First Alert FA148CP, FA168CPS manual Download Information 94, Pager Options 160, 167, 169

Page 6
Part. 1 Part. 2 common [0,0,0]
[15]
NOTE: Do not enter “0” if using FA4285/FA4286 Phone Module.

92 PHONE LINE MONITOR ENABLE

UL: see Inst. Instructions for requirements

[0,0]

1 2

NOTE: Output Device must either be programmed to be STOPPED in field 80 or STOPPED by Code + # + 8 + output number.

Entry 1:: 0 = disabled, 1-15 = 1 min - 15 min

(#+10 = 10 min; #+11 = 11 min; #+12 = 12 min; #+13 = 13 min; #+14 = 14 min; #+15 = 15 min)

Entry 2:

0 = Keypad display when line is faulted

1 = Keypad display plus keypad trouble sound

2 = Same as “1”, plus programmed output device STARTS. If either partition is armed, external sounder activates also.

93

No. OF REPORTS IN ARMED PERIOD

[1]

 

PER ZONE (Swinger Suppression)

 

 

0 = Unlimited Reports; 1 = 1 report; 2 = 2 reports UL: must be “0”

SIA Installations: Must be set for option 1 or 2.

DOWNLOAD INFORMATION (94, 95)

94 DOWNLOAD PHONE No.

Enter up to 20 digits, 0–9; #+11 for ''; #+12 for '#'; #+13 for a 2-second pause. Do not fill unused spaces. If fewer than 20 digits, exit field by pressing . To clear entries from field, press 94. UL: downloading may be performed only if a technician is at the site.

95 RING COUNT FOR DOWNLOADING

96, 97 INITIALIZE/RESET DEFAULTS 98, *99 EXIT COMMANDS

PAGER OPTIONS (160- 172)

0 = Disable Station Initiated Download;

1–14 = number of rings (1–9, # +10 =10, # +11 =11,

# +12 =12, # +13 =13, # +14 =14);

15 = answering machine defeat (# +15 =15).

These are commands, not data fields. See page 2.

These are commands, not data fields. See page 2.

160 PAGER 1 PHONE No.

Enter up to 20 digits. 0–9; #+11 = ''; #+12 = '#'; #+13 = 2-second pause.

161 PAGER 1 CHARACTERS

162 PAGER 1 REPORT OPTIONS

Enter the optional prefix characters, up to 16 digits. 0–9; #+11 = ''; #+12 = '#'; #+13 = 2-second pause.

For each partition, select from the following options:

0 = no reports sent

1 = Open/closes all users

4 = All alarms and troubles

5 = All alarms / troubles, and open/closes for all users 12 = Alarms / troubles for zones entered in zone list 9 13 = Alarms / troubles for zones entered in zone list 9,

and open/closes for all users

163 PAGER 2 PHONE No.

Enter up to 20 digits. 0–9; #+11 = ''; #+12 = '#'; #+13 = 2-second pause.

164 PAGER 2 CHARACTERS

165 PAGER 2 REPORT OPTIONS

Enter the optional prefix characters, up to 16 digits. 0–9; #+11 = ''; #+12 = '#'; #+13 = 2-second pause.

[0,0,0] See field *162 for reporting options. Select for each partition (use zone list 10 if using options 12 or 13).

Part. 1 Part. 2 common

166 PAGER 3 PHONE No.

Enter up to 20 digits. 0–9; #+11 = ''; #+12 = '#'; #+13 = 2-second pause.

167

PAGER 3

CHARACTERS

 

 

 

Enter the optional prefix characters, up to 16 digits.

 

 

 

0–9; #+11 = ''; #+12 = '#'; #+13 = 2-second pause.

168

PAGER 3 REPORT OPTIONS

 

 

 

0,0,0]

 

See field *162 for reporting options. Select for each

 

 

 

Part. 1 Part. 2

common

partition (use zone list 11 if using options 12 or 13).

169

PAGER 4

PHONE No.

Enter up to 20 digits. 0–9; #+11 = ''; #+12 = '#'; #+13 = 2-second pause.

170 PAGER 4 CHARACTERS

171 PAGER 4 REPORT OPTIONS

172 PAGER DELAY OPTION FOR ALARMS

Enter the optional prefix characters, up to 16 digits.

0–9; #+11 = ''; #+12 = '#'; #+13 = 2-second pause.

 

 

[0,0,0]

See field *162 for reporting options. Select for each

Part. 1 Part. 2

common

partition (use zone list 12 if using options 12 or 13).

 

[3]

 

0 = none, 1 = 1 minute, 2 = 2 minutes, 3 = 3 minutes

 

 

 

 

This delay is for ALL pagers in the system.

 

 

 

6

Image 6
Contents $&36 $&3 K5305-5PRV2 10/03 Rev. aTo Enter Programming Mode RF JAM Option Installer CodeQuick ARM Enable Zone Sounds and Timing 3156, *57, *58 Menu Modes System Status Report CodesPrimary Phone No Restore Report Codes 70 76 71 72 73 74 Output and System Setup 77∗79, *80, *81, *82 Menu Modes 167 Download Information 94Pager Options 160 168Configurable Zone Type Options *182-*185 Touch Screen Device AUI EnableMiscellaneous System Fields *174-*181 Entry Zone Type EntryEntries for Fields *182 and *184 Field *182Reserved Zones = EOLZone Lists for Output Devices List No Used For… Contains These Zones…Output Definitions FA168CPSHour Audible Alarm Alarm by NightHour Silent Alarm Auxiliary AlarmDays 213 156157 159For Loop Function Zone Type For 5804BD Wireless Input TypesReports as †† Enabled By… This Device¬.3594l K5305-5PRV2 10/03 Rev. a Inc