Carrier 48HJ015-025 Ð Fan Performance Data, 48HJ015, 208/230, 460-V Units, Airflow, Fiop

Page 13

Table 3A Ð Fan Performance Data, 48HJ015, 208/230, 460-V Units

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

0.2

 

 

0.4

 

 

0.6

 

 

0.8

 

 

1.0

 

 

(CFM)

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

3750

741

510

0.58

854

715

0.82

952

921

1.05

1041

1130

1.29

1124

1344

 

1.53

4000

773

647

0.74

882

859

0.98

978

1071

1.22

1064

1285

1.46

1145

1502

 

1.71

4250

806

796

0.91

912

1015

1.16

1004

1233

1.40

1089

1452

1.65

1167

1674

 

1.91

4500

839

958

1.09

942

1183

1.35

1032

1407

1.60

1114

1632

1.86

1191

1859

 

2.12

4750

873

1134

1.29

972

1365

1.56

1060

1595

1.82

1140

1825

2.08

1215

2056

 

2.34

5000

908

1323

1.51

1003

1560

1.78

1089

1796

2.05

1167

2032

2.32

1241

2268

 

2.58

5250

942

1527

1.74

1035

1769

2.02

1118

2011

2.29

1195

2252

2.57

1267

2494

 

2.84

5500

978

1745

1.99

1067

1992

2.27

1148

2240

2.55

1223

2487

2.83

1293

2733

 

3.11

5750

1013

1978

2.25

1099

2230

2.54

1179

2484

2.83

1252

2736

3.12

1321

2988

 

3.40

6000

1049

2227

2.54

1132

2483

2.83

1210

2742

3.12

1282

2999

3.42

1349

3257

 

3.71

6250

1085

2491

2.84

1166

2751

3.13

1241

3015

3.44

1312

3279

3.74

1378

3541

 

4.03

 

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

1.2

 

 

1.4

 

 

1.6

 

 

1.8

 

 

2.0

 

 

(CFM)

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

3750

1203

1562

1.78

1277

1784

2.03

1349

2010

2.29

1417

2240

2.55

1483

2473

 

2.82

4000

1222

1724

1.96

1294

1950

2.22

1364

2180

2.48

1431

2413

2.75

1495

2650

 

3.02

4250

1242

1900

2.16

1313

2129

2.43

1381

2362

2.69

1446

2599

2.96

1509

2839

 

3.23

4500

1264

2089

2.38

1333

2322

2.65

1399

2558

2.91

1463

2799

3.19

1525

3042

 

3.47

4750

1286

2290

2.61

1354

2528

2.88

1419

2769

3.15

1482

3012

3.43

1542

3259

 

3.71

5000

1310

2507

2.86

1376

2748

3.13

1440

2992

3.41

1501

3240

3.69

1560

3489

 

3.98

5250

1335

2737

3.12

1399

2983

3.40

1461

3230

3.68

1522

3481

3.97

Ð

Ð

 

Ð

5500

1360

2981

3.40

1423

3231

3.68

1484

3483

3.97

1543

3737

4.26

Ð

Ð

 

Ð

5750

1386

3241

3.69

1448

3495

3.98

1508

3750

4.27

Ð

Ð

Ð

Ð

Ð

Ð

 

6000

1413

3514

4.00

1474

3773

4.30

1532

4032

4.59

Ð

Ð

Ð

Ð

Ð

Ð

 

6250

1440

3803

4.33

1500

4066

4.63

1558

4330

4.93

Ð

Ð

Ð

Ð

Ð

Ð

 

 

 

LEGEND

Bhp

Ð Brake Horsepower Input to Fan

FIOP

Ð

Factory-Installed Option

Watts

Ð

Input Watts to Motor

NOTES:

1.Boldface indicates standard operating range.

2. indicates ®eld-supplied motor and drive required.

3.All other numbers indicate ®eld-supplied drive required.

4.Factory shipped motor drive range is 1194 to 1526 rpm. Other rpms require a ®eld-supplied drive.

5.Static pressure losses (i.e., economizer) must be added to exter- nal static pressure before entering Fan Performance table. See Table 7 for accessory/FIOP static pressure information.

6.Interpolation is permissible. Do not extrapolate.

