Cooling Start−Up

The cooling section is a complete factory package utilizing an air−cooled condenser. The system is factory−charged with HFC−410A refrigerant. The compressor is hermetically sealed, internally sprung and base−mounted with rubber−insolated hold−down bolts.

Pre−Start Check List:

1 − Make sure refrigerant lines do not rub against the cabinet or each other.

2 − Inspect all electrical wiring, both factory− and field−installed, for loose connections.

3 − Check voltage at the disconnect switch. Voltage must be within the range listed on the unit nameplate. If not, consult power company and have voltage condition corrected before starting unit.

4 − Recheck voltage with unit running. If power is not within the range listed on the unit nameplate, stop the unit and consult the power company. Check unit amperage. Refer to unit nameplate for correct running amps.

5 − Make sure filter is in place before unit start−up.

Cooling Sequence of Operation

When the thermostat calls for cooling,

and 1). This completes the low voltage control

circuit, energizing the compressor, condenser fan motor and blower motor.

NOTE − At the start of the each cooling demand, the combustion air blower (draft motor) will operate for 10 seconds.

Unit compressors have internal protection. If there is an abnormal rise in the compressor temperature, the protector will open and the compressor will stop.

Blower Delay − Cooling

In the cooling mode, the circulating air blower operation is delayed for 5 seconds after the compressor starts. The blower continues to operate for 90 seconds after the compressor is de−energized.

NOTE − With the proper thermostat and subbase, continuous blower operation is possible by closing the R to G circuit. Cooling blower delay is also functional in this mode.

System Performance

This self−contained system has been factory−charged for optimal performance. If performance is questionable, use the following procedure to check the system.

Ensure that unit has been installed per these instructions and that line voltage and air flow are both correct. Check subcooling values by measuring pressure at the liquid line (high side) service port. Measure liquid line temperature within 2 inches of the service port connection to its main tube. If subcooling measured deviates from values in table 7 by more than 2 degrees F, check internal seals, service panels and duct system for air leaks, as well as restrictions. Also check blower speed settings. Make all necessary adjustments. If unit performance remains questionable, recover unit refrigerant charge, evacuate to 500 Microns, and weigh in refrigerant to match value given on unit nameplate. It is critical that exact required charge is used. Failure to follow this instruction will compromise system performance. If unit performance is still questionable, check for blocked coil or circuits, malfunctioning metering devices or other system component problems.

Table 7

Liquid Subcooling Values

 

Liquid Line Subcooling

Unit Model No.

+/− 2 Deg. F @ ARI

82_F OD minus 80_F IDDB

 

 

/ 67_F IDWB

 

 

15GCSX−24

12_

 

 

15GCSX−30

12_

 

 

15GCSX−36

15_

 

 

15GCSX−42

10_

 

 

15GCSX−48

7_

 

 

15GCSX−60

8_

 

 

Verify system performance using table 8 as a general guide. Table 8 should not be used for charging unit. Minor variations in these pressures may be expected due to differences in installations. Significant differences could mean that the system is not properly charged or that a problem exists with some component in the system.

Used carefully, this table could serve as a useful service guide. Data is based on 80°F dry bulb / 67°F wet bulb return air. Allow unit operation to stabilize before taking pressure readings.

Page 16

Image 16
Contents Table of Contents Retain These Instructions For Future Reference15GCSX Unit Dimensions − inches mm LbsParts Arrangement Safety Information GeneralShipping & Packing List Location Selection Rigging & Setting Unit Accessory Lift KitService Clearances − Inches Millimeters ClearancesVent Hood Installation Vent Hood InstallationExisting Common Vent Systems Page Filters Condensate DrainTypical Condensate Drain Supply & Return Duct Connections Unit Filter SizeRemoving Supply and Return Air Opening CoversGas Piping and Electrical Conduit Access CompressorsGas Supply and Piping Gas Heat Application DataDrip Leg Installation Pressure Test Gas PipingIsolate Gas Valve To Pressure Test Gas piping recommendations208/230 Line Voltage Wiring Heat Anticipator SettingElectrical Thermostat15GCSX Series Gas Packaged Units Typical Wiring Diagram Blower Control A54 Blower Control A54Cool Cooling Start−Up Normal Operating Pressures Heating Start−UpHoneywell VR8205 Series Gas Valve Checking and Adjusting Gas Input Post Start−up Check List GasHigh Altitude Information Heating Sequence of OperationBlower Delay − Heating Unit ControlsBlower Control A54 Ignition Control A3Pressure Switch Rollout SwitchIgnition Control Ignition Control LED CodesComfort Alert Code Auto−Reset Function Condenser Fan ClearancesSystem Operation Monitor Lsom System Operation Monitor A132System Operation Monitor LED Troubleshooting Codes Maintenance Planned ServiceRepair Parts & Accessories
Related manuals
Manual 4 pages 39.07 Kb

Gas Packaged Units, 15GCSX specifications

Lennox International Inc. is a leading name in the HVAC industry, renowned for its innovative and energy-efficient products. Among its featured offerings are the 15GCSX Gas Packaged Units, specifically designed to provide reliable heating and cooling performance for residential and light commercial applications.

The 15GCSX models stand out with their impressive efficiency ratings, achieving up to 14 SEER (Seasonal Energy Efficiency Ratio) for cooling and 81% AFUE (Annual Fuel Utilization Efficiency) for heating. This ensures that users can enjoy a comfortable indoor environment while also managing energy costs, making them an environmentally friendly choice.

One of the key features of the 15GCSX is its compact design, allowing for easy installation in tight spaces. This is particularly beneficial for urban settings where space can be at a premium. The unit’s all-in-one design integrates both heating and cooling capabilities, eliminating the need for separate systems and simplifying maintenance.

The 15GCSX Gas Packaged Units utilize advanced technologies to optimize performance. Equipped with Lennox’s proprietary iComfort technology, these units can connect to smart thermostats, allowing users to monitor and adjust settings remotely. This innovation enhances energy savings and provides users with full control over their indoor climate, contributing to enhanced comfort levels.

In terms of durability, the 15GCSX models feature a robust construction, complete with weather-resistant cabinet materials designed to withstand the elements. The unit’s stainless steel heat exchanger is built for longevity and efficiency, further enhancing the overall reliability of the system.

Noise reduction is another critical consideration in the design of the 15GCSX units. They come equipped with a specially designed, quiet-running fan and compressor that help to minimize operational sound levels, ensuring a peaceful indoor environment during use.

In conclusion, the Lennox 15GCSX Gas Packaged Units represent a high-quality solution for efficient heating and cooling needs. With their combination of advanced technology, energy efficiency, compact design, and durability, these units are an excellent choice for homeowners and businesses seeking reliable climate control. The integration of smart features and silent operation further solidifies their position as a preferred option in the HVAC market.