DETERMINING AIR FLOW FOR FIREBOX LOCATION

Determining if You Have a Confined or Unconfined Space

Use this work sheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install firebox plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height). Length x Width x Height = ________cu. ft. (volume of space)

Example: Space size 22 ft. (length) x 18 ft. (width) x 8 ft. (ceiling height) = 3168 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

_____________ (volume of space) ÷ 50 cu. ft. = (Maximum Btu/Hr the space can support)

Example: 3168 cu. ft. (volume of space) ÷ 50 cu. ft. = 63.3 or 63,300 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free firebox

____________

Btu/Hr

Example:

 

 

 

Gas water heater*

____________

Btu/Hr

 

 

 

Gas water heater

 

40,000

Btu/Hr

Gas furnace

____________

Btu/Hr

 

Vent-free firebox

 

 

 

Vented gas heater

____________

Btu/Hr

+

 

 

with log heater

39,000

Btu/Hr

Gas firebox logs

____________

Btu/Hr

 

=

 

 

Total

79,000

Btu/Hr

Other gas appliances* + ____________ Btu/Hr

 

 

 

 

Total

= ____________

Btu/Hr

 

 

 

 

*Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

______________ Btu/Hr (maximum the space can support)

______________ Btu/Hr (actual amount of Btu/Hr used)

Example: 63,300 Btu/Hr (maximum the space can support) 79,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework work sheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin- ing room or add ventilation grills between rooms. See Ventilation Air from Inside Building, page 6.

B.Vent room directly to the outdoors. See Ventilation Air from Outdoors, page 6.

C.Install a lower Btu/Hr firebox, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the firebox and gas log heater may be operated is smaller than that defined as an unconfined space, provide adequate combustion and ventillation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1, 1992, Section 5.3 or applicable local codes.

Continued

103451

5

Image 5
Contents What to do if YOU Smell GAS Unvented VENT-FREEUnpacking Safety InformationLocal Codes Product SpecificationsLocating Firebox Product FeaturesAIR for Combustion and Ventilation Providing Adequate VentilationDetermining if You Have a Confined or Unconfined Space AIR for Combustion VentilationDetermining AIR Flow for Firebox Location Ventilation Air From Outdoors Ventilation AIRVentilation Air From Inside Building Installation Clearances InstallationMantel Clearances for Conventional Installation Minimum Wall and Ceiling Clearances see FigureMantel Clearances for Built-In Installation BUILT-IN Firebox InstallationAttaching Firebox to Wall Studs Installing Firebox Using Optional Accessory MantelsFor Built-in Installation of Circulating Models Only Installing GAS LineHARD-WIRING Firebox Removing Duplex Outlet Replacement Parts Technical ServiceInstalling Fireplace Screen Parts Under WarrantyCabinet Mantel Accessory with Firebox Perimeter Brass Trim AccessoriesBlower Accessory GA3700 Manual Shutoff Valve GA5010FB36NCA and FB42NC Illustrated Parts BreakdownFirebox FB36NCA and FB42NC Parts ListFB36CA and FB42C KEY Part Number Description QTY FB36CA FB42C Firebox FB36CA and FB42CVanguard Unvented VENT-FREE Logmate Firebox 103451 Warranty Information