components ensure longevity and reduce the need for extensive maintenance, making it a reliable choice for operators.

Lastly, the RT-PRC007-EN comes with a variety of customization options, including different refrigerant types, control systems, and capacity configurations. This flexibility allows it to adapt to the specific needs of different applications and building designs.

In summary, the Trane RT-PRC007-EN represents a fusion of efficiency, reliability, and advanced technology, making it an excellent option for those seeking a cutting-edge air-cooled chiller for their commercial HVAC needs.