Desa 103426-01 Floor Clearances, Unvented Natural Gas Log Heater, Installation, Continued

Page 8
Floor Clearances

UNVENTED NATURAL GAS LOG HEATER

INSTALLATION

Continued

Determining Minimum Mantel Clearance When Using a Hood

If above minimum clearances are not met, you must have a hood. Follow minimum clearances shown in Figure 8 when using hood.

 

12"

 

 

 

Mantel Shelf

 

 

 

 

 

 

 

 

 

 

 

 

 

Underside of

 

10"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mantel Shelf

 

 

 

 

 

 

 

 

 

 

 

 

8"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 1/2"

 

 

 

 

 

 

 

 

All minimum

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

distances are

Minimum Non-

 

 

 

 

 

 

 

 

 

 

in inches

 

 

 

 

 

 

 

 

 

 

 

 

Combustible

 

 

 

 

 

 

 

 

 

 

 

Log Sets

Material

 

 

8"

 

12"

 

15"

18"

20"

 

18", 24",

 

 

 

 

 

 

 

 

Min.

 

 

 

 

 

 

 

& 30" Models

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Top of Fireplace

Hood

Opening

Distances to

(GA6050, GA6052)

Underside of

 

 

Mantel

Figure 8 - Minimum Mantel Clearances When Using Hood

If reasons number 1 or 2 above apply to you, you must permanently open chimney flue damper. You must install the damper clamp accessory (to order, see Accessories, page 23). This will insure vented operation (see Figure 11). The damper clamp will keep damper open. Installation instructions are included with clamp accessory.

See chart below for minimum permanent flue opening you must provide. Attach damper clamp so the minimum permanent flue opening will be maintained at all times.

Area of Various Standard Round Flues

Diameter (ins.)

Area (sq. ins.)

 

 

5"

20 sq. inches

6"

29 sq. inches

7"

39 sq. inches

8"

51 sq. inches

 

 

Chimney

Minimum Permanent

Height (ft.)

Flue Opening (sq. ins.)

 

 

6' to 15'

39 sq. inches

15' to 30'

29 sq. inches

 

 

If your installation does not meet the above minimum clearances, you must:

operate the logs only with the flue damper open, OR

raise the mantel to an acceptable height,

OR

remove the mantel.

Floor Clearances

A.If installing appliance on the floor level, you must maintain the minimum dis- tance of 14" to combustibles (see Fig- ure 9).

Hearth

Combustible Material

5"

Min.

Figure 10 - Minimum Fireplace Clearances Above Combustible Flooring

INSTALLING DAMPER CLAMP ACCESSORY FOR VENTED OPERATION

Damper

Clamp

Damper

Damper Damper Clamp

14"

Combustible Material

Note: When used as a vented heater, appli- ance must be installed only in a solid-fuel burning fireplace with a working flue and constructed of non combustible material.

Masonry Fireplace

Min.

Non-Combustible

Material

Figure 9 - Minimum Fireplace Clearances If Installed at Floor Level

B.If combustible materials are less than 14" to the fireplace, you must install appliance at least 5" above the combus- tible flooring (see Figure 10).

If your heater is a manually controlled model, you may use this heater as a vented product. There are three reasons for operating your heater in the vented mode.

1.The fireplace does not meet the clear- ance to combustibles requirements for vent-free operation.

2.State or local codes do not permit vent- free operation.

3.You prefer vented operation.

Damper

Manufactured Fireplace

Figure 11 - Attaching Damper Clamp

Continued

8

103426

Image 8
Contents OWNER’S OPERATION AND INSTALLATION MANUAL where not prohibited by state or local codesDESA INTERNATIONAL —WHAT TO DO IF YOU SMELL GASWARNINGS SAFETY INFORMATIONUNVENTED NATURAL GAS LOG HEATER PRODUCT FEATURES Safety DevicePRODUCT IDENTIFICATION LOCAL CODESAIR FOR COMBUSTION AND VENTILATION PROVIDING ADEQUATE VENTILATIONDETERMINING AIR FLOW FOR HEATER LOCATION Unusually Tight ConstructionContinued VENTILATION AIRVentilation Air From Inside Building Ventilation Air From OutdoorsINSTALLATION INSTALLATION AND CLEARANCESIf Not Using Mantel CHECK GAS TYPEIf Using Mantel Mantel ClearancesDetermining Minimum Mantel Clearance INSTALLATIONFloor Clearances INSTALLATIONUNVENTED NATURAL GAS LOG HEATER ContinuedINSTALLING HEATER BASE ASSEMBLY Installation Items NeededINSTALLATION ContinuedCONNECTING TO GAS SUPPLY INSTALLATIONInstallation Items Needed UNVENTED NATURAL GAS LOG HEATERPressure Testing Gas Supply Piping System Pressure Testing Heater Gas ConnectionsCHECKING GAS CONNECTIONS Test Pressures In Excess Of 1/2 PSIGINSTALLING LOGS American Oak Design Models INSTALLATIONUNVENTED NATURAL GAS LOG HEATER ContinuedINSTALLING LOGS Split Oak Design Models INSTALLATIONFigure 22 - Installing Bottom Middle Log Figure 24 - Installing Top Log #4Thermostat-ControlledModels FOR YOUR SAFETY OPERATING HEATERREAD BEFORE LIGHTING LIGHTING INSTRUCTIONSMANUAL LIGHTING PROCEDURE Manually-ControlledModels FOR YOUR SAFETYThermostat Controlled Models TO TURN OFF GAS TO APPLIANCEINSPECTING BURNERS Manually-ControlledModelsVARIABLE CONTROL OPERATION PILOT FLAME PATTERNCLEANING AND MAINTENANCE FRONT BURNER FLAME PATTERNODS/PILOT AND BURNERS LOGSTROUBLESHOOTING OBSERVED PROBLEMPOSSIBLE CAUSE REMEDYTROUBLESHOOTING OBSERVED PROBLEMMaintenance, page ContinuedTROUBLESHOOTING OBSERVED PROBLEMMaintenance, page UNVENTED NATURAL GAS LOG HEATEROPTIONAL POSITIONING OF THERMOSTAT SENSING BULB For Masonry and Factory- built Metal FireplaceSPECIFICATIONS REPLACEMENT PARTSSERVICE HINTS TECHNICAL SERVICEACCESSORIES MANUAL SHUTOFF VALVE - GA5010BLACK FIREPLACE HOOD - GA6050 BRASS FIREPLACE HOOD - GA6052ILLUSTRATED PARTS BREAKDOWN4 Variable Manually Controlled Models VS18NVBCFS18NVB VS24NVB CFS24NVB VS30NVB CFS30NVB UNVENTED NATURAL GAS LOG HEATERPARTS LIST Variable Manually-ControlledSplit Oak ModelsPART NUMBER FOR VS18NVB/CFS18NVBILLUSTRATED PARTS BREAKDOWN UNVENTED NATURAL GAS LOG HEATERThermostat-ControlledSplit Oak Models PARTS LISTPART NUMBER FOR VS18NTAILLUSTRATED PARTS3 BREAKDOWN Variable Manually-Controlled Models VL18NV VL24NVVL30NV UNVENTED NATURAL GAS LOG HEATERVariable Manually-ControlledAmerican Oak Models PARTS LISTPART NUMBER FOR VL18NVUNVENTED NATURAL GAS LOG HEATER Page NOT A UPC LIMITED WARRANTY VENT-FREENATURAL GAS LOG HEATERSWARRANTY INFORMATION