Desa (V)G42/50, (V)G42R/50R, (V)G42H/50H Firestop Spacers FS-10, Penetrating the roof

Page 9

Venting Installation

Continued

Screws

B

A

Figure 9 - Elbow Offset

Firestop Spacers (FS-10)

Firestop spacers are required at each point where the chimney penetrates a floor space. Their purpose is to establish and maintain the required clearance between the chimney and the combustible materials. When the pipe passes through a framed opening into a living space above, the firestop must be placed onto the ceiling from below as shown in Figure 10.

Penetrating the roof

To maintain a 1" clearance to the pipe on a roof with a pitch, a rectangular opening must be cut.

1.Determine the center point through which the pipe will penetrate the roof.

2.Determine the center point of the roof. Pitch is the distance the roof drops over a given span, usually 12". A 6/12 pitch means that the roof drops 6" for each 12" one measure horizontally down from the roof rafters.

3.Use the roof opening chart (Figure 12) to determine the correct opening length and flashing required.

4.Remove the shingles around the opening measured. Cut out this section.

5.Add the next sections of the pipe until the end penetrates the roof line. Check to see that the proper clearances are maintained. Extend chimney by adding sections of double wall pipe until pipe is minimum of 30" above the highest point of the roof cutout. Termination and chimney must extend a minimum of 36" above the highest point where it passes through the roof.

They also provide complete separation from one floor space to another or attic space as required by most codes. When the double wall pipe passes through a framed opening into an attic space, the firestop must be placed into an attic floor as shown in Figure 11.

Existing

Ceiling

Frame

Firestop

Spacer

19.5" Min.

2" Min.

2" Min.

30" Min.

2" Min.

Opening "A"

Screws or Staples (Min. of 8)

Figure 10 - Firestop Spacer with Living

Space Above Ceiling

Screws or Staples

Firestop(Min. of 8) Spacer

Existing

Ceiling

Frame

Figure 11 - Firestop Spacer with Attic

Space Above Ceiling

Pitch

Slope

Opening

Used Flashing

 

 

"A" Max.

Model No.

Flat

19.5"

V6F-10DM

0-6/12

26.6°

22"

V6F-10DM

6/12-

45.0°

27"

V12F-10DM

12/12

 

 

 

Figure 12 - Roof Opening Measurements

Flashing installation (v6f-10dm or v12f-10dm)

Determine the flashing to be used with the roof opening chart. Slide flashing over pipe until base is flat against roof. Replace as many shingles as needed to cover exposed area and flashing base. Secure in position by nailing through shingles (see Figure 13, page 10). DO NOT NAIL THROUGH FLASHING CONE.

109493-01Nwww.desatech.com

Image 9
Contents Save this Book Safety Information Table of ContentsModels SpecificationsRound TOP Termination Selecting location Fireplace InstallationMinimum clearance to combustibles FramingMantels Hearth ExtensionAssembly and installation of double wall chimney system Venting InstallationOptional Outside air Kit Model ak4/ak4f Chimney PipeElbow SET only Using Elbow offsets 30E-12DMFlashing installation v6f-10dm or v12f-10dm Firestop Spacers FS-10Penetrating the roof Installing Flashing on a Metal Roof Chase installationsOptional Gas Line Installation Foot ruleFinishing the fireplace Installing Door Frames Glass Door InstallationInstalling glass doors Operation Maintenance GuidelinesDoor Adjustment Glass DoorsOutside air and damper handle operation Technical ServiceReplacement Parts Herringbone Brick LinerEmber Protector EP-36 Ash Box StandarD Brick Liner Bi-Fold Glass Door AccessoriesDouble Wall Pipe 12-12DM Offset and Return

(V)G42H/50H, (V)G42/50, (V)G42R/50R, (V)G42HR/50HR specifications

Desa (V)G42/50, (V)G42HR/50HR, (V)G42R/50R, and (V)G42H/50H represent a series of advanced heating solutions designed to meet varied thermal requirements while ensuring energy efficiency and user comfort. Each model in this range boasts its unique features that cater to specific needs, providing versatility for residential and commercial applications.

The (V)G42/50 series serves as a staple in modern heating technology. With a focus on efficiency and environmental sustainability, these models utilize high-efficiency burners and sophisticated heat exchangers that maximize heat output while minimizing fuel consumption. Their compact design allows for easy installation in limited spaces, making them an ideal choice for both contemporary and traditional settings. Comfort is enhanced through user-friendly digital thermostats that allow for precise temperature control.

Moving to the (V)G42HR/50HR, these units incorporate high-efficiency ratings and variable speed fans to adjust airflow based on heating demand. This adaptability not only increases energy savings but also improves indoor air quality by reducing the accumulation of airborne particulates. The use of high-grade insulation materials ensures minimal heat loss, providing a more consistent indoor temperature.

The (V)G42R/50R models are designed specifically for radiant heating applications. Featuring advanced radiant heat technology, these units distribute warmth evenly across the space, creating a comfortable environment without the drafts often associated with conventional heating systems. The integration of smart home technology allows for remote operation and monitoring, enhancing user convenience.

Lastly, the (V)G42H/50H models are tailored for high-capacity heating needs. These systems are built for larger spaces, offering robust heating capabilities while maintaining energy efficiency. Their construction utilizes durable materials that extend product longevity and reduce the need for frequent maintenance.

In summary, the Desa (V)G series offers a comprehensive lineup of heating solutions with advanced technology and features designed for efficiency, comfort, and adaptability. From standard models to high-capacity and radiant heating systems, each unit addresses unique heating challenges, making them suitable for diverse applications while prioritizing energy conservation and user satisfaction.