Bosch Appliances DS7445I, DS7447E, DS7400XI Installation Considerations, Programming the DS7400Xi

Page 76

11.2Installation Considerations

Failure to install and program the control in accordance with the requirements in this section voids the listing mark of Underwriters Laboratories, Inc.

The maximum standby battery capacity is 35 Ah @ 12 VDC.

The total nominal standby current must not exceed 1.5 A nor 2.5 A when in alarm.

The control must be mounted indoors and within the protected area.

Enclosure tamper switches (if used) must be connected to a 24- hour zone.

Grounding must be in accordance with article 250 of the NEC (NFPA 70).

At least one UL Listed keypad with zone display must be connected.

Zones must be connected to UL Listed, compatible devices.

50 Hz. AC input cannot be used in UL Listed Requirements.

The ground wire provided with the enclosure must be connected to the “Earth GND” connection on the control and the enclosure tab.

The keypad panic alarm output must follow the corresponding zone function’s programming (e.g. fire = pulsing [or steady if not a combination], burglary = steady). In all cases, the special emergency keys must be silent.

The ground start feature shall not be programmed.

11.3Programming the DS7400Xi

When used in UL Listed Requirements, the control must conform to certain programming requirements. The following is a list of the required program entries and required accessories for specific UL Listed Requirements.

11.3.1Household Fire Alarm Using Digital Alarm Communicator Transmitter With Local Bell

The control must be installed in accordance with NFPA 72.

Required Accessories:

At least one Detection Systems, Inc. Model DS250 Series smoke detector with an MB Series base, DS280 Series, MX280 Series, or another Listed compatible smoke detector.

At least one DS7480 Bell Supervision Module.

One Wheelock 46T-G10-12 bell or 34T-12 horn (will provide 85db for UL985 and NFPA 72 requirements; other Listed compatible devices with a voltage range of 10.2 to 14.0 V may be used) is required and must be installed inside the protected area.

The standard control enclosure can be used.

At least one DS7447/DS7447E or DS7445/DS7445i Keypad must be used.

Four-wire detectors must be used with Listed power supervision devices. A compatible Listed 4-wire detector is the Detection Systems, Inc. DS250 in an MB4W base. A compatible Listed EOL relay is the Detection Systems, Inc. EOL200.

All zones must be used with the EOL resistor (P/N 25899), provided.

1. Report Programming:

Fire Zone Report must be programmed.

Low Battery Report (Program Address 3336) must be programmed.

AC Failure Report (Program Address 3338) must be programmed.

2. Timer Programming:

• Bell Cutoff Times (Program Addresses 4032 and 4033) must

be programmed for not less than 4 minutes.

3. Zone Function Programming:

For household fire installations only, the output signal may be pulsed or steady. For a combination system, see the selection below on alarm output programming.

4. Alarm Output Programming:

Program Address 2734 must be programmed as: Data Digit 1= 6, Data Digit 2= 3.

5. General Control Programming:

Program Address 2732 must be programmed as: Data Digit 1= 0, Data Digit 2= 0.

11.3.2Grade A Household Burglary Alarm Using Digital Alarm Communicator Transmitter With Local Bell

The control must be installed in accordance with UL Standard UL1641.

Required Accessories:

At least one Wheelock 46T-G10-12 bell or 34T-12 horn (other Listed compatible devices with a voltage range of 10.2 to 14.0 V may be used) is required for this application.

The standard DS7400 enclosure can be used.

1. Report Programming:

Burglar Zone Reports must be programmed for those zones used.

Low Battery Report (Program Address 3336) must be programmed.

AC Failure Report (Program Address 3338) must be programmed.

2. Timer Programming:

Bell Cutoff Times (Program Addresses 4032 and 4033) must be programmed for not less than 4 minutes.

Entry Delay Timer (Program Addresses 4028 and 4029) must be programmed for not longer than 60 seconds.

Exit Delay Timer (Program Address 4030) must be programmed for not longer than 45 seconds.

3. General Control Programming:

Program Address 0000, Data Digit 2 must be programmed for NO Swinger Shunts (enter 0, 1, or 2).

Program Address 2732 must be programmed as: Data Digit 1= 0, Data Digit 2= 0.

4. Alarm Output Programming:

Program Address 2734 must be programmed as: Data Digit 1= 6, Data Digit 2= 3.

Program Address 2737 must be programmed as: Data Digit 1= 8.

