12.3Personal Dialing Format

This is a 2 pulse per second (PPS) 0/2 (no account code/2 report event digits) format intended for manual reception, i.e. the panel will call a phone number where a person is expected to answer. After a call is made, the panel will start sending the first report. If the report was a “Communication Test” and Program Address 3340 had a value of 12 the person answering the phone would hear 1 pulse followed by a 1 second delay, then 2 pulses followed by a 3 second delay. This sequence will repeat for 60 seconds per call. After the 60 seconds the panel will hang up and call again if any reports still remain to be sent.

A way to expedite this report process would be to provide an acknowledge to the panel that the report was heard and understood by the receiving party. When an acknowledge is provided, the panel will start sending the next report or hang up if no reports remain. To provide an acknowledge, press the 1 key of the telephone keypad during the 3 second delay of the report transmission. This “Acknowledge Feature” is an enhancement that will allow the panel to send all reports in one call. If the call is not acknowledged a communication failure is sent after all dial attempts are made.

Programming the first data digit as zero will disable the report. Values 1-9 and A-F are acceptable. A zero in the second data digit will send ten pulses.

12.4Pager Format

The Pager format allows the control panel to dial a digital pager and leave a numeric message which includes an account ID and report type. The telephone number is dialed when a report is available. At the completion of the telephone dialing, a time delay equal to 10 seconds occurs. This delay allows time to connect with the pager service, while skipping over any voice announcement. When the delay has ended, the numeric message is sent. This message includes the account number followed by up to 5 reports. If a delay time greater than 10 seconds is required, see Programming Address 4038 to adjust the delay time. In addition, increments of 3 seconds can be added by programming the “*3” character (3 second delay) at the end of the phone number in address 3159 or 3175.

For example, if you call pager number 123-4567 and it takes 20 seconds after you finished dialing before you are allowed to enter the message, the following digits should be programmed in address 3159: 1 2 3 4 5 6 7 *3 *3 *3 *3. This will give you an overall delay of 22 seconds.

NOTE: For Pager Format, it is not advisable to use the HEX character values (*0 = A, *1 = B, *2 = C, *3 = D, *4 = E, *5 = F) in the report programming addresses 3207 through 3419. These characters could cause unpredictable results when sent to a pager system that only expects numeric characters between 0-9. This is the reason that this format will not allow an associated user number with an open and close report.

The following are recommended programming values for addresses 3207 through 3419 when using the Pager format.

NOTE: The Pager format is an open-loop format which has no acknowledge tone. There is no indication at the control panel that the signal has been sent. Therefore, the Pager format is not recommended as the primary communication method.

Refer to the worksheet on the next page for Reports with Restorals. The values for each report can be determined by the user in conjunction with the installer. Again, the digit “0” (zero) should not be used as the reporting (first) digit as it will affect other reports in the system. Examples have been provided for possible reporting values, but the values can be set to the user’s preferences.

