Step 8 Ð Make Electrical Connections

FIELD POWER SUPPLY Ð Unit is factory wired for volt- age shown on unit nameplate.

When installing units, provide a disconnect per NEC (National Electrical Code) of adequate size (Table 2).

All ®eld wiring must comply with NEC and local requirements.

Route power and ground lines through control box end panel or unit basepan (see Fig. 4 and 5) to connections as shown on unit wiring diagram and Fig. 14.

The unit must be electrically grounded in accordance with local codes and NEC ANSI/NFPA 70 (National Fire Protection Association).

Field wiring must conform to temperature limitations for type ``T'' wire. All ®eld wiring must comply with NEC and local requirements.

Transformer no. 1 is wired for 230-v unit. If 208/230-v unit is to be run with 208-v power supply, the transformer must be rewired as follows:

1.Remove cap from red (208 v) wire.

2.Remove cap from orange (230 v) spliced wire.

3.Replace orange wire with red wire.

4.Recap both wires.

 

LEGEND

EQUIP

Ð Equipment

GND

Ð Ground

NEC

Ð National Electrical Code

TB

Ð Terminal Board

NOTE: Maximum wire size for TB1 is 2/0.

Fig. 14 Ð Field Power Wiring Connections

IMPORTANT: BE CERTAIN UNUSED WIRES ARE CAPPED. Failure to do so may damage the transformers.

Operating voltage to compressor must be within voltage range indicated on unit nameplate. On 3-phase units, volt- ages between phases must be balanced within 2%.

Table 2 Ð Electrical Data

 

NOMINAL

VOLTAGE

COMPRESSOR

 

 

 

OFM

 

 

 

IFM

 

POWER

COMBUSTION

POWER SUPPLY

DISCONNECT

UNIT

VOLTAGE

RANGE

No. 1

No. 2

 

 

 

 

 

 

 

 

 

 

 

EXHAUST

FAN MOTOR

 

 

 

 

SIZE

48HJ

(3 Ph,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Min

Max

RLA

LRA

RLA

LRA

Qty

 

FLA

LRA

 

Hp

FLA

LRA

FLA

LRA

FLA

 

MCA

 

MOCP*

FLA

 

LRA

 

60 Hz)

 

 

 

 

 

 

 

(ea)

 

(ea)

 

 

 

 

 

208/230

187

254

39.7

228

Ð

Ð

3

 

 

1.7

 

3.8

3.7

10.5/10.5

84.5/84.5

Ð

Ð

0.57

 

65/65

 

100/100

64/64

 

324/324

 

 

 

 

4.6

18.8

0.57

 

70/70

 

100/100

70/70

 

343/343

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

015

460

414

508

19.9

114

Ð

Ð

3

 

 

0.8

 

1.9

3.7

4.8

42.3

Ð

Ð

0.30

 

32

 

50

32

 

162

 

 

 

2.3

6.0

0.30

 

34

 

50

34

 

168

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575

518

632

16.0

91

Ð

Ð

3

0.75

 

1.5

 

3

3.9

23.4

Ð

Ð

0.57

 

26

 

40

26

 

119

 

 

 

2.1

4.8

0.57

 

28

 

40

29

 

124

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230

187

254

28.2

160

28.2

160

3

 

1.7

 

24.8

5

15.8/15.8

105/91

Ð

Ð

0.57

 

84/84

 

110/100

90/90

 

499/485

 

 

 

4.6

18.8

0.57

 

89/89

 

110/110

95/95

 

518/504

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

017

460

414

508

14.1

80

14.1

80

3

 

0.8

 

10.8

5

7.9

46

Ð

Ð

0.30

 

42

 

50

45

 

238

 

 

2.3

6.0

0.30

 

44

 

50

47

 

244

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575

518

632

11.3

64

11.3

64

3

 

0.75

 

8.4

 

5

6.0

37

Ð

Ð

0.57

 

34

 

40

36

 

190

 

 

 

 

2.1

4.8

0.57

 

36

 

45

39

 

195

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230

187

254

35.6

198

35.6

198

2

 

5.5

 

24.8

10

28.0/28.0

193/168

Ð

Ð

0.57

 

119/119

 

150/150

127/127

 

639/614

 

 

 

4.6

18.8

0.57

 

124/124

150/150

133/133

657/632

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

025

460

414

508

17.8

99

17.8

99

2

 

2.8

 

10.8

10

14.6

84

Ð

Ð

0.30

 

60

 

70

65

 

304

 

 

2.3

6.0

0.30

 

63

 

80

67

 

310

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575

518

632

14.3

79

14.3

79

2

 

3.4

 

8.4

 

10

13.0

66

Ð

Ð

0.57

 

52

 

60

56

 

241

 

 

 

 

2.1

4.8

0.57

 

54

 

60

59

 

246

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FLA

Ð

LEGEND

Full Load Amps

HACR

Ð Heating, Air Conditioning and Refrigeration

IFM

Ð Indoor (Evaporator) Fan Motor

LRA

Ð

Locked Rotor Amps

MCA

Ð Minimum Circuit Amps

MOCP

Ð Maximum Overcurrent Protection

NEC

Ð

National Electrical Code

OFM

Ð Outdoor (Condenser) Fan Motor

RLA

Ð

Rated Load Amps

*This is the maximum size permissible; smaller fuse size may be used where conditions permit.