In a system that includes both fire alarm and burglar alarm devices, the system must produce distinct sounds for fire and burglar alarm conditions either by using different indicating appliances or by using distinct cadences for the same appliance.

Page 76 P/N: F01U035325-01

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

Image 76
Contents Keypad Quick Reference Guide Access ControlNumber of hours from Table of Contents Installation Guide for UL Listed Systems 12.013.0 14.0Specifications 15 Max. Load Currents Backup Battery Calculation Standby Current LoadOptions DS7412 RS232 Serial Interface moduleCurrent Draw = 500 μA, Standby 560 μA, Alarm Install the Enclosure Enclosure InstallationInstall the Control/Communicator Wiring Control Terminal Wiring Loop + Aux. Power Input Or PO2Power Indication LED Loop + ZoneBetween battery wires and all Hardware Layout ExampleS7430 DS7400XiSystem Worksheet Personal Identification Number Information System WorksheetPIN Information User Pin # Auth Parti Name Level Tions 002 1001 James LPIN Information Zone Location and Notes Type Zone/Output Partition & LocationSee section TypeSystem Worksheet System Worksheet Zone Location and Notes Worksheet Glossary General Control ProgrammingZone Function Programming General Authority by PartitionZone Programming Entry/Exit Delay Cancel Zone FunctionsZone Output Programming Partition Control ProgrammingGround Fault Detect Programming Commercial Fire Mode ProgrammingCustom Arming Programming Keypad Assignment ProgrammingOpen/Close Report Control Programming Report ProgrammingPhone Number General Control Programming Failure Report DelayPhone Answering Programming For Installations in New Zealand Two-wire ConnectionFCC Compliance Notice FCC Phone Connection Notice To UsersEmergency Procedures Fire Reset/Fire TroubleEmergency Keypad Alarms Operating GuideFire Safety If Installed in Family ResidencesInstallation Considerations Having and Practicing an Escape PlanProgramming PINs Personal Identification NumbersGeneral Information To set the expiration date for an existing Temporary PINSingle Partition Mode To arm all the Partitions to which you have accessTo arm only some of the Partitions to which you have access Master KeypadKeypad Error Displays System FaultsEvent History To readback the Event History BufferTesting Your System Battery TestsZone System Walk Test Communicator TestHow to Program the Control Panel Understanding the Programming Charts To select Disabled, enter the data digit as aTo select Entry/Exit Delay #2, enter the data digit as a Enter one of these numbers for the appropriate data digitProgramming General Control Programing Program AddressAllow Maximum Security Arming Siren on Comm. Fail for Silent ZoneSteady alarm response Programming the Zone FunctionsZone Function Programming Program Addresses DetailsZone Programming Program Addresses Assigning a Zone Function to the ZoneThis step, a Zone function is assigned to the Zone Assigning a Zone Type to the Zone Zone Programming Zone Type Program AddressesZone Partition Assignment Program Addresses Assigning a Partition to the ZoneBelongs to Partition Zone Bypass Programming Program Addresses Swinger Shunt Bypasses see programming for Program AddressEnter the Data Digit as a Select Options Output Programming Program Addresses 2734, 2735 Programmable OutputData Digit Output Partition Assignment Program AddressesData Digit Partition Control Programming Program AddressQuick Arm Control Programming Program Address Keypad Assignment Programming Program Addresses Keypad Partition Assignment Program AddressesSee Glossary .6 for further details Program AddressEmergency Key Programming Program Addresses Custom Arming Programming Program AddressesSee Glossary .7 for further details Data Digit Must beEnter the Data Digit as a Select Options Custom Arming Programming Program AddressesSee Glossary sections 6.9 and 6.10 for further details Commercial Fire Mode Programming Program Address See Glossary .11 for further detailsOpen/Close Report Control Programming Program Address Report Control Programming Program AddressSee Glossary .12 for further details SeeAC Fail Report Delay Programming Program Address Timer Programming Program Addresses 4028-4030See Glossary .13 for further details Arming Warning Programming Program Addresses General Authority Programming Program AddressSee Glossary .1 for further details Select Option Report Programming Program Addresses Report Programming Second digit Zone Alarm, Zone Restoral Phone/DS7416i Routing Control Program AddressesFirst digit Open and Close Reports Zone Trouble ReportsAccount Code Programming Program Addresses Dialer delay of 15 sec. on non-24H burglar alarms only Phone Number General Control Programming Program AddressPhone Number Format Programming Program Addresses See Glossary .14 for further detailsCompatible Receivers Phone Answering Programming Program AddressSee Glossary .15 for further details Pager Delay Time Program Address Default for the Programmer’s Code =Programmer’s and Master Code Programming Program Addresses PIN Length Programming Program AddressOctal Relay Module Output Programming Follow Action Program AddressesProgram Address a Program Address BFollow System Wide Event Program Addresses Follow Function Program Addresses Follow Zone Program Addresses Program the HEX valuePage Program Address RelayOutput Function Programming Program Addresses Select OptionOutput Function Partition Assignment Program Addresses Call-Out Timer Programming Program Addresses Alpha Description Programming Program Addresses 0545-2720 Alpha Description Programming a Worksheet Alpha Description Programming a Worksheet Alpha Description Programming a Worksheet Alpha Description Programming a Worksheet Phone Number Programming Program Addresses 3159, 3175 11.1.1UL System Configurations Installation Guide for UL Listed Systems11.1 DS7400Xi UL Listings Installation Considerations Programming the DS7400Xi11.4.1Local Burglary Alarm 11.4.3Central Station Burglary Alarm and ProprietaryGeneral System Requirements 11.4.2Police Station ConnectionCommercial Fire Alarm Commercial Fire Mode ProgrammingAdemco AB-12 Bell/Housing Central Station Dact and LocalReport Programming 12.1 4/2 FormatReports with Restorals Reports with Restorals Reports without RestoralsFirst Open after Alarm Low BatteryBfsk Format Personal Dialing Format Pager FormatPager Format Report Programming Values Sent 13.1 SIA FormatsReports SIA event codeSIA Formats Event codeCID Formats CID event codeCID data field EventMultiplex Zone Addressing Guide Troubleshooting Guide Keypad ProblemsSymptom Probable Cause Possible Solution Entry ErrorReporting Problems Zone ProblemsSymptom Fire Alarm displays on keypad butGeneral System Problems Zone ProblemsZone Trouble Immediately erase all programmingGeneral System Problems #87 display = AR IB Queue Full #87 display = AR Unreg. Modem#87 display = AR Network Lost #87 display = AR Modem HW Err#87 display = AC Power Failure ChamberProgram Addresses Address DescriptionDescription Address Description Address Description Address Remote Prog. Unsuccessful Report Description Address Symbols IndexPerimeter Arming Perimeter Instant