DS7400Xi ( 4+) Reference Guide

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01 Page 81

Image 81
Contents Access Control Keypad Quick Reference GuideNumber of hours from Table of Contents 12.0 Installation Guide for UL Listed Systems13.0 14.0Specifications Standby Current Load 15 Max. Load Currents Backup Battery CalculationDS7412 RS232 Serial Interface module OptionsCurrent Draw = 500 μA, Standby 560 μA, Alarm Enclosure Installation Install the EnclosureInstall the Control/Communicator Wiring Loop + Aux. Power Input Or PO2 Control Terminal WiringPower Indication LED Loop + ZoneHardware Layout Example Between battery wires and allS7430 DS7400XiSystem Worksheet System Worksheet Personal Identification Number InformationPIN Information User Pin # Auth Parti Name Level Tions 002 1001 James LPIN Information Type Zone/Output Partition & Location Zone Location and NotesSee section TypeSystem Worksheet System Worksheet Zone Location and Notes Worksheet General Control Programming GlossaryZone Function Programming General Authority by PartitionEntry/Exit Delay Cancel Zone Functions Zone ProgrammingZone Partition Control Programming Output ProgrammingCommercial Fire Mode Programming Ground Fault Detect ProgrammingCustom Arming Programming Keypad Assignment ProgrammingReport Programming Open/Close Report Control ProgrammingFailure Report Delay Phone Number General Control ProgrammingPhone Answering Programming Two-wire Connection For Installations in New ZealandFCC Compliance Notice FCC Phone Connection Notice To UsersFire Reset/Fire Trouble Emergency ProceduresEmergency Keypad Alarms Operating GuideIf Installed in Family Residences Fire SafetyInstallation Considerations Having and Practicing an Escape PlanPersonal Identification Numbers Programming PINsGeneral Information To set the expiration date for an existing Temporary PINTo arm all the Partitions to which you have access Single Partition ModeTo arm only some of the Partitions to which you have access Master KeypadSystem Faults Keypad Error DisplaysEvent History To readback the Event History BufferBattery Tests Testing Your SystemZone System Walk Test Communicator TestHow to Program the Control Panel To select Disabled, enter the data digit as a Understanding the Programming ChartsTo select Entry/Exit Delay #2, enter the data digit as a Enter one of these numbers for the appropriate data digitGeneral Control Programing Program Address ProgrammingAllow Maximum Security Arming Siren on Comm. Fail for Silent ZoneProgramming the Zone Functions Steady alarm responseZone Function Programming Program Addresses DetailsAssigning a Zone Function to the Zone Zone Programming Program AddressesThis step, a Zone function is assigned to the Zone Zone Programming Zone Type Program Addresses Assigning a Zone Type to the ZoneAssigning a Partition to the Zone Zone Partition Assignment Program AddressesBelongs to Partition Swinger Shunt Bypasses see programming for Program Address Zone Bypass Programming Program AddressesEnter the Data Digit as a Select Options Programmable Output Output Programming Program Addresses 2734, 2735Output Partition Assignment Program Addresses Data DigitData Digit Partition Control Programming Program AddressQuick Arm Control Programming Program Address Keypad Partition Assignment Program Addresses Keypad Assignment Programming Program AddressesSee Glossary .6 for further details Program AddressCustom Arming Programming Program Addresses Emergency Key Programming Program AddressesSee Glossary .7 for further details Data Digit Must beCustom Arming Programming Program Addresses Enter the Data Digit as a Select OptionsSee Glossary sections 6.9 and 6.10 for further details See Glossary .11 for further details Commercial Fire Mode Programming Program AddressReport Control Programming Program Address Open/Close Report Control Programming Program AddressSee Glossary .12 for further details SeeTimer Programming Program Addresses 4028-4030 AC Fail Report Delay Programming Program AddressSee Glossary .13 for further details General Authority Programming Program Address Arming Warning Programming Program AddressesSee Glossary .1 for further details Select Option Report Programming Program Addresses Report Programming Phone/DS7416i Routing Control Program Addresses Second digit Zone Alarm, Zone RestoralFirst digit Open and Close Reports Zone Trouble ReportsAccount Code Programming Program Addresses Phone Number General Control Programming Program Address Dialer delay of 15 sec. on non-24H burglar alarms onlyPhone Number Format Programming Program Addresses See Glossary .14 for further detailsPhone Answering Programming Program Address Compatible ReceiversSee Glossary .15 for further details Default for the Programmer’s Code = Pager Delay Time Program AddressProgrammer’s and Master Code Programming Program Addresses PIN Length Programming Program AddressFollow Action Program Addresses Octal Relay Module Output ProgrammingProgram Address a Program Address BFollow System Wide Event Program Addresses Follow Function Program Addresses Program the HEX value Follow Zone Program AddressesPage Relay Program AddressSelect Option Output Function Programming Program AddressesOutput Function Partition Assignment Program Addresses Call-Out Timer Programming Program Addresses Alpha Description Programming Program Addresses 0545-2720 Alpha Description Programming a Worksheet Alpha Description Programming a Worksheet Alpha Description Programming a Worksheet Alpha Description Programming a Worksheet Phone Number Programming Program Addresses 3159, 3175 Installation Guide for UL Listed Systems 11.1.1UL System Configurations11.1 DS7400Xi UL Listings Programming the DS7400Xi Installation Considerations11.4.3Central Station Burglary Alarm and Proprietary 11.4.1Local Burglary AlarmGeneral System Requirements 11.4.2Police Station ConnectionCommercial Fire Mode Programming Commercial Fire AlarmAdemco AB-12 Bell/Housing Central Station Dact and Local12.1 4/2 Format Report ProgrammingReports with Restorals Reports with Restorals Reports without RestoralsLow Battery First Open after AlarmBfsk Format Pager Format Personal Dialing FormatPager Format 13.1 SIA Formats Report Programming Values SentReports SIA event codeEvent code SIA FormatsCID event code CID FormatsCID data field EventMultiplex Zone Addressing Guide Keypad Problems Troubleshooting GuideSymptom Probable Cause Possible Solution Entry ErrorZone Problems Reporting ProblemsSymptom Fire Alarm displays on keypad butZone Problems General System ProblemsZone Trouble Immediately erase all programmingGeneral System Problems #87 display = AR Unreg. Modem #87 display = AR IB Queue Full#87 display = AR Network Lost #87 display = AR Modem HW ErrChamber #87 display = AC Power FailureAddress Description Program AddressesDescription Address Description Address Description Address Remote Prog. Unsuccessful Report Description Address Index SymbolsPerimeter Arming Perimeter Instant

