Heat & Glo LifeStyle PIER-40 owner manual Combustible Mantel, Sidewalls/Surrounds

Page 41

E. Combustible Mantel

Refer to shaded areas of Figure 11.4 for locations and dimensions of a combustible mantel.

A combustible mantel may be positioned no lower than 14 1/4 in. (362 mm) above the top of the fireplace opening.

A combustible mantel may have a maximum depth of 12 in. (305 mm).

Combustible trim and materials cannot be placed within 6 in. (152mm) of the fireplace opening (top or sides).

Combustible materials projecting more than 1 1/2 in. (38 mm) shall not be placed within 12 in. (305 mm) from the top of the fireplace opening.

Combustible trim must not cover the metal surfaces of the fireplace.

Mantel clearance is in accordance with Section 7-3.3.3of ANSI/ NFPA211.

F. Sidewalls/Surrounds

 

 

7 ft (2134 mm)

 

 

minimum

 

 

base of fireplace

 

Combustible

to ceiling

 

 

Combustible Wall

Decorative Facing

 

 

 

2 x 4 stud wall

 

 

 

Grid represents 1 in. squares

Standoffs

 

 

 

12 in./305 mm

 

 

Mantel

 

Non-combustible

14 1/4 in./362 mm

 

minimum

Decorative Facing

 

12 in./305 mm

 

such as: Steel, iron,

 

brick, tile, concrete,

minimum

 

 

 

slate, tile, plasters

 

 

1 1/2 in./38 mm

 

 

 

 

 

 

6 in./152 mm

maximum

 

 

 

 

minimum

 

 

 

Seal joint with

non-combustibleMeasured from top of fireplace opening sealant

Figure 11.4 Clearances to Mantels or other Combustibles above Fireplace

Adjacent combustible sidewalls must be located a minimum of 12 in. (305 mm) from the fireplace opening.

Combustible or non-combustible mantel legs, surrounds and stub walls may be constructed per Figure 11.5.

4 in.

[102 mm]

11.92in. [303 mm]

FLUSH

FRONT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

36 in.

 

 

 

 

 

 

 

angle

 

 

[914 mm]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50°

 

 

 

 

 

 

 

 

 

 

 

(fireplace opening)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40 in.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[1016 mm]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12 in.

 

 

 

[305 mm]

 

 

 

 

 

 

36 in.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[914 mm]

 

 

 

 

 

 

 

 

 

 

39°

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(fireplace opening

 

 

 

angle

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40 in.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[1016 mm]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12 in.

 

 

 

 

 

 

 

 

 

[305 mm]

9 3/4 in.

[248 mm]

BRICK

FRONT

Figure 11.5 Mantel Leg or Wall Projections (acceptable on both sides of opening)

Heat & Glo • BAY-40, PIER-40 • 34977 • Rev AB 7/12

41

Image 41
Contents Hot screen/mesh and glass doors will cause burns Fire RiskNumber Model Listing Label Information/LocationGrate User Guide Table of ContentsInstaller Guide Limited Lifetime Warranty Warranty Hearth & Home Technologies IncThis warranty is void if Warranty ConditionsAppliance Certification Listing and Code ApprovalsNon-Combustible Materials Combustible MaterialsHot glass will cause burns Operating InstructionsYour Fireplace Starting a Fire Seasoned WoodGrate FirescreenOutside Air optional Glass DoorsOptional Components Vented Gas Log Sets & Gas Log LightersWood Fuel Chimney Inspection/Cleaning Maintenance and ServiceDisposal of Ashes Creosote Formation and Need for RemovalCheck Firebox Refractory Glass CleaningInspect Grate Frequency As desiredStart Fire Problems Possible Cause Solution Troubleshooting GuideTypical Fireplace System Getting StartedNegative Pressure Design and Installation ConsiderationsDraft Frequently open doors Central heat outlets or returns Locating Fireplace & ChimneyInspect Fireplace and Components Tools and Supplies NeededFireplace System Requirements Select Fireplace Location Framing & ClearancesAir Space Clearances ClearancesSidewalls/Surrounds Frame the FireplaceThings to Consider Installation of FireplacePosition the Fireplace Place Protective Metal Hearth StripsFt min. from top of uppermost chimney section to air inlet AK14/AK18 Installation PIER-40 Install Outside Air KitAK17 Installation BAY-40 Chimney Assembly Height of Chimney Components Chimney RequirementsExample Using Offsets/ReturnsAssemble Chimney Sections Install Chimney Air KitInstalling the Ceiling Firestop Install Ceiling Firestops330 mm Install Attic Insulation ShieldInstall Flashing Complete InstallationFollowing steps should be skipped if using a chase Cut out Hole in RoofFlat Roofs Chimney Termination RequirementsConstruct the Chase Chase InstallationsInstall Chase Top Install Fireplace & ChimneyST1175 Square Termination Cap Install Termination CapTCT1175 Terra Cotta Cap Radiation Shield ShroudsField Constructed Shrouds Open Top Shroud TR11/TR11T caps require radiation shieldRoofed Style Shroud radiation shield required Mailbox Style Shroud radiation shield required = 1/k x inches of thickness Finishing Hearth Extension 1575 mm Hearth Refractory In. Micore or equivilent insulation Finishing MaterialSidewalls/Surrounds Combustible MantelGas Log/Lighter Provision AccessoriesWood Burning Inserts Gas Code, Ansi Z223.1Reference Materials Fireplace Dimensions13 mm Catalog # Description Chimney Components15-1/4 387 mm 483 mm 15-5/8 397 mm BAY-40 Service PartsComments StockedAt Depot PIER-40 Service PartsPart number list on following Part number list on followingPier-40 Do not Discard this Manual