DETERMINING FRESH-AIR FLOW FOR FIREPLACE LOCATION

Determining if You Have a Confined or Unconfined Space

Use this work sheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install fireplace plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height).

Length x Width x Height = _________________ cu. ft. (volume of space)

Example: Space size 22 ft. (length) x 18 ft. (width) x 8 ft. (ceiling height) = 3168 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

_________________ (volume of space) ÷ 50 cu. ft. = (Maximum Btu/Hr the space can support)

Example: 3168 cu. ft. (volume of space) ÷ 50 cu. ft. = 63.3 or 63,300 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free fireplace

 

___________________ Btu/Hr

 

 

 

 

Gas water heater*

 

___________________ Btu/Hr

Example:

 

 

 

Gas furnace

 

___________________ Btu/Hr

Gas water heater

 

40,000

Btu/Hr

Vented gas heater

 

___________________ Btu/Hr

Vent-free fireplace +

28,000

Btu/Hr

Gas fireplace logs

 

___________________ Btu/Hr

Total

=

68,000

Btu/Hr

Other gas appliances* +

___________________ Btu/Hr

 

 

 

 

Total

=

___________________ Btu/Hr

 

 

 

 

*Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_________________ Btu/Hr (maximum the space can support)

_________________ Btu/Hr (actual amount of Btu/Hr used)

Example: 63,300 Btu/Hr (maximum the space can support) 68,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework work sheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin- ing room or add ventilation grills between rooms. See Ventilation Air from Inside Building, page 6.

B.Vent room directly to the outdoors. See Ventilation Air from Outdoors, page 6.

C.Install a lower Btu/Hr fireplace, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

DETERMINING FRESH-AIR FLOW FOR FIREPLACE LOCATION WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANS Z223.1, 1992, Section 5.3 or applicable local codes.

Continued

103414

5

Image 5
Contents CGFP28P AND CGFP28PT OWNER’S OPERATION AND INSTALLATION MANUALWHAT TO DO IF YOU SMELL GAS Do not try to light any applianceCGFP28P and CGFP28PT SAFETY INFORMATIONUNVENTED PROPANE/LP GAS FIREPLACE WARNINGSUNPACKING PRODUCT IDENTIFICATIONLOCAL CODES SAFETY FEATURES PRODUCT FEATURESAIR FOR COMBUSTION AND VENTILATION OPERATIONAIR FOR COMBUSTION AND VENTILATION ContinuedDETERMINING FRESH-AIRFLOW FOR FIREPLACE LOCATION CGFP28P and CGFP28PT VENTILATION AIRUNVENTED PROPANE/LP GAS FIREPLACE AIR FOR COMBUSTION AND VENTILATIONCHECK GAS TYPE INSTALLATIONELECTRICAL HOOKUP When Using Optional Blower INSTALLATION INSTALLING GA3650T BLOWER ACCESSORYCGFP28P and CGFP28PT UNVENTED PROPANE/LP GAS FIREPLACEINSTALLATION OPERATING THE BLOWERIf your fireplace system is installed ContinuedINSTALLING GA3650T BLOWER ACCESSORY INSTALLATIONCGFP28P and CGFP28PT UNVENTED PROPANE/LP GAS FIREPLACEa. If your fireplace system is installed INSTALLATIONContinued Operating the BlowerCONVENTIONAL FIREPLACE INSTALLATION INSTALLATION CLEARANCESINSTALLATION CGFP28P and CGFP28PTCheck Local Building Codes BUILT-INFIREPLACE INSTALLATIONINSTALLATION ContinuedINSTALLATION INSTALLING GAS PIPING TO FIREPLACE LOCATIONCGFP28P and CGFP28PT UNVENTED PROPANE/LP GAS FIREPLACEPressure Testing Gas Supply Piping System CHECKING GAS CONNECTIONSPressure Testing Fireplace Gas Connections INSTALLATIONCGFP28P and CGFP28PT UNVENTED PROPANE/LP GAS FIREPLACEContinued INSTALLING LOGSINSTALLATION OPERATING FIREPLACE FOR YOUR SAFETY READ BEFORE LIGHTINGLIGHTING INSTRUCTIONS TO TURN OFF GAS TO APPLIANCETHERMOSTAT CONTROL OPERATION MANUAL LIGHTING PROCEDUREFOR YOUR SAFETY READ BEFORE LIGHTING OPERATING FIREPLACEVARIABLE MANUAL CONTROL OPERATION INSPECTING BURNERSPILOT FLAME PATTERN FRONT BURNER FLAME PATTERNLOGS CLEANING AND MAINTENANCEOBSERVED PROBLEM TROUBLESHOOTINGCGFP28P and CGFP28PT UNVENTED PROPANE/LP GAS FIREPLACEMaintenance, page TROUBLESHOOTINGContinued Refer to Air for Combustion and VentiCGFP28P and CGFP28PT TROUBLESHOOTINGUNVENTED PROPANE/LP GAS FIREPLACE ContinuedSPECIFICATIONS SERVICE HINTSTECHNICAL SERVICE PARTS CENTRALSCGFP28P ILLUSTRATED PARTS BREAKDOWNCGFP28P and CGFP28PT UNVENTED PROPANE/LP GAS FIREPLACECGFP28P PARTS LISTPART NUMBER DESCRIPTIONILLUSTRATED LOG BASE ASSEMBLYPARTS BREAKDOWNPARTS LIST LOG BASE ASSEMBLY THERMOSTAT- CONTROLLED MODELCGFP28PT CGFP28P and CGFP28PT FIREPLACEUNVENTED PROPANE/LP GAS FIREPLACE ILLUSTRATEDPARTS LIST FIREPLACE CGFP28P CGFP28PTACCESSORIES REPLACEMENT PARTSPARTS UNDER WARRANTY PARTS NOT UNDER WARRANTYPage NOT A UPC WARRANTY INFORMATIONModel Serial No Date Purchased 2701 Industrial Drive P.O. Box Bowling Green, KY