New Buck Corporation 91 manual Minimum Clearances

Page 10

MINIMUM CLEARANCES:

The Model 91 Bay Fireplace Insert is intended for installation in accordance with the standard for chimneys, fireplaces, vents, and solid-fuel burning appliances. NFPA-211Code: NOTE-This model is not intended for installation into Zero Clearance or pre-fabricated fireplace.

1.The hearth must be of masonry construction and must extend a minimum of 24" in front of the firebox opening and a minimum of 8" to either side of the firebox opening.

2.Floor protector must be 3/8" minimum thickness non-combustible material or equivalent.

3.If your fireplace has wood trim above it, the wood trim musts be at least 20" above the top of the unit and may be a maximum of 1/2" thick.

4.If your fireplace has a wood mantel, the mantel or mantel supports must be located at a height of 30" above the top

Image 10
Contents Page Page Page Safety Standard Compliance Room Heater FeaturesOperating Controls Model 91 Wood Stove Identification EPA Compliance StatusCatalyst Equipped Catalyst WarrantyAchieving Catalytic LIGHT-OFF When Refueling Proper Fuel SelectionASH Removal Catalyst MonitoringCreosote Formation and Need for Removal Option a Installation Fireplace Insert Minimum Clearances Positioning the Heater Mounting the Trim PanelsFinal Check Section Model 91 BAY Minimum Clearances Tools for InstallationFloor Protection Preparing the Stove for Installation ChimneyClose Clearance Installations in inches Rise Per. FT Brick Clear Tested and Listed Wall Protector Wood Heater Safety Helpful HintsOperation Guide to the Different Burning Qualities of WoodBuilding a Fire Burn RatesPreventive Maintenance / Parts Replacement the Catalysts Door Gasket Replacement Cold Heater Motor Assembly Replacement Wiring Schematic Page