Desa 103426-01 Continued, Ventilation Air From Inside Building, Ventilation Air From Outdoors

Page 5
Continued

SPLIT OAK AND AMERICAN OAK DESIGN 18", 24" AND 30" MODELS

AIR FOR COMBUSTION AND VENTILATION

Continued

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

__________ Btu/Hr (maximum the

space can support)

__________ Btu/Hr (actual amount of

Btu/Hr used)

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 3). You can also remove door into adjoining room (see option 3, Figure 3). Follow the National Fuel Gas Code NFPA 54/ANSI Z223.1, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

VENTILATION AIR WARNING: Rework worksheet, adding the space of the adjoining unconfined space. The combined spaces must have enough fresh air to supply all appliances in both spaces.

Example: 51,200 Btu/Hr (maximum the space can support)

73,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a con-

Ventilation

Grills

Into Adjoining

12"

Ventilation Grills Into Adjoining Room,

Room,

Or

Option 2

Option 1

Remove

fined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventila- tion grills between rooms. See Ventila- tion Air From Inside Building.

B.Vent room directly to the outdoors. See Ventilation Air From Outdoors.

C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

Ventilation Air From Inside BuildingWARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space, provide ad- equate combustion and ventila- tion air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1, 1992, Section 5.3.

Door into Adjoining Room, Option Ventilation Air From Outdoors 3

12"

Figure 3 - Ventilation Air from Inside Building

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces.

IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostat-controlled power vent. Heated air entering the attic will activate the power vent.

Ventilated

Outlet Attic

Air

Outlet

 

Air

To Attic

 

To

Crawl

Space

Inlet

Air

Inlet Air

 

Ventilated

 

Crawl Space

 

 

Figure 4 - Ventilation Air from Outdoors

103426

5

Image 5
Contents where not prohibited by state or local codes OWNER’S OPERATION AND INSTALLATION MANUALDESA INTERNATIONAL —WHAT TO DO IF YOU SMELL GASWARNINGS SAFETY INFORMATIONUNVENTED NATURAL GAS LOG HEATER Safety Device PRODUCT FEATURESPRODUCT IDENTIFICATION LOCAL CODESPROVIDING ADEQUATE VENTILATION AIR FOR COMBUSTION AND VENTILATIONDETERMINING AIR FLOW FOR HEATER LOCATION Unusually Tight ConstructionVENTILATION AIR ContinuedVentilation Air From Inside Building Ventilation Air From OutdoorsINSTALLATION AND CLEARANCES INSTALLATIONIf Not Using Mantel CHECK GAS TYPEMantel Clearances If Using MantelDetermining Minimum Mantel Clearance INSTALLATIONINSTALLATION Floor ClearancesUNVENTED NATURAL GAS LOG HEATER ContinuedInstallation Items Needed INSTALLING HEATER BASE ASSEMBLYINSTALLATION ContinuedINSTALLATION CONNECTING TO GAS SUPPLYInstallation Items Needed UNVENTED NATURAL GAS LOG HEATERPressure Testing Heater Gas Connections Pressure Testing Gas Supply Piping SystemCHECKING GAS CONNECTIONS Test Pressures In Excess Of 1/2 PSIGINSTALLATION INSTALLING LOGS American Oak Design ModelsUNVENTED NATURAL GAS LOG HEATER ContinuedINSTALLATION INSTALLING LOGS Split Oak Design ModelsFigure 22 - Installing Bottom Middle Log Figure 24 - Installing Top Log #4OPERATING HEATER Thermostat-ControlledModels FOR YOUR SAFETYREAD BEFORE LIGHTING LIGHTING INSTRUCTIONSManually-ControlledModels FOR YOUR SAFETY MANUAL LIGHTING PROCEDUREThermostat Controlled Models TO TURN OFF GAS TO APPLIANCEManually-ControlledModels INSPECTING BURNERSVARIABLE CONTROL OPERATION PILOT FLAME PATTERNFRONT BURNER FLAME PATTERN CLEANING AND MAINTENANCEODS/PILOT AND BURNERS LOGSOBSERVED PROBLEM TROUBLESHOOTINGPOSSIBLE CAUSE REMEDYOBSERVED PROBLEM TROUBLESHOOTINGMaintenance, page ContinuedOBSERVED PROBLEM TROUBLESHOOTINGMaintenance, page UNVENTED NATURAL GAS LOG HEATERFor Masonry and Factory- built Metal Fireplace OPTIONAL POSITIONING OF THERMOSTAT SENSING BULBREPLACEMENT PARTS SPECIFICATIONSSERVICE HINTS TECHNICAL SERVICEMANUAL SHUTOFF VALVE - GA5010 ACCESSORIESBLACK FIREPLACE HOOD - GA6050 BRASS FIREPLACE HOOD - GA6052Variable Manually Controlled Models VS18NVB ILLUSTRATED PARTS BREAKDOWN4CFS18NVB VS24NVB CFS24NVB VS30NVB CFS30NVB UNVENTED NATURAL GAS LOG HEATERVariable Manually-ControlledSplit Oak Models PARTS LISTPART NUMBER FOR VS18NVB/CFS18NVBUNVENTED NATURAL GAS LOG HEATER ILLUSTRATED PARTS BREAKDOWNPARTS LIST Thermostat-ControlledSplit Oak ModelsPART NUMBER FOR VS18NTAVariable Manually-Controlled Models VL18NV VL24NV ILLUSTRATED PARTS3 BREAKDOWNVL30NV UNVENTED NATURAL GAS LOG HEATERPARTS LIST Variable Manually-ControlledAmerican Oak ModelsPART NUMBER FOR VL18NVUNVENTED NATURAL GAS LOG HEATER Page NOT A UPC LIMITED WARRANTY VENT-FREENATURAL GAS LOG HEATERSWARRANTY INFORMATION