Heat & Glo LifeStyle PIER-40 owner manual Assemble Chimney Sections, Install Chimney Air Kit

Page 27

C. Assemble Chimney Sections

Warning! Risk of Fire! Do NOT install substitute or damaged chimney components.

Use only those components described in this manual.

Substitute or damaged chimney components could impair safe operation and cause overheating and fire.

Support the pipe during construction and check to be sure inadvertent loading has not dislodged the chimney section from the fireplace or at any chimney joint.

Attach a straight chimney section or an offset to the top of the fireplace.

Place inner flue to the inside of the chimney section below it. Place the outer casing outside the outer casing of the chimney section below it. Refer to Figure 8.4.

NoTICE: Chimney sections cannot be disassembled once locked together. Plan ahead!

Lock chimney sections and/or offsets/returns together by pushing downward until the top section meets the stop bead on the lower section.

Pull on the top section to make sure it is fully engaged and will not separate.

You may use #6 or #8 sheet metal screws no longer than 1/2 in. (13 mm) to fasten chimney sections together. Do NOT penetrate inner flue.

Warning! Risk of Fire! You MUST use screws (pro- vided) to fasten offset/returns to chimney sections to keep the chimney parts from twisting. Failure to do so could cause fire.

Fasten offset/returns to chimney sections. Insert the screws (provided) through the predrilled holes. Do NOT penetrate inner flue.

Secure chimney returns with hanger straps provided; fasten to studs or joists.

Vertical straight runs of chimney must be supported every 35 ft (10.7 m).

D. Install Chimney Air Kit

Follow instructions provided with this accessory.

Figure 8.4 Assembling Chimney Sections

Heat & Glo • BAY-40, PIER-40 • 34977 • Rev AB 7/12

27

Image 27
Contents Hot screen/mesh and glass doors will cause burns Fire RiskListing Label Information/Location GrateNumber Model Table of Contents Installer GuideUser Guide Limited Lifetime Warranty Warranty Hearth & Home Technologies IncThis warranty is void if Warranty ConditionsCombustible Materials Listing and Code ApprovalsAppliance Certification Non-Combustible MaterialsOperating Instructions Your FireplaceHot glass will cause burns Firescreen Seasoned WoodStarting a Fire GrateVented Gas Log Sets & Gas Log Lighters Glass DoorsOutside Air optional Optional ComponentsWood Fuel Creosote Formation and Need for Removal Maintenance and ServiceChimney Inspection/Cleaning Disposal of AshesFrequency As desired Glass CleaningCheck Firebox Refractory Inspect GrateStart Fire Problems Possible Cause Solution Troubleshooting GuideTypical Fireplace System Getting StartedDesign and Installation Considerations DraftNegative Pressure Frequently open doors Central heat outlets or returns Locating Fireplace & ChimneyTools and Supplies Needed Fireplace System RequirementsInspect Fireplace and Components Select Fireplace Location Framing & ClearancesAir Space Clearances ClearancesSidewalls/Surrounds Frame the FireplacePlace Protective Metal Hearth Strips Installation of FireplaceThings to Consider Position the FireplaceFt min. from top of uppermost chimney section to air inlet Install Outside Air Kit AK17 Installation BAY-40AK14/AK18 Installation PIER-40 Chimney Assembly Height of Chimney Components Chimney RequirementsExample Using Offsets/ReturnsAssemble Chimney Sections Install Chimney Air KitInstalling the Ceiling Firestop Install Ceiling Firestops330 mm Install Attic Insulation ShieldCut out Hole in Roof Complete InstallationInstall Flashing Following steps should be skipped if using a chaseFlat Roofs Chimney Termination RequirementsConstruct the Chase Chase InstallationsInstall Chase Top Install Fireplace & ChimneyST1175 Square Termination Cap Install Termination CapTCT1175 Terra Cotta Cap Open Top Shroud TR11/TR11T caps require radiation shield ShroudsRadiation Shield Field Constructed ShroudsRoofed Style Shroud radiation shield required Mailbox Style Shroud radiation shield requiredFinishing Hearth Extension= 1/k x inches of thickness 1575 mm Hearth Refractory In. Micore or equivilent insulation Finishing MaterialSidewalls/Surrounds Combustible MantelGas Code, Ansi Z223.1 AccessoriesGas Log/Lighter Provision Wood Burning InsertsReference Materials Fireplace Dimensions13 mm Catalog # Description Chimney Components15-1/4 387 mm 483 mm 15-5/8 397 mm BAY-40 Service PartsStocked At DepotComments Part number list on following Service PartsPIER-40 Part number list on followingPier-40 Do not Discard this Manual