Desa CF26NTA Ventilation AIR, Ventilation Air From Inside Building, Ventilation Air From Outdoors

Page 7

AIR FOR COMBUSTION

AND VENTILATION

Continued

The space in the above example is a confined space because the actual Btu/Hr used is more than the maxi- mum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

Ventilation

 

Grills

Or

into Adjoining

Remove

Room,

Door into

Option 1

Adjoining

 

Room,

 

Option 3

12"

Ventilation Grills

Into Adjoining Room,

Option 2

A.Rework worksheet, adding the space of an adjoin- ing room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building.

B.Vent room directly to the outdoors. See Ventila- tion Air From Outdoors.

C.Install a lower Btu/Hr fireplace, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an un- confined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be oper- ated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA54 Section 5.3 or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining un- confined space. When ventilating to an adjoining unconfined space, you must provide two perma- nent openings: one within 12” of the ceiling and one within 12” of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see option 3, Figure 2). Follow the National Fuel Gas Code ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

12"

Figure 2 - Ventilation Air from Inside Building Shown with Optional Mantel

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent openings: one within 12” of the ceiling and one within 12” of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel Gas Code ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostat- controlled power vent. Heated air entering the attic will activate the power vent.

 

 

Outlet

 

Ventilated

 

 

 

Attic

 

 

Air

 

 

 

 

 

 

 

Outlet

 

 

 

 

 

 

 

 

 

 

 

 

Air

 

 

 

 

 

 

 

 

 

 

To Attic

To

Crawl

Space

Inlet

Air

Inlet Air

 

Ventilated

 

Crawl Space

 

Figure 3 - Ventilation Air from Outdoors

Shown with Optional Mantel

113896-01B

www.desatech.com

7

Image 7
Contents What to do if YOU Smell GAS Table of Contents Safety Information Unpacking Local CodesPiezo Ignition System Product FeaturesSafety Pilot Product IdentificationConfined and Unconfined Space AIR for Combustion VentilationDetermining FRESH-AIR Flow for Fireplace Location Unusually Tight ConstructionVentilation Air From Inside Building Ventilation AIRVentilation Air From Outdoors Check GAS Type InstallationLocating Fireplace Rough Opening for Installing Wall BUILT-IN Fireplace InstallationAttaching Fireplace to Wall Studs Mantel Clearances for Built-In InstallationTrim shipped with mantel Optional Mantel InstallationRemoving Brick Liner Retainer Assembling TrimRemoving Hood Installing Blower Assembly GA3450TInstalling Blower Bracket Assembly For Built-In Installation Installation Items Needed Connecting to GAS SupplyPropane/LP Connecting Fireplace to GAS SupplyNatural From KPa Checking GAS ConnectionsTest Pressures Equal To or Less Than 1/2 Psig 3.5 kPa Test Pressures In Excess Of 1/2 PsigPressure Testing Heater GAS Connections Installing LogsOperating Fireplace For Your Safety Read Before LightingLighting Instructions Thermostat Control Operation Manual Lighting ProcedureInspecting Burners To Turn OFF GAS To ApplianceMain Burner Cleaning MaintenanceBurner Flame Pattern Burner Primary AIR HolesBlow air into the primary air holes on the injector holder CabinetObserved Problem Possible Cause Remedy TroubleshootingSee Cleaning and Mainte On windows Tilation air Gas leak. See Warning Technical Service SpecificationsReplacement Parts Service HintsModels CF26PTA and CF26NTA Illustrated Parts BreakdownParts List 20-1 11-1 20-3 11-2 KEY Part Number Description QTY Accessories Not Shown Cleaning KIT GCKCabinet Mantel with Full Hearth Base Information VideoParts Central 113896-01B Keep this Warranty Warranty InformationLimited Warranty VENT-FREE GAS BAY Front Fireplace

CF26NTA specifications

Desa CF26NTA is a highly versatile and innovative diesel generator designed to meet the power needs of various applications. With its robust construction and efficient performance, the CF26NTA serves as an ideal power solution for both residential and commercial use, particularly in regions where grid power is unreliable or unavailable.

One of the main features of the Desa CF26NTA is its powerful 26 kVA output, which provides ample energy to support multiple appliances and systems simultaneously. This generator is capable of handling the demands of larger homes, construction sites, and outdoor events, ensuring that essential functions are maintained even during power outages.

The CF26NTA utilizes advanced technology to provide reliable power while minimizing fuel consumption and emissions. Equipped with a high-efficiency diesel engine, this generator offers extended run times and an impressive fuel economy, making it a cost-effective choice for long-term power needs. The engine complies with stringent environmental regulations, ensuring that users can operate it with confidence regarding its impact on the environment.

Another notable characteristic of the Desa CF26NTA is its user-friendly control panel, which features easy-to-read gauges and indicators. This design allows operators to monitor essential parameters such as voltage, frequency, and fuel levels at a glance, facilitating efficient management of the generator's operation. Additionally, the generator is fitted with automatic voltage regulation (AVR) technology, providing stable power output and protecting connected devices from voltage fluctuations.

Portability is an essential aspect of the CF26NTA, as it is designed with a compact frame and integrated wheels for easy transportation. Whether moving it between job sites or relocating for outdoor events, users will appreciate the generator's ease of mobility without compromising its stability during operation.

The Desa CF26NTA is built to withstand the rigors of demanding environments. It features weather-resistant casing and a durable design that ensures longevity and dependability even in challenging conditions. Furthermore, its maintenance-friendly layout allows for easy access to key components, simplifying routine servicing and upkeep.

In summary, the Desa CF26NTA stands out with its robust power output, efficient diesel engine technology, user-friendly features, and portable design. It is an excellent choice for anyone in need of a reliable generator that combines performance with convenience, making it suitable for various applications, from home use to commercial settings.