Start Up Conditions

Thermal Expansion

Property Damage Hazard

Avoid water heater damage

Install thermal expansion tank if necessary

Contact qualified installer or service agency

Water supply system may, because of such events as high line pressure, frequent cut-offs, and the effects of water hammer have installed devices such as pressure reducing valves, check valves, back flow preventers, eta, to control these types of problems. When these devices are not equipped with an internal by-pass, and no other measures are taken, the devices cause the water system to be closed. As water is heated, it expands (thermal expansion) and closed systems do not allow for the expansion of heated water.

The water within the water heater tank expands as it is heated and increases the pressure of the water system. If the relieving

point of water heater's temperature-pressure relief valve is

reached, the valve will relief the excess pressure. The

temperature-pressure relief valve is not intended for the constant relief of thermal expansion. This is an unacceptable

condition and must be corrected.

It is recommended that any devices installed which could create a closed system have a by-pass and/or the system have an expansion tank to relieve the pressure built by thermal expansion. Thermal expansion tanks are available from Sears stores and through the Sears Service Centers. Contact the local plumbing inspector, water supplier and/or the Sears Service Center for assistance in controlling these situations, see Figure 26.

Thermal Expansion Tank Specifications

 

Tank

Dimensions

Pipe

Model

Capacity

in

Inches

Fitting

Number

In Gallons

Diameter

Len_lth

On Tank

153.331020

2

8(203mm)

12-3/4(323mm)

3/4"Male

153.331050

5

11 (279 mm)

144/4 (375 ram)

3/4" Male

 

Expansion

Tank Sizing

Chart

 

 

 

Inlet*

Water

Heater

Capacity

(Gallons)

 

Water

 

 

 

 

 

 

Pressure

30

40

50

66

80

Expansion

40psi

2

2

2

5

5

Tank

50psi

2

2

2

5

5

Capacity

60psi

2

2

5

5

5

Needed

70psi

2

2

5

5

5

 

80psi

2

5

5

5

5

*Highest recorded inlet water pressure in a 24 hour period or regulated water pressure.

NOTE: Expansion tanks are pre-charged with a 40 psi air charge. If the inlet water pressure is higher than 40 psi, the expansion tank's air pressure must be adjusted to match that pressure, but must not be higher than 80 psi.

WATER HEATER

(3)

eoLo

RESSUREGAOGE

RECOMMENDED INSTALLATION

(VERTICAL MOUNTING)

WATER HEATER

COLD WATER

INLET FITTING

FLOOR_ CEILING JOIST, ETC.

P4ES2U2g

VALVE WITH

_\'(1)BY-PASS

EXPANSION

WATER SHUT-OFF

PRESSURE GAUGEINLET COLD

ALTERNATE RECOMMENDED INSTALLATION

(HORIZONTAL MOUNTING)

FIGURE 26.

Strange Sounds

Possible noises due to expansion and contraction of some metal parts during periods of heat-up and cool-down do not represent harmful or dangerous conditions.

Condensation causes sizzling and popping within the burner area during heating and cooling periods and should be considered normal, see Condensation section.

Draft Hood Operation

Check draft hood operation by performing a worst case depressurization of the building. With all doors and windows closed, and with all air handling equipment and exhaust fans operating such as furnaces, clothes dryers, range hoods and bathroom fans, a match flame should still be drawn into the draft hood of the water heater with its burner firing. If the flame

23

Image 23
Contents Installation and service must be Safety InstructionInstallation Care Maintenance Troubleshooting Parts ListImportant Definitions Feel water before bathing or showering Improper installation and use may result Property damageRiskoffire Explosion HazardMatedal Needed Basic Water Piping 12-13 TemperatureLighting Operating Label Temperature Regulation Tank Sediment Cleaning Venting System InspectionVentpipe Diameter RecoveryDimensions Tank TypeBasic Tools Additional Tools Needed When Sweat SolderingMaterials Needed Pilot & Main Burner ThermostatALL Piping Materialsto be Suppliedby Customers FKURE5 Removing the Old Water HeaterFURE2 Fire Hazard Facts to Consider About LocationDoor FURE9 Insulation BlanketsALL AIR from Outdoors See Figures 9, 11,12 ALL AIR from Inside BuildingsProperty Damage Hazard Water PipingWater Damage Hazard Temperature-Pressure Relief ValveInstallation Completed Using Breathing Hazard Carbon Monoxide Gas Filling the Water HeaterVenting Property Damage HazardFire and Explosion Hazard Gas PipingFire and Explosion Hazard Sediment TrapsGAS Piping with ALL Black Iron Pipeto GAS Control GAS Control For Your Safety Read Before LightingTemperature Regulation Carbon Monoxide and Fire Hazard Tank Sediment Cleaning Burner InspectionBurner Cleaning Vent System InspectionDraining Temperature-Pressure Relief Valve OperationHousekeeping Anode Rod InspectionSee Figure Drain Valve Washer ReplacementService Strange Sounds Thermal Expansion Tank SpecificationsExpansion Tank Sizing Chart Start Up ConditionsAIR In Hot Water Faucets High Temperature Shut Off SystemCondensation Smoke OdorFURE27 Operational Conditions Leakage CheckpointsStay LIT Pilot Outage Model Numbers Key No. Part Description Burner AssemblySears, Roebuck and Co., Hoffman Estates, IL 60179 U.S.A Full ONE Year Warranty on Water HeaterLimited Warranty on Tanks That Leak

153.333315 HA, 153.333445, 153.333415 HA, 153.333545, 153.333345 specifications

The Kenmore 153.333345, 153.333545, 153.333445, 153.333315 HA, and 153.333415 HA air conditioning units represent a diversified range of solutions for both residential and commercial climate control needs. These models are specifically designed to meet the varying requirements of different environments, making them excellent choices for effectively managing indoor temperatures.

One of the main features of these Kenmore models is their advanced energy efficiency. Each unit is equipped with Energy Star certification, ensuring that they consume less electricity compared to standard models. This not only helps consumers save on energy bills but also contributes to environmental sustainability by reducing greenhouse gas emissions.

The cooling capacity of these units is tailored to fit spaces of various sizes. With BTU ratings that range across the different models, users can find an appropriate solution whether they require cooling for a small room or a more expansive area. Additionally, the inclusion of variable speed compressors allows for precise temperature control and improved humidity management, providing enhanced comfort without excessive energy expenditure.

Technologically, these models incorporate modern smart features that make user interaction seamless. Many of the Kenmore units can be controlled via smartphone apps and are compatible with smart home systems. This connectivity allows users to adjust settings, set schedules, and even monitor energy usage remotely.

The design of the Kenmore air conditioners emphasizes ease of installation and maintenance. Their lightweight construction permits simpler setups, while detachable filters ensure that air quality remains high by allowing for easy cleaning and replacement. Moreover, the units feature robust build quality, designed to withstand the rigors of daily use over many years.

In terms of noise levels, Kenmore has prioritized quiet operation. These air conditioners are engineered to operate at lower decibel levels, meaning that they can be used in bedrooms or quiet office spaces without causing disturbances.

In summary, the Kenmore 153.333345, 153.333545, 153.333445, 153.333315 HA, and 153.333415 HA air conditioning units present a blend of energy efficiency, advanced technology, ease of use, and reliability. These features make them excellent choices for anyone looking to optimize indoor comfort while minimizing energy impact.