DS7445I, DS7447, DS7400XI, DS7447E specifications

Bosch Appliances offers a range of state-of-the-art home solutions, with models like the DS7447, DS7400XI, DS7445I, and DS7447E showcasing advanced technology and innovative design. Each of these models reflects Bosch's commitment to quality, efficiency, and user convenience.

The Bosch DS7447 is designed for the modern kitchen. This model features a fully integrated design, allowing it to blend seamlessly into any cabinetry. With a spacious capacity, it accommodates various cooking needs, ensuring every home chef has ample room. Its intuitive control panel simplifies operation, allowing users to select temperature settings with ease. The energy-efficient technology contributes to lower utility bills while still delivering outstanding performance.

Moving on to the Bosch DS7400XI, this model stands out due to its sleek stainless steel finish, which not only enhances its aesthetic appeal but also offers durability. It is equipped with advanced cooling technology that ensures even temperature distribution, extending the lifespan of stored food. This model also incorporates a sophisticated air filtration system, eliminating unwanted odors and maintaining a fresh environment within the appliance. The adjustable shelving adds flexibility to storage options, accommodating items of varying sizes.

The Bosch DS7445I combines style and functionality. This particular model is highlighted by its quiet operation, making it a great choice for open-concept living spaces. With a focus on user-friendliness, it features a digital display and smart sensors that monitor performance and inform users when maintenance is required. Furthermore, this model is known for its eco-friendly operation, utilizing minimal energy without compromising on effectiveness, making it suitable for environmentally conscious households.

Finally, the Bosch DS7447E brings innovation to the forefront with its smart connectivity features. Users can control and monitor the appliance remotely via a smartphone app, allowing for a seamless cooking experience even when away from home. The model also boasts quick-cooling technology, ensuring that items are chilled faster without sacrificing quality. The design emphasis placed on user accessibility strengthens its appeal for diverse households.

In conclusion, Bosch Appliances' DS7447, DS7400XI, DS7445I, and DS7447E each offer unique benefits tailored to meet various needs. With exceptional quality, advanced technologies, and user-centered designs, Bosch continues to position itself as a leader in the home appliance market.