Goodman Mfg PG 15 specifications Unit Location, Outside Slab Installation

Page 5

CARBON MONOXIDE POISONING HAZARD

Special Warning for Installation of Furnaces or Air Handling Units in Enclosed Areas such as Garages, Utility Rooms or Parking Areas

Carbon monoxide producing devices (such as an automobile, space heater, gas water heater, etc.) should not be operated in enclosed areas such as unventilated garages, utility rooms or parking areas because of the danger of carbon monoxide (CO) poisoning resulting from the exhaust emissions. If a furnace or air handler is installed in an enclosed area such as a garage, utility room or parking area and a carbon monoxide producing device is operated therein, there must be adequate, direct outside ventilation.

This ventilation is necessary to avoid the danger of CO poisoning which can occur if a carbon monoxide producing device continues to operate in the enclosed area. Carbon monoxide emissions can be (re)circulated throughout the structure if the furnace or air handler is operating in any mode.

CO can cause serious illness including permanent brain damage or death.

B10259-216

To avoid possible illness or death of the building occupants, do NOT locate outside air intake device (economizer, manual fresh air intake, motorized fresh air intake) too close to an exhaust outlet, gas vent termination, or plumbing vent outlet. For specific distances required, consult local codes.

Allow minimum clearances from the enclosure for fire protection, proper operation, and service access (see appendix). These clearances must be permanently maintained.

The combustion air inlet and flue outlet hoods on the unit must never be obstructed. If used, do not allow the economizer/manual fresh air damper/ motorized fresh air damper to become blocked by snow or debris. In some climates or locations, it may be necessary to elevate the unit to avoid these problems.

When the unit is heating, the temperature of the return air entering the unit must be between 50° F and 100° F.

GROUND LEVEL INSTALLATIONS ONLY:

When the unit is installed on the ground adjacent to the building, a level concrete (or equal) base is recommended. Prepare a base that is 3” larger than the package unit footprint and a minimum of 3” thick.

The base should also be located where no runoff of water from higher ground can collect in the unit.

UNIT LOCATION

IMPORTANT NOTE: Remove wood shipping rails prior to instal- lation of the unit.

ALL INSTALLATIONS:

For proper flame pattern within the heat exchanger and proper condensate drainage, the unit must be mounted level.

The flue outlet hood must be at least 12 inches from any opening through which flue gases could enter a building, and at least three feet above any forced air inlet located within ten feet. The economizer/manual fresh air intake/ motorized fresh air intake and combustion air inlet mounted on the unit are not affected by this restriction.

To avoid possible corrosion of the heat exchanger, do not locate the unit in an area where the outdoor air (i.e. combustion air for the unit) will be frequently contaminated by compounds containing chlorine or fluorine. Common sources of such compounds include swimming pool chemicals and chlorine bleaches, paint stripper, adhesives, paints, varnishes, sealers, waxes (which are not yet dried) and solvents used during construction and remodeling. Various commercial and industrial processes may also be sources of chlorine/ fluorine compounds.

Outside Slab Installation

ROOFTOP INSTALLATIONS ONLY:

NOTE: To ensure proper condensate drainage, unit must be installed in a level position.

To avoid possible property damage or personal injury, the roof must have sufficient structural strength to carry the weight of the unit(s) and snow or water loads as required by local codes. Consult a structural engineer to determine the weight capabilities of the roof.

5

Image 5
Contents Ansi Z21.47CSA-2.3 Central Furnaces PG 15 Seer M SeriesIndex Index Safety Instructions Replacement PartsUnit Location Outside Slab InstallationRoof Curb Installation Rooftop InstallationGAS Piping Rigging DetailsRigging Natural Gas ConnectionTypical Propane Gas Piping Proper Piping PracticePropane Gas Pipe Sizing Electrical WiringTwo-Stage Heating with Two-Stage Cooling Thermostat Diagram Horizontal Air Flow Duct Cover Installation Down Discharge ApplicationsCirculating AIR and Filters Venting Filter InstallationCondensate Drain Drain ConnectionHeat Anticipator Setting STARTUP, ADJUSTMENTS, and ChecksNormal Sequences of Operation Rollout Protection ControlWith Power And Gas On With Power And Gas OffSecondary Limit Control Pre-Operation Checks Gas Supply And Manifold CheckBlower Speed Adjustments Temperature Rise CheckManifold Gas Pressure Range Nominal Gas Input Natural Gas Only CheckTroubleshooting Check wiring Flame Sensor MaintenanceManifold Assembly Accessories and Functional PartsFunctional Parts List Burner FlameAppendix Ignition Control Diagnostic Indicator Chart Dimension Medium Large YL/BK BL/PK LPS 0140G00533 REV a PG15*****41B* Wiring Diagram PG15*****41B* Wiring Diagram Ton 2 Ton 2 -/ 4 Ton Unit= Outside of Temperature Rise Range Not Recommended Before Calling Your Servicer

PG 15 specifications

Goodman Manufacturing's PG 15 series stands out in the competitive HVAC market as a high-efficiency, cost-effective option for both residential and light commercial applications. This product line is particularly valued for its reliable performance and innovative technologies, which focus on energy efficiency, durability, and user comfort.

One of the main features of the PG 15 is its SEER (Seasonal Energy Efficiency Ratio) rating, which reflects its ability to provide superior cooling while using less energy. The higher the SEER rating, the more efficiently the unit operates, leading to significant savings on energy bills. The PG 15 boasts an impressive SEER rating, making it an ideal choice for conscientious consumers looking to lower their utility costs.

Incorporating advanced technologies, the PG 15 features a high-efficiency scroll compressor. This design minimizes vibration and noise, providing a quieter operation that enhances overall comfort in the living or working environment. Additionally, the compressor is designed for longevity, reducing maintenance needs and enhancing the unit's lifespan.

Another notable characteristic of the PG 15 is its durable construction. The unit is built with a galvanized steel cabinet that is protected with a rust-resistant finish, ensuring it withstands the rigors of harsh weather conditions. The 15-inch fan motor and multi-speed blower also contribute to efficient airflow and improved indoor air quality, while the refrigerant management system aids in efficient cooling performance.

Installation versatility is another advantage of the PG 15 series. Designed to accommodate a range of installation setups, this system can easily integrate into existing frameworks, making it suitable for both new constructions and retrofits.

Furthermore, Goodman Mfg places emphasis on customer satisfaction and support. The PG 15 series comes with a comprehensive warranty, offering peace of mind to homeowners and business owners alike. This commitment to quality and customer service has helped Goodman establish a reputation for reliability and performance in the HVAC industry.

In summary, the Goodman PG 15 stands out due to its energy-efficient design, advanced technologies, durable construction, and versatile installation options, making it a compelling choice for anyone seeking an effective and reliable HVAC solution.