7.Maximum continuous bhp is 4.25 and the maximum continuous watts are 3775. Extensive motor and drive testing on these units ensures that the full horsepower range of the motor can be uti- lized with con®dence. Using your fan motors up to the watts rating shown will not result in nuisance tripping or premature motor fail- ure. Unit warranty will not be affected.

13

Image 13
Contents Safety Considerations ContentsInstallation ``A ``B ``C Accessory Curb DescriptionPackage no Height 50DP900211Unit Maximum Shipping Weight Dimension aUnit Physical Data Base Unit Dimensions, 48HJ015,017 Base Unit Dimensions, 48HJ025 Air Distribution Ð Through-the-Bottom 48HJ017 and 025 Shown Combustion Fan Housing Location Electrical Data Make Electrical ConnectionsEquip GNDUnit Voltage Unit Make Outdoor-Air Inlet Adjustments48HJD015 All 48HJD025, HJE015 HJE017 Economizer Motor Control Module Location START-UP Accessory Field-Installed Economizer AdjustAirflow Ð Fan Performance Data, 48HJ015, 208/230, 460-V UnitsFiop Ð Fan Performance Data, 48HJ015, 575-V Units Fan Performance Data, 48HJ017 Units Air Quantity Limits Fan Performance Data, 48HJ025 UnitsUnit 48HJ Minimum CFM Maximum CFM Base Unit Operation Accessory/FIOP Economizer Static Pressure in. wgUnit CFM Economizer Pressure DropLubrication ServiceEvaporator Fan, 48HJ017,025 Units Evaporator Fan, 48HJ015 UnitsManufacturer Lubricant Condenser-Fan Adjustment Belt Tension Adjustment Ð To adjust belt tensionHigh and Low Outdoor-Air Temperature Economizer Checkout ProceduresGas Valve Adjustment Pilot AdjustmentMain Burner Removal Protective DevicesTypical Wiring Schematic 48HJ025 Shown Typical Wiring Schematic 48HJ025 Shown Typical Component Arrangement 48HJ025 Shown IFM AHAIFR CLOPage Page Packaged Service Training Page PRE-START-UP START-UP Checklist

48HJ015-025 specifications

The Carrier 48HJ015-025 is a distinguished series of rooftop packaged units renowned for their efficient performance and reliability in light commercial applications. Designed for a variety of indoor environments, these units are engineered to provide efficient heating and cooling solutions, making them suitable for retail spaces, offices, and other commercial buildings.

One of the main features of the Carrier 48HJ series is its advanced scroll compressor technology, which enhances the overall efficiency of the systems. This type of compressor is known for its durability and quiet operation, providing consistent temperature control while minimizing energy consumption. The use of a scroll compressor contributes to a higher Seasonal Energy Efficiency Ratio (SEER) and Heating Seasonal Performance Factor (HSPF), making these units a smart choice for energy-conscious businesses.

Additionally, the 48HJ series incorporates a multi-speed indoor blower that allows for precise airflow control. This feature ensures optimal indoor comfort by adjusting the air distribution based on the specific heating or cooling needs of the space. The ability to adapt to varying load conditions enhances efficiency and reduces energy wastage.

Another noteworthy characteristic of the Carrier 48HJ015-025 is its robust construction. Built with galvanized steel, the units are designed to withstand harsh environmental conditions, ensuring longevity and minimal maintenance requirements. The powder-painted finish offers corrosion resistance, contributing to the unit’s durability over time.

The series also integrates advanced controls for ease of operation. The user-friendly thermostat enables precise temperature management and can be programmed according to the specific needs of the facility. Moreover, compatibility with Building Management Systems (BMS) facilitates seamless integration into existing infrastructure, enabling remote monitoring and enhanced operational efficiency.

In terms of environmental considerations, the Carrier 48HJ series utilizes R-410A refrigerant, which is known for its reduced impact on the ozone layer compared to older refrigerants. This commitment to sustainability aligns with modern environmental standards and regulations.

Overall, the Carrier 48HJ015-025 stands out as a versatile and efficient rooftop packaged unit, perfect for varying commercial applications. Its combination of advanced technology, reliability, and user-focused design makes it a prominent choice for businesses seeking optimized climate control solutions while ensuring sustainability and energy efficiency.