Carrier 48HJ015-025 Base Unit Operation, Accessory/FIOP Economizer Static Pressure in. wg

Page 17

Table 7 Ð Accessory/FIOP Economizer Static Pressure (in. wg)

UNIT

UNIT

CFM

ECONOMIZER

480HJ

VOLTAGE

PRESSURE DROP

 

 

 

3,750

.03

015, 017

 

4,000

.03

All

5,000

.05

 

 

6,000

.07

 

 

7,500

.10

 

 

6,000

.07

025

All

7,200

.09

9,000

.11

 

 

 

 

10,000

.12

 

 

 

 

LEGEND

BHP Ð Brake Horsepower

FIOP Ð Factory-Installed Option

NOTES:

1.The factory-assembled horizontal adapter substantially improves fan performance. See Fig. 24.

2.The static pressure must be added to external static pressure. The sum and the evaporator entering-air cfm should then be used in conjunction with the Fan Performance table to determine blower rpm, bhp, and watts.

Gas Heat Ð Verify gas pressures before turning on heat as follows:

1.Turn off manual gas stop.

2.Connect pressure gage to supply gas tap (See Fig. 13 on page 8).

3.Connect pressure gage to manifold pressure tap on gas valve.

4.Turn on manual gas stop and set thermostat to HEAT po- sition. After the unit has run for several minutes, verify that incoming pressure is 5.0 in. wg or greater, and that the manifold pressure is 3.5 in. wg. If manifold pressure must be adjusted, refer to Gas Valve Adjustment section on page 22.

5.After unit has been in operation for 5 minutes, check tem- perature rise across the heat exchangers. See unit infor- mative plate for correct rise limits of the heat supplied. Air quantities may need to be adjusted to bring the actual rise to within the allowable limits.

Base Unit Operation

COOLING, UNITS WITHOUT ECONOMIZER Ð When thermostat calls for cooling, terminals G and Y1 are ener- gized. The indoor (evaporator) fan contactor (IFC) and compressor contactor no. 1 (C1) are energized and evaporator- fan motor (IFM), compressor no. 1 (017,025) or unloaded compressor (015), and condenser fan start. The condenser- fan motors run continuously while unit is cooling. If the ther- mostat calls for a second stage of cooling by energizing Y2, compressor contactor no. 2 (C2) is energized and compres- sor no. 2 starts (017,025), or compressor no. 1 runs fully loaded (015).

A freeze protection thermostat (FPT) is located on the evaporator coil. It detects frost build-up and locks out the compressors, allowing the coil to clear. Once frost has melted, the compressors can be reenergized by resetting the thermostat.

HEATING, UNITS WITHOUT ECONOMIZER

NOTE: The 48HJD015 units have 1 stage of heat, and the 48HJE015, 48HJE017, and HJD025 units have 2 stages of heat.

First Stage Ð Turn unit power on. Open manual gas line valve. Set thermostat system switch at HEAT or AUTO. po- sition and set fan switch to AUTO. position for heating.

First-stage thermostat calls for heat. Time-delay relay for evaporator fan begins timer sequence. Induced-draft relay closes, and induced-draft motor starts.

Pressure switch closes and pilot valve no. 1 opens, allow- ing gas to ¯ow to the ®rst-stage pilot. Spark ignitor ignites pilot ¯ame. Sensor detects ¯ame and the main gas valve no. 1 opens. Gas ¯ows to main burners and ®rst-stage burners ignite. Spark igniter turns off.

When sequence is complete, time-delay relay closes and evaporator fans start.

Second-Stage Ð On 2-stage units, with an additional heat- ing call, the second-stage thermostat closes. (The control re- lay [HR2] closes during the ®rst stage of operation.) Pilot valve no. 2 opens, and the spark ignitor ignites pilot. The sensor detects a ¯ame and energizes main gas valve coil no. 2, opening main gas valve no. 2. Gas ¯ows to the main burners, and the second-stage burners ignite. The spark ignitor turns off.

When the second-stage thermostat is satis®ed, the second- stage gas valve closes.

When the ®rst-stage thermostat is satis®ed, the ®rst-stage gas valve closes. The induced-draft motor turns off, the time delay relay is deenergized, and the timer sequence begins. When the sequence is complete, the evaporator-fan motor turns off.

COOLING, UNITS WITH ECONOMIZER Ð Upon a call for cooling, when outdoor ambient is above the changeover control setting, the economizer damper moves to VENT position. The compressors and evaporator and condenser fans energize and operate as per Cooling, Units Without Econo- mizer section above.