NOTES: In compliance with NEC requirements for multimotor and combina- tion load equipment (refer to NEC Articles 430 and 440), the overcurrent pro- tective device for the unit shall be fuse or HACR breaker. The Canadian units may be fuse or circuit breaker.

9

Image 9
Contents Contents Safety ConsiderationsInstallation ``A ``B ``C Accessory Curb DescriptionPackage no Height 50DP900211Dimension a Unit Maximum Shipping WeightUnit Physical Data Base Unit Dimensions, 48HJ015,017 Base Unit Dimensions, 48HJ025 Air Distribution Ð Through-the-Bottom 48HJ017 and 025 Shown Combustion Fan Housing Location Electrical Data Make Electrical ConnectionsEquip GNDMake Outdoor-Air Inlet Adjustments Unit Voltage Unit48HJD015 All 48HJD025, HJE015 HJE017 Economizer Motor Control Module Location START-UP Accessory Field-Installed Economizer AdjustÐ Fan Performance Data, 48HJ015, 208/230, 460-V Units AirflowFiop Ð Fan Performance Data, 48HJ015, 575-V Units Fan Performance Data, 48HJ017 Units Fan Performance Data, 48HJ025 Units Air Quantity LimitsUnit 48HJ Minimum CFM Maximum CFM Base Unit Operation Accessory/FIOP Economizer Static Pressure in. wgUnit CFM Economizer Pressure DropLubrication ServiceEvaporator Fan, 48HJ015 Units Evaporator Fan, 48HJ017,025 UnitsManufacturer Lubricant Condenser-Fan Adjustment Belt Tension Adjustment Ð To adjust belt tensionHigh and Low Outdoor-Air Temperature Economizer Checkout ProceduresGas Valve Adjustment Pilot AdjustmentMain Burner Removal Protective DevicesTypical Wiring Schematic 48HJ025 Shown Typical Wiring Schematic 48HJ025 Shown Typical Component Arrangement 48HJ025 Shown IFM AHAIFR CLOPage Page Packaged Service Training Page PRE-START-UP START-UP Checklist

48HJ015-025 specifications

The Carrier 48HJ015-025 is a distinguished series of rooftop packaged units renowned for their efficient performance and reliability in light commercial applications. Designed for a variety of indoor environments, these units are engineered to provide efficient heating and cooling solutions, making them suitable for retail spaces, offices, and other commercial buildings.

One of the main features of the Carrier 48HJ series is its advanced scroll compressor technology, which enhances the overall efficiency of the systems. This type of compressor is known for its durability and quiet operation, providing consistent temperature control while minimizing energy consumption. The use of a scroll compressor contributes to a higher Seasonal Energy Efficiency Ratio (SEER) and Heating Seasonal Performance Factor (HSPF), making these units a smart choice for energy-conscious businesses.

Additionally, the 48HJ series incorporates a multi-speed indoor blower that allows for precise airflow control. This feature ensures optimal indoor comfort by adjusting the air distribution based on the specific heating or cooling needs of the space. The ability to adapt to varying load conditions enhances efficiency and reduces energy wastage.

Another noteworthy characteristic of the Carrier 48HJ015-025 is its robust construction. Built with galvanized steel, the units are designed to withstand harsh environmental conditions, ensuring longevity and minimal maintenance requirements. The powder-painted finish offers corrosion resistance, contributing to the unit’s durability over time.

The series also integrates advanced controls for ease of operation. The user-friendly thermostat enables precise temperature management and can be programmed according to the specific needs of the facility. Moreover, compatibility with Building Management Systems (BMS) facilitates seamless integration into existing infrastructure, enabling remote monitoring and enhanced operational efficiency.

In terms of environmental considerations, the Carrier 48HJ series utilizes R-410A refrigerant, which is known for its reduced impact on the ozone layer compared to older refrigerants. This commitment to sustainability aligns with modern environmental standards and regulations.

Overall, the Carrier 48HJ015-025 stands out as a versatile and efficient rooftop packaged unit, perfect for varying commercial applications. Its combination of advanced technology, reliability, and user-focused design makes it a prominent choice for businesses seeking optimized climate control solutions while ensuring sustainability and energy efficiency.