Schlage L-SERIES manual Electrified Locks, L9080PEL L9080PEU

Page 22

L S E R I E S

Electrified Locks

Typical Wiring Diagram for Electrified L-Series Locks

L9080PEL

L9080PEU

Frame to

Door Connector

(Not Furnished)

Varistor would

go here if used (Not Furnished)

Applications: Security control centers, cashier rooms, fire safety alarms, stairwell doors, telephone equipment rooms, computer rooms, hospital equipment, and narcotics areas.

Regulating Devices: Security alarms, wall switches, security consoles, access card readers, thermo-sensitive devices, smoke and fire alarms, telephone access controls, automatic time devices, and computerized controls.

All installations should be in accordance with local electrical codes and National Electrical Code, NFPA 70-1996.

Electrical Requirements for EL or EU

Voltage: 24V AC or 24V DC (Maximum 29V, Minimum 20V)

Peak Current: Amps 1.3 at 5 to 10 second intervals

Holding Current: Amps .135 between peak current intervals.

Operating Temperature: Maximum +151°F, Minimum -31°F

Micro Switch Electrical Requirements for

Request to Exit (RX) Function

Amps, 1.0; Volts, 24 AC or DC

Peak load: Amps, 5; Volts, 250 AC or 28 DC

Replacement Kit

L283-053–Solenoid and Driver, EL or EU

Switch

24V AC

115V AC

(Not Furnished)

Transformer

(Not Furnished)

Typical Installation

Electrified L-Series locks contain a transistorized circuit which provides full voltage to the solenoid upon initial application of electrical power and at 5 to 10 second intervals.

Each lock should preferably have its own 24 volt transformer. Two or more locks may be operated in parallel from a single transformer provided it has the necessary current rating.

NOTE: DO NOT connect locks in series from a higher volt- age rated transformer.

We DO NOT recommend that these locks be connected to a supply circuit that also contains electromagnetic devices. If an electromagnetic device is connected to the supply circuit the resulting transient voltages could damage the lock. The tran- sient voltage must be carefully suppressed at the equipment producing them before connecting the lock to the same cir- cuit.

A varistor rated at 35 volts (peak recurrent) may be used for transient voltage protection.

20

Image 22
Contents Series Extra Heavy Duty Mortise Locks Specifications Exposed TrimCutaway View Performance FeaturesDoor Preparation 625 Lever Designs & Finishes626 Knob Designs & Finishes FinishesMediterranean Designs & Finishes MeranoEscutcheons, Roses, Special Turns & Finishes Full FaceFunction Functions4 53 P Cylinder Suffix Lock SeriesL9040 F22 Bath/Bedroom Privacy Lock Mortise Locks-Non-KeyedL9010 F01 Passage Latch L9044 Privacy With Coin Turn OutsideL9056 Mortise Locks-KeyedL9050 F04 Office and Inner Entry Lock L9060 F09 Apartment Entrance LockL9082 Electrically Locked or L9080EL-RX Request To Exit RX Electrified L9080EU-RX LockL9082 Institution Lock L9082EL L9082EU Electrically Unlocked Both SidesStoreroom Lock With Deadbolt L9486 Hotel Lock w/ Do Not Disturb IndicatorL9480 L9485 L9486 F15 Hotel LockL9460 F17 Cylinder x Thumbturn Lock Deadbolt With Occupied IndicatorMortise Locks-Keyed Deadlocks L9462 F16 Double Cylinder LockL9040 Privacy With Turns Both Sides L9485 Special FunctionsL9110 Double Dummy With Active Trim L9482 L9460 L9460 With Fixed Dummy TrimPrimus High Security Cylinders Standard CylindersPrimus Lockout Cylinders Standard Non-IC Mortise Cylinders Standard Non-IC CylindersEscutcheons Full Size IC Mortise Cylinders Full Size Interchangeable Core CylindersFull Size Interchangeable Cores Only Small Format Interchangeable Core Only Small Format Interchangeable Core Sfic CylindersSmall Format Interchangeable Core Cylinders Core MechanismL400 and L9000 Series IC Installation ToolL9060 Outside Only Full Size Core Blocking Ring Requirements DimensionBlocking and Compression Rings Blocking Ring LengthElectrified Locks L9080PEL L9080PEUStandard Square Corner Armored FrontsArmored Fronts Standard Square Corner Armor StrikeRelocate catch screw Door HandingPull and rotate Left Hand Reverse Bevel626 625 How to Order626 605Administrative Offices