Upon a ®rst call for cooling, when outdoor ambient is be- low the changeover control setting, the evaporator fan starts and the economizer is fully open. The compressors remain off.

Upon a second-stage call for cooling, compressor no. 1 (017,025) or unloaded compressor (015) is energized and me- chanical cooling is integrated with economizer cooling. If the outdoor-air temperature drops below 50 F, a cooling lock- out switch prevents the compressors from running.

When supply-air temperature drops below a ®xed set point, the economizer damper modulates to maintain the tempera- ture at the ®xed set point.

HEATING, UNITS WITH ECONOMIZER Ð Outdoor-air damper stays at VENT position while evaporator fan is operating.

17

Image 17
Contents Installation ContentsSafety Considerations ``A ``B ``C Accessory Curb DescriptionPackage no Height 50DP900211Unit Dimension aUnit Maximum Shipping Weight Physical Data Base Unit Dimensions, 48HJ015,017 Base Unit Dimensions, 48HJ025 Air Distribution Ð Through-the-Bottom 48HJ017 and 025 Shown Combustion Fan Housing Location Electrical Data Make Electrical ConnectionsEquip GND48HJD015 All 48HJD025, HJE015 HJE017 Make Outdoor-Air Inlet AdjustmentsUnit Voltage Unit Economizer Motor Control Module Location START-UP Accessory Field-Installed Economizer AdjustFiop Ð Fan Performance Data, 48HJ015, 208/230, 460-V UnitsAirflow Ð Fan Performance Data, 48HJ015, 575-V Units Fan Performance Data, 48HJ017 Units Unit 48HJ Minimum CFM Maximum CFM Fan Performance Data, 48HJ025 UnitsAir Quantity Limits Base Unit Operation Accessory/FIOP Economizer Static Pressure in. wgUnit CFM Economizer Pressure DropLubrication ServiceManufacturer Lubricant Evaporator Fan, 48HJ015 UnitsEvaporator Fan, 48HJ017,025 Units Condenser-Fan Adjustment Belt Tension Adjustment Ð To adjust belt tensionHigh and Low Outdoor-Air Temperature Economizer Checkout ProceduresGas Valve Adjustment Pilot AdjustmentMain Burner Removal Protective DevicesTypical Wiring Schematic 48HJ025 Shown Typical Wiring Schematic 48HJ025 Shown Typical Component Arrangement 48HJ025 Shown IFM AHAIFR CLOPage Page Packaged Service Training Page PRE-START-UP START-UP Checklist

48HJ015-025 specifications

The Carrier 48HJ015-025 is a distinguished series of rooftop packaged units renowned for their efficient performance and reliability in light commercial applications. Designed for a variety of indoor environments, these units are engineered to provide efficient heating and cooling solutions, making them suitable for retail spaces, offices, and other commercial buildings.

One of the main features of the Carrier 48HJ series is its advanced scroll compressor technology, which enhances the overall efficiency of the systems. This type of compressor is known for its durability and quiet operation, providing consistent temperature control while minimizing energy consumption. The use of a scroll compressor contributes to a higher Seasonal Energy Efficiency Ratio (SEER) and Heating Seasonal Performance Factor (HSPF), making these units a smart choice for energy-conscious businesses.

Additionally, the 48HJ series incorporates a multi-speed indoor blower that allows for precise airflow control. This feature ensures optimal indoor comfort by adjusting the air distribution based on the specific heating or cooling needs of the space. The ability to adapt to varying load conditions enhances efficiency and reduces energy wastage.

Another noteworthy characteristic of the Carrier 48HJ015-025 is its robust construction. Built with galvanized steel, the units are designed to withstand harsh environmental conditions, ensuring longevity and minimal maintenance requirements. The powder-painted finish offers corrosion resistance, contributing to the unit’s durability over time.

The series also integrates advanced controls for ease of operation. The user-friendly thermostat enables precise temperature management and can be programmed according to the specific needs of the facility. Moreover, compatibility with Building Management Systems (BMS) facilitates seamless integration into existing infrastructure, enabling remote monitoring and enhanced operational efficiency.

In terms of environmental considerations, the Carrier 48HJ series utilizes R-410A refrigerant, which is known for its reduced impact on the ozone layer compared to older refrigerants. This commitment to sustainability aligns with modern environmental standards and regulations.

Overall, the Carrier 48HJ015-025 stands out as a versatile and efficient rooftop packaged unit, perfect for varying commercial applications. Its combination of advanced technology, reliability, and user-focused design makes it a prominent choice for businesses seeking optimized climate control solutions while ensuring sustainability and energy efficiency.