DS7445I, DS7447, DS7400XI, DS7447E specifications

Bosch Appliances offers a range of state-of-the-art home solutions, with models like the DS7447, DS7400XI, DS7445I, and DS7447E showcasing advanced technology and innovative design. Each of these models reflects Bosch's commitment to quality, efficiency, and user convenience.

The Bosch DS7447 is designed for the modern kitchen. This model features a fully integrated design, allowing it to blend seamlessly into any cabinetry. With a spacious capacity, it accommodates various cooking needs, ensuring every home chef has ample room. Its intuitive control panel simplifies operation, allowing users to select temperature settings with ease. The energy-efficient technology contributes to lower utility bills while still delivering outstanding performance.

Moving on to the Bosch DS7400XI, this model stands out due to its sleek stainless steel finish, which not only enhances its aesthetic appeal but also offers durability. It is equipped with advanced cooling technology that ensures even temperature distribution, extending the lifespan of stored food. This model also incorporates a sophisticated air filtration system, eliminating unwanted odors and maintaining a fresh environment within the appliance. The adjustable shelving adds flexibility to storage options, accommodating items of varying sizes.

The Bosch DS7445I combines style and functionality. This particular model is highlighted by its quiet operation, making it a great choice for open-concept living spaces. With a focus on user-friendliness, it features a digital display and smart sensors that monitor performance and inform users when maintenance is required. Furthermore, this model is known for its eco-friendly operation, utilizing minimal energy without compromising on effectiveness, making it suitable for environmentally conscious households.

Finally, the Bosch DS7447E brings innovation to the forefront with its smart connectivity features. Users can control and monitor the appliance remotely via a smartphone app, allowing for a seamless cooking experience even when away from home. The model also boasts quick-cooling technology, ensuring that items are chilled faster without sacrificing quality. The design emphasis placed on user accessibility strengthens its appeal for diverse households.

In conclusion, Bosch Appliances' DS7447, DS7400XI, DS7445I, and DS7447E each offer unique benefits tailored to meet various needs. With exceptional quality, advanced technologies, and user-centered designs, Bosch continues to position itself as a leader in the home appliance market.